Storm overflow register · South West Water

Camels Head sewage works: storm overflow spills 2025

Camels Head sewage treatment works, run by South West Water, has 2 monitored storm overflows discharging to Weston Mill Lake(E). In 2025 they recorded 126 spills totalling 2,188 hours, against 163 spills and 2,328 hours in 2024. By hours spilling, it ranks 30 of 334 South West Water works, where 1 spilled longest.

Works size: 53,419 population equivalent (PLYMOUTH (CAMELS HEAD) STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecCamels Head WwTW4 spills, 96.6 h, 5 Jan to 9 Jan7 spills, 179.1 h, 24 Jan to 31 Jan9 spills, 101.9 h, 23 Feb to 27 Feb3 spills, 22.4 h, 15 Apr to 16 Apr3 spills, 37.4 h, 18 Apr to 20 Apr2 spills, 32.8 h, 12 Jun to 14 Jun29 Aug 2025 03:06 GMT, 13.2 h2 spills, 44.8 h, 3 Sep to 5 Sep19 Oct 2025 11:05 GMT, 5.6 h4 Nov 2025 17:54 GMT, 18.5 h6 spills, 152.2 h, 9 Nov to 16 Nov29 Nov 2025 10:11 GMT, 10.1 h20 spills, 258.5 h, 1 Dec to 12 Dec11 spills, 166.3 h, 15 Dec to 22 DecCamels Head WwTW116 spills, 93 h, 5 Jan to 9 Jan507 spills, 158.4 h, 24 Jan to 31 Jan229 spills, 90.8 h, 23 Feb to 28 Feb13 spills, 22.1 h, 15 Apr to 16 Apr40 spills, 35.9 h, 18 Apr to 20 Apr93 spills, 31.3 h, 12 Jun to 14 Jun33 spills, 12.3 h, 29 Aug to 29 Aug51 spills, 43.1 h, 3 Sep to 5 Sep11 spills, 5.3 h, 19 Oct to 19 Oct100 spills, 14.7 h, 4 Nov to 5 Nov123 spills, 148.6 h, 9 Nov to 16 Nov29 spills, 9.3 h, 29 Nov to 29 Nov262 spills, 243.6 h, 1 Dec to 12 Dec15 Dec 2025 07:41 GMT, 139.2 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0500k1M1.5M2MJan 2025: 527 h spilling ≈ 482,457 m³ (range 192,173-1.2 million m³)JanFeb 2025: 193 h spilling ≈ 176,379 m³ (range 70,255-442,807 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 118 h spilling ≈ 107,640 m³ (range 42,875-270,234 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 64 h spilling ≈ 58,671 m³ (range 23,370-147,296 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 26 h spilling ≈ 23,340 m³ (range 9,297-58,597 m³)AugSep 2025: 88 h spilling ≈ 80,455 m³ (range 32,047-201,986 m³)SepOct 2025: 11 h spilling ≈ 9,977 m³ (range 3,974-25,047 m³)OctNov 2025: 353 h spilling ≈ 323,377 m³ (range 128,808-811,851 m³)NovDec 2025: 808 h spilling ≈ 739,291 m³ (range 294,475-1.9 million m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
15 Dec 2025, 07:41Camels Head WwTW5.8 days50,744 - 319,830 m³
11 Nov 2025, 16:27Camels Head WwTW4.3 days37,443 - 235,995 m³
7 Dec 2025, 01:28Camels Head WwTW4.1 days35,693 - 224,965 m³
26 Jan 2025, 18:35Camels Head WwTW3.0 days25,819 - 162,730 m³
5 Jan 2025, 02:19Camels Head WwTW2.9 days25,649 - 161,658 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate2.0 million m³range 797,748 - 5.0 million m³
In litres2.0 billionrange 797.7 million - 5.0 billion L
Olympic swimming pools801at 2,500 m³ each
Organic load, as people's raw sewage3.0 millionperson-days of untreated BOD

Assumed spill rate while spilling: 101.3 - 638.3 L/s (central 254.3 L/s), from a dry-weather flow of 101.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 31,910 kg180,250 kg1.0 million kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 83,764 kg851,180 kg3.6 million kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1,516 kg12,617 kg46,761 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 957 kg5,207 kg27,151 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 79.8 trillion organisms2.0 × 10¹⁵ organisms5.0 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Camels Head WwTW

Storm tank at sewage works · discharges to Weston Mill Lake(E)

Spills 2025
63 (1,139 hours) · down 25% on 2024
Spills 2024
84 (1,296 hours)
Long-term average
73.4 spills a year (monitored since 2016)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Not part of a WFD catchment
Outlet location
SX44665714 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00207 · 303000 · company name: CAMELS HEAD STW_SSO_PLYMOUTH

Camels Head WwTW

Inlet overflow at sewage works · discharges to Weston Mill Lake(E)

Spills 2025
63 (1,049 hours) · down 20% on 2024
Spills 2024
79 (1,032 hours)
Long-term average
74.0 spills a year (monitored since 2017)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Not part of a WFD catchment
Outlet location
SX44665714 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00206 · 303000 · company name: CAMELS HEAD STW_SO_PLYMOUTH

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.