Storm overflow register · South West Water

St Cleer sewage works: storm overflow spills 2025

St Cleer sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to Tremar Stream. In 2025 it recorded 67 spills totalling 1,096 hours, against 125 spills and 2,324 hours in 2024. By hours spilling, it ranks 101 of 334 South West Water works, where 1 spilled longest.

Works size: 2,578 population equivalent (ST CLEER STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSt Cleer Wastewater…8 spills, 176.2 h, 4 Jan to 13 Jan24 Jan 2025 02:13 GMT, 8.3 h8 spills, 46.3 h, 26 Jan to 28 Jan19 Feb 2025 20:55 GMT, 98 min21 Feb 2025 09:39 GMT, 5.2 h4 spills, 33.8 h, 23 Feb to 25 Feb2 spills, 17.5 h, 26 Feb to 26 Feb2 spills, 0.9 h, 15 Apr to 15 Apr2 spills, 11.4 h, 18 Apr to 19 Apr7 Jun 2025 13:22 GMT, 62 min2 spills, 5 h, 19 Oct to 19 Oct2 spills, 17.1 h, 4 Nov to 5 Nov9 Nov 2025 14:16 GMT, 5.5 h3 spills, 19 h, 12 Nov to 13 Nov5 spills, 27.6 h, 13 Nov to 15 Nov10 spills, 42.1 h, 22 Nov to 24 Nov3 spills, 8.6 h, 29 Nov to 29 Nov3 spills, 668.6 h, 1 Dec to 29 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60k80kJan 2025: 231 h spilling ≈ 10,195 m³ (range 4,061-25,595 m³)JanFeb 2025: 58 h spilling ≈ 2,566 m³ (range 1,022-6,443 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 12 h spilling ≈ 543 m³ (range 216-1,364 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 1.0 h spilling ≈ 44 m³ (range 18-111 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 5.0 h spilling ≈ 221 m³ (range 88-554 m³)OctNov 2025: 120 h spilling ≈ 5,296 m³ (range 2,110-13,297 m³)NovDec 2025: 669 h spilling ≈ 29,534 m³ (range 11,764-74,146 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
3 Dec 2025, 07:03St Cleer Wastewater Treatment Works25.7 days10,868 - 68,497 m³
4 Jan 2025, 21:44St Cleer Wastewater Treatment Works3.1 days1,316 - 8,291 m³
1 Dec 2025, 02:04St Cleer Wastewater Treatment Works2.0 days828 - 5,216 m³
10 Jan 2025, 05:44St Cleer Wastewater Treatment Works1.8 days768 - 4,841 m³
23 Feb 2025, 12:41St Cleer Wastewater Treatment Works1.1 days461 - 2,906 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate48,404 m³range 19,280 - 121,521 m³
In litres48.4 millionrange 19.3 million - 121.5 million L
Olympic swimming pools19at 2,500 m³ each
Organic load, as people's raw sewage72,606person-days of untreated BOD

Assumed spill rate while spilling: 4.9 - 30.8 L/s (central 12.3 L/s), from a dry-weather flow of 4.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 771 kg4,356 kg24,304 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,024 kg20,572 kg87,617 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 37 kg305 kg1,130 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 23 kg126 kg656 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.9 trillion organisms48.4 trillion organisms1.2 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

St Cleer Wastewater Treatment Works

Storm tank at sewage works · discharges to Tremar Stream

Spills 2025
67 (1,096 hours) · down 46% on 2024
Spills 2024
125 (2,324 hours)
Long-term average
94.9 spills a year (monitored since 2017)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
UWWTR improvement completed
WFD catchment
Seaton (GB108048002320)
Outlet location
SX26036791 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB01124 · 302956 · company name: ST CLEER STW_SSO_LISKEARD

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.