Storm overflow register · South West Water

Lamerton sewage works: storm overflow spills 2025

Lamerton sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to River Lumburn (S). In 2025 it recorded 109 spills totalling 2,168 hours, against 139 spills and 2,776 hours in 2024. By hours spilling, it ranks 31 of 334 South West Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecLamerton STW1 Jan 2025 16:35 GMT, 7.8 h4 Jan 2025 21:31 GMT, 221.6 h14 Jan 2025 09:50 GMT, 14.3 h23 Jan 2025 10:49 GMT, 3.4 h24 Jan 2025 01:26 GMT, 51.4 h26 Jan 2025 08:26 GMT, 70.7 h29 Jan 2025 07:11 GMT, 42.2 h31 Jan 2025 02:30 GMT, 2.2 h31 Jan 2025 04:47 GMT, 8 min31 Jan 2025 05:01 GMT, 68 min31 Jan 2025 06:23 GMT, 1 min31 Jan 2025 07:27 GMT, 4 min31 Jan 2025 07:32 GMT, 3 h31 Jan 2025 13:34 GMT, 3 h31 Jan 2025 17:35 GMT, 2 min31 Jan 2025 18:16 GMT, 10 min31 Jan 2025 18:30 GMT, 2 min31 Jan 2025 19:00 GMT, 5 min31 Jan 2025 19:37 GMT, 16 min31 Jan 2025 20:54 GMT, 18 min31 Jan 2025 21:42 GMT, 7 min1 Feb 2025 05:59 GMT, 2 min1 Feb 2025 09:09 GMT, 86 min1 Feb 2025 12:24 GMT, 2 min1 Feb 2025 12:40 GMT, 4 min1 Feb 2025 12:50 GMT, 2 min1 Feb 2025 13:27 GMT, 67 min1 Feb 2025 14:48 GMT, 16 min1 Feb 2025 15:15 GMT, 15 min1 Feb 2025 15:42 GMT, 1 min1 Feb 2025 15:49 GMT, 19 min1 Feb 2025 16:19 GMT, 8 min1 Feb 2025 16:34 GMT, 6 min1 Feb 2025 16:43 GMT, 19 min1 Feb 2025 17:10 GMT, 2 min1 Feb 2025 17:52 GMT, 1 min1 Feb 2025 18:35 GMT, 16 min1 Feb 2025 19:09 GMT, 57.5 h4 Feb 2025 07:53 GMT, 18 h19 Feb 2025 20:40 GMT, 65.8 h22 Feb 2025 14:53 GMT, 7 min22 Feb 2025 15:21 GMT, 16 min22 Feb 2025 23:04 GMT, 218.6 h15 Apr 2025 13:16 GMT, 2.7 h16 Apr 2025 01:17 GMT, 4.1 h18 Apr 2025 14:53 GMT, 16 min18 Apr 2025 15:11 GMT, 24.3 h22 Apr 2025 21:45 GMT, 2.4 h7 Jun 2025 12:17 GMT, 2.8 h12 Jun 2025 09:55 GMT, 4.5 h13 Jun 2025 16:46 GMT, 5.8 h28 Aug 2025 23:52 GMT, 20 min3 Sep 2025 09:48 GMT, 3.1 h19 Oct 2025 06:29 GMT, 16.9 h20 Oct 2025 06:07 GMT, 34 h23 Oct 2025 08:22 GMT, 17.7 h24 Oct 2025 07:57 GMT, 17.3 h4 Nov 2025 12:03 GMT, 57.8 h9 Nov 2025 13:19 GMT, 38.3 h11 Nov 2025 04:23 GMT, 1148.9 h

Hours spilling by month, 2025

0200400600800Jan 2025: 422 hours spillingJanFeb 2025: 291 hours spillingFebMar 2025: 74 hours spillingMarApr 2025: 34 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 13 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.3 hours spillingAugSep 2025: 3.1 hours spillingSepOct 2025: 86 hours spillingOctNov 2025: 572 hours spillingNovDec 2025: 673 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
11 Nov 2025, 04:23Lamerton STW47.9 days
4 Jan 2025, 21:31Lamerton STW9.2 days
22 Feb 2025, 23:04Lamerton STW9.1 days
26 Jan 2025, 08:26Lamerton STW2.9 days
19 Feb 2025, 20:40Lamerton STW2.7 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate37,139 m³range 14,793 – 93,239 m³
In litres37.1 millionrange 14.8 million – 93.2 million L
Olympic swimming pools15at 2,500 m³ each
Organic load, as people's raw sewage55,708person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 592 kg3,342 kg18,648 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,553 kg15,784 kg67,225 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 28 kg234 kg867 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 18 kg97 kg503 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.5 trillion organisms37.1 trillion organisms932.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Lamerton STW

Inlet overflow at sewage works · discharges to River Lumburn (S)

Spills 2025
109 (2,167 hours) · down 22% on 2024
Spills 2024
139 (2,776 hours)
Long-term average
118.8 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Lumburn (GB108047007850)
Outlet location
SX45387556 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00658 · 302128 · company name: LAMERTON STW_SO_LAMERTON

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.