Storm overflow register · South West Water

Widegates sewage works: storm overflow spills 2025

Widegates sewage treatment works, run by South West Water, has 1 monitored storm overflow discharging to Tributary of River Seaton. In 2025 it recorded 39 spills totalling 34 hours, against 31 spills and 17 hours in 2024. By hours spilling, it ranks 285 of 334 South West Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWidegates WwTW4 Jan 2025 20:57 GMT, 1 min5 Jan 2025 19:11 GMT, 1 min6 Jan 2025 00:59 GMT, 24 min23 Jan 2025 10:30 GMT, 5 min26 Jan 2025 11:26 GMT, 39 min26 Jan 2025 12:15 GMT, 22 min26 Jan 2025 13:10 GMT, 10 min26 Jan 2025 20:39 GMT, 37 min26 Jan 2025 21:45 GMT, 23 min26 Jan 2025 22:33 GMT, 5 min28 Jan 2025 16:18 GMT, 13 min19 Feb 2025 19:35 GMT, 53 min23 Feb 2025 18:17 GMT, 23 min23 Feb 2025 20:06 GMT, 86 min24 Feb 2025 06:32 GMT, 11 min26 Feb 2025 06:18 GMT, 23 min18 Apr 2025 11:36 GMT, 4 min6 Jun 2025 19:21 GMT, 14 min7 Jun 2025 12:27 GMT, 7 min6 Jul 2025 23:00 GMT, 8 min20 Jul 2025 11:16 GMT, 5 min27 Aug 2025 10:44 GMT, 11 min28 Aug 2025 22:35 GMT, 78 min31 Aug 2025 15:30 GMT, 9 min3 Sep 2025 09:09 GMT, 30 min4 Sep 2025 01:44 GMT, 4 min9 Sep 2025 19:02 GMT, 12 min14 Sep 2025 11:14 GMT, 9 min20 Sep 2025 13:45 GMT, 6 min4 Nov 2025 13:18 GMT, 18 min4 Nov 2025 15:18 GMT, 4 min4 Nov 2025 15:25 GMT, 15 min4 Nov 2025 22:49 GMT, 42 min4 Nov 2025 23:40 GMT, 58 min7 Nov 2025 12:29 GMT, 30 min9 Nov 2025 13:51 GMT, 22 min12 Nov 2025 04:14 GMT, 31 min13 Nov 2025 19:00 GMT, 39 min14 Nov 2025 13:20 GMT, 27 min1 Dec 2025 15:17 GMT, 11 min3 Dec 2025 23:52 GMT, 4 min4 Dec 2025 02:33 GMT, 6 min5 Dec 2025 09:38 GMT, 1 min5 Dec 2025 13:18 GMT, 8 min5 Dec 2025 14:16 GMT, 14 min5 Dec 2025 14:48 GMT, 52 min5 Dec 2025 21:13 GMT, 10 min8 Dec 2025 22:22 GMT, 85 min9 Dec 2025 00:13 GMT, 2.3 h12 Dec 2025 02:43 GMT, 11 min15 Dec 2025 05:40 GMT, 7.6 h15 Dec 2025 13:29 GMT, 10 min17 Dec 2025 19:30 GMT, 10 min17 Dec 2025 19:53 GMT, 3 h18 Dec 2025 10:29 GMT, 61 min18 Dec 2025 11:33 GMT, 2.2 h20 Dec 2025 20:34 GMT, 7 min

Hours spilling by month, 2025

05101520Jan 2025: 3.0 hours spillingJanFeb 2025: 3.3 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 0.1 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 0.3 hours spillingJunJul 2025: 0.2 hours spillingJulAug 2025: 1.6 hours spillingAugSep 2025: 1.0 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 4.8 hours spillingNovDec 2025: 20 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
15 Dec 2025, 05:40Widegates WwTW7.6 h
17 Dec 2025, 19:53Widegates WwTW3.0 h
9 Dec 2025, 00:13Widegates WwTW2.3 h
18 Dec 2025, 11:33Widegates WwTW2.2 h
23 Feb 2025, 20:06Widegates WwTW1.4 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate586 m³range 233 – 1,471 m³
In litres585,998range 233,415 – 1.5 million L
Olympic swimming pools0.2at 2,500 m³ each
Organic load, as people's raw sewage879person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 9.3 kg53 kg294 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 25 kg249 kg1,061 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 0.4 kg3.7 kg14 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 0.3 kg1.5 kg7.9 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 23.3 billion organisms586.0 billion organisms14.7 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Widegates WwTW

Inlet overflow at sewage works · discharges to Tributary of River Seaton

Spills 2025
39 (34 hours) · up 26% on 2024
Spills 2024
31 (17 hours)
Long-term average
29.4 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Seaton (GB108048002320)
Outlet location
SX28605736 (OS grid reference) · View on Apple Maps
EA ID / permit
SBB01360 · SWWA 1003 · company name: WIDEGATES STW_SO_LOOE

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All South West Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.