Storm overflow register · South West Water

Folly Gate sewage works: storm overflow spills 2025

Folly Gate sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to Trib of Beckamoor Brook. In 2025 it recorded 126 spills totalling 2,580 hours, against 200 spills and 4,175 hours in 2024. By hours spilling, it ranks 17 of 334 South West Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFolly Gate WwTW SSO1 Jan 2025 08:14 GMT, 340.5 h15 Jan 2025 14:26 GMT, 19.2 h24 Jan 2025 01:56 GMT, 7.2 h24 Jan 2025 21:45 GMT, 10.6 h25 Jan 2025 22:46 GMT, 9.1 h26 Jan 2025 10:33 GMT, 21.9 h27 Jan 2025 08:40 GMT, 2 min27 Jan 2025 09:35 GMT, 27 min27 Jan 2025 10:20 GMT, 3 min27 Jan 2025 10:41 GMT, 2 min27 Jan 2025 11:01 GMT, 30 min27 Jan 2025 12:32 GMT, 25 min27 Jan 2025 13:59 GMT, 17 min27 Jan 2025 14:52 GMT, 2 min27 Jan 2025 15:14 GMT, 45.4 h29 Jan 2025 14:08 GMT, 20 h30 Jan 2025 11:20 GMT, 74.1 h2 Feb 2025 19:12 GMT, 39.3 h5 Feb 2025 08:19 GMT, 40.8 h7 Feb 2025 06:56 GMT, 5.8 h15 Feb 2025 12:13 GMT, 12.2 h16 Feb 2025 09:43 GMT, 3.7 h16 Feb 2025 13:46 GMT, 42 min20 Feb 2025 13:13 GMT, 48.8 h22 Feb 2025 15:21 GMT, 19.8 h23 Feb 2025 13:01 GMT, 24.6 h24 Feb 2025 14:42 GMT, 17.7 h25 Feb 2025 10:25 GMT, 102 min25 Feb 2025 22:31 GMT, 9.8 h26 Feb 2025 08:28 GMT, 45 min26 Feb 2025 09:22 GMT, 10 min26 Feb 2025 09:42 GMT, 10 min26 Feb 2025 10:03 GMT, 75.2 h1 Mar 2025 18:23 GMT, 16.4 h3 Mar 2025 06:30 GMT, 5.4 h15 Apr 2025 14:43 GMT, 66.3 h18 Apr 2025 10:55 GMT, 59.6 h23 Apr 2025 09:29 GMT, 39 min23 Apr 2025 16:56 GMT, 5.3 h24 Apr 2025 08:40 GMT, 30 min27 May 2025 11:30 GMT, 3.6 h27 May 2025 17:04 GMT, 34 min12 Jun 2025 09:47 GMT, 17.3 h13 Jun 2025 07:14 GMT, 67 min13 Jun 2025 13:24 GMT, 69.2 h16 Jun 2025 12:31 GMT, 10.4 h23 Oct 2025 08:58 GMT, 52 min23 Oct 2025 17:12 GMT, 18.2 h24 Oct 2025 11:45 GMT, 73.3 h27 Oct 2025 16:03 GMT, 42.8 h29 Oct 2025 11:53 GMT, 24.7 h30 Oct 2025 14:55 GMT, 20.5 h31 Oct 2025 12:01 GMT, 72.6 h3 Nov 2025 13:26 GMT, 25 h4 Nov 2025 14:35 GMT, 43.7 h6 Nov 2025 10:27 GMT, 27 h7 Nov 2025 14:04 GMT, 69.9 h10 Nov 2025 12:05 GMT, 21.4 h11 Nov 2025 14:19 GMT, 44.4 h13 Nov 2025 10:47 GMT, 26.2 h14 Nov 2025 13:01 GMT, 68.4 h17 Nov 2025 09:29 GMT, 97.3 h21 Nov 2025 13:33 GMT, 19.7 h22 Nov 2025 10:37 GMT, 6.5 h23 Nov 2025 02:23 GMT, 7.5 h23 Nov 2025 10:07 GMT, 49.8 h25 Nov 2025 15:01 GMT, 44.5 h27 Nov 2025 11:43 GMT, 26.2 h1 Dec 2025 14:36 GMT, 212.5 h10 Dec 2025 13:33 GMT, 21.3 h11 Dec 2025 11:02 GMT, 22.1 h12 Dec 2025 09:14 GMT, 73.9 h15 Dec 2025 11:15 GMT, 214.4 h24 Dec 2025 12:57 GMT, 86 h28 Dec 2025 08:52 GMT, 6.9 h28 Dec 2025 20:19 GMT, 53 min29 Dec 2025 09:38 GMT, 3.8 h29 Dec 2025 18:30 GMT, 65 min

Hours spilling by month, 2025

0200400600800Jan 2025: 512 hours spillingJanFeb 2025: 325 hours spillingFebMar 2025: 35 hours spillingMarApr 2025: 132 hours spillingAprMay 2025: 4.1 hours spillingMayJun 2025: 98 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 0.0 hours spillingSepOct 2025: 192 hours spillingOctNov 2025: 638 hours spillingNovDec 2025: 643 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
1 Jan 2025, 08:14Folly Gate WwTW SSO14.2 days
15 Dec 2025, 11:15Folly Gate WwTW SSO8.9 days
1 Dec 2025, 14:36Folly Gate WwTW SSO8.9 days
17 Nov 2025, 09:29Folly Gate WwTW SSO4.1 days
24 Dec 2025, 12:57Folly Gate WwTW SSO3.6 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate44,210 m³range 17,610 – 110,992 m³
In litres44.2 millionrange 17.6 million – 111.0 million L
Olympic swimming pools18at 2,500 m³ each
Organic load, as people's raw sewage66,315person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 704 kg3,979 kg22,198 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,849 kg18,789 kg80,025 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 33 kg279 kg1,032 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 21 kg115 kg599 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.8 trillion organisms44.2 trillion organisms1.1 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Folly Gate WwTW SSO

Storm tank at sewage works · discharges to Trib of Beckamoor Brook

Spills 2025
126 (2,580 hours) · down 37% on 2024
Spills 2024
200 (4,175 hours)
Long-term average
127.8 spills a year (monitored since 2022)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Middle River Okement (GB108050008110)
Outlet location
SX57269811 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00464 · NRA-SW-1243 · company name: FOLLY GATE STW_SSO_FOLLY GATE

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.