Storm overflow register · Southern Water

Brockenhurst sewage works: storm overflow spills 2025

Brockenhurst sewage treatment works, run by Southern Water, has 2 monitored storm overflows discharging to Lymington River. In 2025 they recorded 62 spills totalling 499 hours, against 138 spills and 1,855 hours in 2024. By hours spilling, it ranks 47 of 215 Southern Water works, where 1 spilled longest.

Works size: 3,864 population equivalent (BROCKENHURST STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBrockenhurst WwTW1 Jan 2025 15:38 GMT, 21.3 h30 spills, 54 h, 4 Jan to 9 Jan2 spills, 26.1 h, 24 Jan to 25 Jan5 spills, 5.1 h, 26 Jan to 26 Jan31 spills, 17.8 h, 27 Jan to 30 Jan16 spills, 16.3 h, 31 Jan to 2 Feb20 Feb 2025 20:55 GMT, 14 min13 spills, 10.7 h, 21 Feb to 22 Feb34 spills, 41.6 h, 23 Feb to 27 Feb23 Apr 2025 04:13 GMT, 25 min7 Jun 2025 17:22 GMT, 3 h31 Jul 2025 19:15 GMT, 12.3 h3 spills, 2.7 h, 29 Aug to 29 Aug3 Sep 2025 03:42 GMT, 2.3 h5 spills, 25.2 h, 19 Oct to 21 Oct3 spills, 19.9 h, 22 Oct to 23 Oct2 spills, 21.2 h, 10 Nov to 11 Nov2 spills, 12.6 h, 22 Nov to 23 Nov3 spills, 7.9 h, 1 Dec to 2 Dec11 spills, 95.7 h, 4 Dec to 10 Dec18 Dec 2025 04:29 GMT, 43.3 hBrockenhurst WwTW5 Jan 2025 07:57 GMT, 18.8 h28 spills, 10.5 h, 26 Jan to 27 Jan7 Jun 2025 16:24 GMT, 25 min31 Jul 2025 17:58 GMT, 54 min5 spills, 5.7 h, 20 Oct to 20 Oct7 spills, 6.3 h, 9 Dec to 9 Dec8 spills, 16.7 h, 18 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30kJan 2025: 164 h spilling ≈ 10,832 m³ (range 4,314-27,193 m³)JanFeb 2025: 59 h spilling ≈ 3,886 m³ (range 1,548-9,757 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.4 h spilling ≈ 26 m³ (range 11-66 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 3.4 h spilling ≈ 225 m³ (range 90-565 m³)JunJul 2025: 5.7 h spilling ≈ 377 m³ (range 150-947 m³)JulAug 2025: 10 h spilling ≈ 675 m³ (range 269-1,695 m³)AugSep 2025: 2.3 h spilling ≈ 152 m³ (range 61-382 m³)SepOct 2025: 51 h spilling ≈ 3,363 m³ (range 1,340-8,444 m³)OctNov 2025: 34 h spilling ≈ 2,238 m³ (range 891-5,618 m³)NovDec 2025: 170 h spilling ≈ 11,242 m³ (range 4,478-28,224 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
18 Dec 2025, 04:29Brockenhurst WwTW1.8 days1,141 - 7,192 m³
8 Dec 2025, 22:40Brockenhurst WwTW1.6 days1,030 - 6,491 m³
5 Jan 2025, 05:07Brockenhurst WwTW1.4 days884 - 5,571 m³
5 Dec 2025, 18:36Brockenhurst WwTW1.1 days691 - 4,352 m³
1 Jan 2025, 15:38Brockenhurst WwTW21.3 h562 - 3,540 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate33,024 m³range 13,154 - 82,909 m³
In litres33.0 millionrange 13.2 million - 82.9 million L
Olympic swimming pools13at 2,500 m³ each
Organic load, as people's raw sewage49,536person-days of untreated BOD

Assumed spill rate while spilling: 7.3 - 46.2 L/s (central 18.4 L/s), from a dry-weather flow of 7.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 526 kg2,972 kg16,582 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,381 kg14,035 kg59,777 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 25 kg208 kg771 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 16 kg86 kg448 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.3 trillion organisms33.0 trillion organisms829.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Brockenhurst WwTW

Storm tank at sewage works · discharges to Lymington River

Spills 2025
52 (439 hours) · down 56% on 2024
Spills 2024
119 (1,687 hours)
Long-term average
86.8 spills a year (monitored since 2016)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - GW inundation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Lymington River (GB107042011220)
Outlet location
SU3090002600 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00109 · W00311 · company name: BROCKENHURST SSO - 115374

Brockenhurst WwTW

Inlet overflow at sewage works · discharges to Lymington River

Spills 2025
10 (59 hours) · down 47% on 2024
Spills 2024
19 (169 hours)
Long-term average
13.2 spills a year (monitored since 2016)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Lymington River (GB107042011220)
Outlet location
SU3090002600 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00108 · W00311 · company name: BROCKENHURST CSO - 115399

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Southern Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.