Storm overflow register · South West Water

West Charleton sewage works: storm overflow spills 2025

West Charleton sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to Charleton Stream(S). In 2025 it recorded 46 spills totalling 391 hours, against 73 spills and 1,003 hours in 2024. By hours spilling, it ranks 196 of 334 South West Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWest Charleton STW1 Jan 2025 14:49 GMT, 2.1 h4 Jan 2025 23:29 GMT, 2.5 h5 Jan 2025 03:00 GMT, 45 min5 Jan 2025 03:57 GMT, 5.5 h5 Jan 2025 12:13 GMT, 61 min5 Jan 2025 23:42 GMT, 93 min6 Jan 2025 02:43 GMT, 39 min6 Jan 2025 15:01 GMT, 68 min6 Jan 2025 17:55 GMT, 90 min8 Jan 2025 10:41 GMT, 8.9 h10 Jan 2025 06:14 GMT, 46 min22 Jan 2025 00:17 GMT, 43 min24 Jan 2025 02:52 GMT, 3.6 h24 Jan 2025 21:32 GMT, 107 min25 Jan 2025 23:47 GMT, 2.5 h26 Jan 2025 08:57 GMT, 3.2 h26 Jan 2025 12:45 GMT, 60 min26 Jan 2025 19:13 GMT, 4.9 h27 Jan 2025 06:21 GMT, 83 min27 Jan 2025 10:03 GMT, 116 min27 Jan 2025 19:43 GMT, 62 min27 Jan 2025 23:16 GMT, 43 min28 Jan 2025 13:17 GMT, 3 h28 Jan 2025 19:50 GMT, 39 min29 Jan 2025 10:47 GMT, 12.2 h31 Jan 2025 04:33 GMT, 10 h1 Feb 2025 10:32 GMT, 3 h23 Feb 2025 22:35 GMT, 2.4 h24 Feb 2025 01:05 GMT, 114 min24 Feb 2025 03:28 GMT, 2.3 h24 Feb 2025 22:10 GMT, 4.7 h26 Feb 2025 07:11 GMT, 105 min9 Mar 2025 20:24 GMT, 95 min15 Apr 2025 20:48 GMT, 6.2 h18 Apr 2025 07:57 GMT, 45 min18 Apr 2025 09:23 GMT, 45 min18 Apr 2025 10:52 GMT, 89 min18 Apr 2025 19:40 GMT, 2.3 h12 Jun 2025 05:11 GMT, 36 min12 Jun 2025 05:59 GMT, 42 min12 Jun 2025 07:04 GMT, 4.4 h29 Aug 2025 00:44 GMT, 61 min2 Sep 2025 23:55 GMT, 114 min11 Nov 2025 21:08 GMT, 55 min1 Dec 2025 16:33 GMT, 63 min1 Dec 2025 18:41 GMT, 116 min5 Dec 2025 16:19 GMT, 68 min6 Dec 2025 00:20 GMT, 35 min7 Dec 2025 05:14 GMT, 35 min7 Dec 2025 06:40 GMT, 26 min7 Dec 2025 09:59 GMT, 99 min8 Dec 2025 21:42 GMT, 5.8 h9 Dec 2025 04:20 GMT, 46 min11 Dec 2025 21:13 GMT, 17 min12 Dec 2025 01:31 GMT, 59 min12 Dec 2025 02:45 GMT, 3.2 h12 Dec 2025 08:11 GMT, 5.5 h15 Dec 2025 03:34 GMT, 217.2 h24 Dec 2025 07:53 GMT, 36.1 h

Hours spilling by month, 2025

0100200300Jan 2025: 75 hours spillingJanFeb 2025: 16 hours spillingFebMar 2025: 1.6 hours spillingMarApr 2025: 11 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 5.7 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 1.0 hours spillingAugSep 2025: 1.9 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 0.9 hours spillingNovDec 2025: 277 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
15 Dec 2025, 03:34West Charleton STW9.0 days
24 Dec 2025, 07:53West Charleton STW1.5 days
29 Jan 2025, 10:47West Charleton STW12.2 h
31 Jan 2025, 04:33West Charleton STW10.0 h
8 Jan 2025, 10:41West Charleton STW8.9 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate6,694 m³range 2,667 – 16,807 m³
In litres6.7 millionrange 2.7 million – 16.8 million L
Olympic swimming pools2.7at 2,500 m³ each
Organic load, as people's raw sewage10,042person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 107 kg602 kg3,361 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 280 kg2,845 kg12,118 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 5.1 kg42 kg156 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 3.2 kg17 kg91 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 266.7 billion organisms6.7 trillion organisms168.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

West Charleton STW

Storm tank at sewage works · discharges to Charleton Stream(S)

Spills 2025
46 (391 hours) · down 37% on 2024
Spills 2024
73 (1,003 hours)
Long-term average
52.5 spills a year (monitored since 2017)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation ongoing
Improvement
Env Act (SODRP) improvement ongoing, Bathing Water and/or Shellfish Water improvement ongoing
Shellfish water
Salcombe
WFD catchment
Not part of a WFD catchment
Outlet location
SX75204235 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB01337 · 203206 · company name: WEST CHARLETON STW_SSO_CHARLETON

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.