Storm overflow register · South West Water

Crowsnest sewage works: storm overflow spills 2025

Crowsnest sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to River Seaton (S). In 2025 it recorded 40 spills totalling 184 hours, against 73 spills and 819 hours in 2024. By hours spilling, it ranks 237 of 334 South West Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecCrowsnest STW23 Jan 2025 10:11 GMT, 6 min26 Jan 2025 09:32 GMT, 11 min26 Jan 2025 10:53 GMT, 24 min26 Jan 2025 12:30 GMT, 29 min26 Jan 2025 20:43 GMT, 28 min26 Jan 2025 21:43 GMT, 9 min28 Jan 2025 03:51 GMT, 13 min28 Jan 2025 04:26 GMT, 4 min23 Feb 2025 17:41 GMT, 110 min23 Feb 2025 19:42 GMT, 26 min23 Feb 2025 20:50 GMT, 18 min24 Feb 2025 06:12 GMT, 5 min24 Feb 2025 23:28 GMT, 8 min26 Feb 2025 04:23 GMT, 14 min26 Feb 2025 05:18 GMT, 6 min26 Feb 2025 05:32 GMT, 18 min26 Feb 2025 05:54 GMT, 53 min15 Apr 2025 12:44 GMT, 3 min15 Apr 2025 13:24 GMT, 32 min7 Jun 2025 11:30 GMT, 39 min7 Jun 2025 12:58 GMT, 8 min19 Jul 2025 21:54 GMT, 7 min25 Jul 2025 08:36 GMT, 16 min25 Jul 2025 10:01 GMT, 7 min25 Jul 2025 11:58 GMT, 106 min26 Jul 2025 09:22 GMT, 18 min26 Jul 2025 12:50 GMT, 11 min26 Jul 2025 16:31 GMT, 4.9 h26 Jul 2025 21:53 GMT, 21 min28 Aug 2025 22:49 GMT, 3 min7 Sep 2025 10:24 GMT, 5 min9 Sep 2025 19:08 GMT, 8 min30 Oct 2025 20:44 GMT, 6 min4 Nov 2025 09:31 GMT, 3 h4 Nov 2025 12:58 GMT, 54 min4 Nov 2025 14:31 GMT, 76 min4 Nov 2025 15:59 GMT, 21 min4 Nov 2025 17:17 GMT, 2.4 h4 Nov 2025 23:06 GMT, 8 min4 Nov 2025 23:51 GMT, 13 min5 Nov 2025 20:56 GMT, 8 min6 Nov 2025 07:46 GMT, 41 min6 Nov 2025 09:12 GMT, 37.4 h8 Nov 2025 08:16 GMT, 8.8 h9 Nov 2025 11:33 GMT, 2.3 h9 Nov 2025 14:00 GMT, 34 min10 Nov 2025 09:27 GMT, 17 min11 Nov 2025 16:11 GMT, 10 min11 Nov 2025 16:27 GMT, 27 min11 Nov 2025 17:13 GMT, 16 min12 Nov 2025 03:29 GMT, 106 min12 Nov 2025 07:48 GMT, 30.3 h14 Nov 2025 13:29 GMT, 26 min22 Nov 2025 08:36 GMT, 10 min22 Nov 2025 08:54 GMT, 41 min22 Nov 2025 09:48 GMT, 88 min23 Nov 2025 01:04 GMT, 20 min23 Nov 2025 01:47 GMT, 25 min23 Nov 2025 02:15 GMT, 27 min23 Nov 2025 03:30 GMT, 22 min24 Nov 2025 00:07 GMT, 30 min24 Nov 2025 05:46 GMT, 15 min24 Nov 2025 07:17 GMT, 54 min24 Nov 2025 11:04 GMT, 28 min25 Nov 2025 17:40 GMT, 24 min25 Nov 2025 18:47 GMT, 6 min25 Nov 2025 19:00 GMT, 16 min26 Nov 2025 10:16 GMT, 18 min26 Nov 2025 11:32 GMT, 5 min27 Nov 2025 17:53 GMT, 7 min29 Nov 2025 01:13 GMT, 5.1 h29 Nov 2025 08:22 GMT, 54 min29 Nov 2025 16:33 GMT, 94 min29 Nov 2025 18:25 GMT, 64 min30 Nov 2025 10:07 GMT, 13 min30 Nov 2025 20:46 GMT, 19.1 h1 Dec 2025 16:33 GMT, 40.6 h

Hours spilling by month, 2025

050100150Jan 2025: 2.1 hours spillingJanFeb 2025: 4.3 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 0.6 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 0.8 hours spillingJunJul 2025: 8.0 hours spillingJulAug 2025: 0.1 hours spillingAugSep 2025: 0.2 hours spillingSepOct 2025: 0.1 hours spillingOctNov 2025: 111 hours spillingNovDec 2025: 57 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
1 Dec 2025, 16:33Crowsnest STW1.7 days
6 Nov 2025, 09:12Crowsnest STW1.6 days
12 Nov 2025, 07:48Crowsnest STW1.3 days
30 Nov 2025, 20:46Crowsnest STW19.1 h
8 Nov 2025, 08:16Crowsnest STW8.8 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate3,148 m³range 1,254 – 7,902 m³
In litres3.1 millionrange 1.3 million – 7.9 million L
Olympic swimming pools1.3at 2,500 m³ each
Organic load, as people's raw sewage4,721person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 50 kg283 kg1,580 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 132 kg1,338 kg5,697 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 2.4 kg20 kg73 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1.5 kg8.2 kg43 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 125.4 billion organisms3.1 trillion organisms79.0 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Crowsnest STW

Inlet overflow at sewage works · discharges to River Seaton (S)

Spills 2025
40 (184 hours) · down 45% on 2024
Spills 2024
73 (819 hours)
Long-term average
53.8 spills a year (monitored since 2021)
Monitor uptime
95% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Seaton (GB108048002320)
Outlet location
SX26406920 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00330 · 302123 · company name: CROWS NEST STW_SO_DARITE

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.