Storm overflow register · South West Water

Tatworth sewage works: storm overflow spills 2025

Tatworth sewage treatment works, run by South West Water, has 2 monitored storm overflows discharging to Forton Brook. In 2025 they recorded 243 spills totalling 4,452 hours, against 274 spills and 4,531 hours in 2024. By hours spilling, it ranks 3 of 334 South West Water works, where 1 spilled longest.

Works size: 2,403 population equivalent (TATWORTH STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecTatworth WwTW29 spills, 1555.8 h, 2 Jan to 10 Mar18 spills, 408.2 h, 15 Mar to 1 Apr69 spills, 758.8 h, 3 Apr to 5 May29 Aug 2025 02:20 GMT, 4.4 h3 Sep 2025 00:28 GMT, 17.5 h7 Sep 2025 08:27 GMT, 14.3 h9 Sep 2025 21:06 GMT, 30.2 h13 Sep 2025 12:32 GMT, 6.4 h19 Oct 2025 09:36 GMT, 42.7 h22 Oct 2025 18:55 GMT, 33 h4 spills, 50.1 h, 31 Oct to 3 Nov4 spills, 80.8 h, 4 Nov to 8 Nov9 Nov 2025 16:26 GMT, 201.7 h9 spills, 937.8 h, 22 Nov to 31 DecTatworth WwTW3 spills, 34 h, 4 Jan to 6 Jan2 spills, 10.1 h, 23 Jan to 24 Jan4 spills, 63.6 h, 26 Jan to 28 Jan4 spills, 8.5 h, 19 Feb to 20 Feb21 Feb 2025 11:33 GMT, 29 min2 spills, 20.8 h, 23 Feb to 25 Feb4 spills, 10.2 h, 26 Feb to 26 Feb15 Apr 2025 15:53 GMT, 7 min4 spills, 9.7 h, 18 Apr to 19 Apr22 Apr 2025 23:25 GMT, 98 min6 Jun 2025 19:35 GMT, 15 min12 Jun 2025 08:25 GMT, 56 min19 Jul 2025 23:52 GMT, 37 min27 Jul 2025 17:34 GMT, 33 min29 Aug 2025 01:24 GMT, 61 min3 spills, 0.9 h, 2 Sep to 3 Sep7 Sep 2025 07:08 GMT, 2.1 h3 spills, 1.4 h, 9 Sep to 10 Sep19 Oct 2025 08:24 GMT, 20 min2 spills, 0.5 h, 22 Oct to 22 Oct31 Oct 2025 22:44 GMT, 46 min4 Nov 2025 16:16 GMT, 70 min2 spills, 1.6 h, 9 Nov to 10 Nov2 spills, 16.5 h, 11 Nov to 12 Nov2 spills, 11.1 h, 13 Nov to 14 Nov2 spills, 5.3 h, 22 Nov to 22 Nov29 Nov 2025 05:43 GMT, 9 min3 spills, 16.3 h, 1 Dec to 2 Dec2 spills, 8 h, 4 Dec to 4 Dec5 spills, 18 h, 5 Dec to 7 Dec8 Dec 2025 21:32 GMT, 25.3 h12 Dec 2025 06:14 GMT, 69 min2 spills, 11.9 h, 15 Dec to 16 Dec3 spills, 25.4 h, 17 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

025k50k75k100kJan 2025: 780 h spilling ≈ 32,124 m³ (range 12,796-80,649 m³)JanFeb 2025: 709 h spilling ≈ 29,184 m³ (range 11,625-73,268 m³)FebMar 2025: 610 h spilling ≈ 25,124 m³ (range 10,008-63,076 m³)MarApr 2025: 679 h spilling ≈ 27,965 m³ (range 11,139-70,208 m³)AprMay 2025: 103 h spilling ≈ 4,249 m³ (range 1,693-10,668 m³)MayJun 2025: 1.2 h spilling ≈ 49 m³ (range 20-124 m³)JunJul 2025: 1.2 h spilling ≈ 49 m³ (range 20-124 m³)JulAug 2025: 5.3 h spilling ≈ 218 m³ (range 87-548 m³)AugSep 2025: 73 h spilling ≈ 2,997 m³ (range 1,194-7,525 m³)SepOct 2025: 77 h spilling ≈ 3,183 m³ (range 1,268-7,990 m³)OctNov 2025: 566 h spilling ≈ 23,292 m³ (range 9,278-58,476 m³)NovDec 2025: 846 h spilling ≈ 34,846 m³ (range 13,880-87,481 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
27 Jan 2025, 04:27Tatworth WwTW19.3 days7,595 - 47,870 m³
15 Dec 2025, 11:58Tatworth WwTW16.5 days6,495 - 40,936 m³
2 Dec 2025, 19:22Tatworth WwTW12.7 days4,996 - 31,486 m³
4 Jan 2025, 20:17Tatworth WwTW9.4 days3,686 - 23,234 m³
15 Feb 2025, 11:35Tatworth WwTW8.6 days3,369 - 21,235 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate183,290 m³range 73,008 - 460,158 m³
In litres183.3 millionrange 73.0 million - 460.2 million L
Olympic swimming pools73at 2,500 m³ each
Organic load, as people's raw sewage274,936person-days of untreated BOD

Assumed spill rate while spilling: 4.6 - 28.7 L/s (central 11.4 L/s), from a dry-weather flow of 4.6 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,920 kg16,496 kg92,032 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 7,666 kg77,898 kg331,774 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 139 kg1,155 kg4,279 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 88 kg477 kg2,485 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 7.3 trillion organisms183.3 trillion organisms4.6 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Tatworth WwTW

Storm tank at sewage works · discharges to Forton Brook

Spills 2025
189 (4,141 hours) · down 10% on 2024
Spills 2024
210 (4,137 hours)
Long-term average
134.7 spills a year (monitored since 2018)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Forton Brook (GB108045014820)
Outlet location
ST33710479 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB01209 · 203249 · company name: TATWORTH STW_SSO_TATWORTH

Tatworth WwTW

Inlet overflow at sewage works · discharges to Forton Brook

Spills 2025
54 (310 hours) · down 16% on 2024
Spills 2024
64 (394 hours)
Long-term average
55.4 spills a year (monitored since 2018)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Forton Brook (GB108045014820)
Outlet location
ST33680481 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB01208 · 203249 · company name: TATWORTH STW_SO_TATWORTH

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.