Millbrook sewage works: storm overflow spills 2025

Millbrook sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to Millbrook Lake. In 2025 it recorded 66 spills totalling 847 hours, against 27 spills and 360 hours in 2024. By hours spilling, it ranks 129 of 334 South West Water works, where 1 spilled longest.

Works size: 3,644 population equivalent (MILLBROOK STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMillbrook STW477 spills, 31.1 h, 4 Jan to 8 Jan24 Jan 2025 05:16 GMT, 9.7 h26 Jan 2025 11:44 GMT, 61.6 h431 spills, 53.6 h, 30 Jan to 3 Feb18 spills, 1.3 h, 4 Feb to 4 Feb305 spills, 91.7 h, 23 Feb to 1 Mar3 spills, 15.8 h, 15 Apr to 16 Apr5 spills, 19.5 h, 18 Apr to 19 Apr12 Jun 2025 10:18 GMT, 4.7 h2 spills, 4.1 h, 13 Jun to 13 Jun3 spills, 5.1 h, 29 Aug to 29 Aug13 spills, 38.4 h, 3 Sep to 5 Sep4 spills, 2.3 h, 9 Sep to 9 Sep12 spills, 19.3 h, 23 Sep to 24 Sep517 spills, 180.6 h, 9 Nov to 19 Nov21 spills, 209.1 h, 1 Dec to 10 Dec11 Dec 2025 22:35 GMT, 23.4 h14 Dec 2025 22:13 GMT, 71.8 h25 Dec 2025 19:33 GMT, 5.3 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60kJan 2025: 127 h spilling ≈ 7,948 m³ (range 3,166-19,955 m³)JanFeb 2025: 119 h spilling ≈ 7,405 m³ (range 2,950-18,591 m³)FebMar 2025: 3.1 h spilling ≈ 194 m³ (range 77-486 m³)MarApr 2025: 35 h spilling ≈ 2,204 m³ (range 878-5,533 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 8.8 h spilling ≈ 549 m³ (range 219-1,379 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 5.1 h spilling ≈ 318 m³ (range 127-799 m³)AugSep 2025: 60 h spilling ≈ 3,740 m³ (range 1,490-9,389 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 181 h spilling ≈ 11,276 m³ (range 4,492-28,310 m³)NovDec 2025: 310 h spilling ≈ 19,325 m³ (range 7,697-48,515 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
4 Dec 2025, 15:16Millbrook STW3.3 days1,957 - 12,334 m³
14 Dec 2025, 22:13Millbrook STW3.0 days1,784 - 11,247 m³
13 Nov 2025, 14:41Millbrook STW2.9 days1,730 - 10,902 m³
26 Jan 2025, 11:44Millbrook STW2.6 days1,533 - 9,661 m³
7 Dec 2025, 22:02Millbrook STW1.7 days1,024 - 6,456 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate52,904 m³range 21,073 - 132,817 m³
In litres52.9 millionrange 21.1 million - 132.8 million L
Olympic swimming pools21at 2,500 m³ each
Organic load, as people's raw sewage79,355person-days of untreated BOD

Assumed spill rate while spilling: 6.9 - 43.5 L/s (central 17.3 L/s), from a dry-weather flow of 6.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 843 kg4,761 kg26,563 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,213 kg22,484 kg95,761 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 40 kg333 kg1,235 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 25 kg138 kg717 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.1 trillion organisms52.9 trillion organisms1.3 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Millbrook STW

Storm tank at sewage works · discharges to Millbrook Lake

Spills 2025
66 (847 hours) · up 144% on 2024
Spills 2024
27 (360 hours)
Long-term average
30.0 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Operational investigation completed
Improvement
Operational improvement ongoing
WFD catchment
Not part of a WFD catchment
Outlet location
SX43555229 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB00784 · NRA-SW-7829/FN/1 · company name: MILLBROOK STW_SSO_MILLBROOK

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.