Storm overflow register · Southern Water

Flexford Lane Sway sewage works: storm overflow spills 2025

Flexford Lane Sway sewage treatment works, run by Southern Water, has 1 monitored storm overflow discharging to Avon Water. In 2025 it recorded 43 spills totalling 508 hours, against 132 spills and 2,303 hours in 2024. By hours spilling, it ranks 42 of 215 Southern Water works, where 1 spilled longest.

Works size: 2,603 population equivalent (SWAY OUTLET CSM DATA, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFlexford Lane Sway…1 Jan 2025 18:36 GMT, 3.1 h5 Jan 2025 01:36 GMT, 119.5 h10 Jan 2025 07:35 GMT, 6 h10 Jan 2025 14:03 GMT, 5 min10 Jan 2025 16:11 GMT, 5 min10 Jan 2025 17:31 GMT, 3.8 h10 Jan 2025 21:43 GMT, 6 min24 Jan 2025 10:19 GMT, 60 min26 Jan 2025 17:03 GMT, 92.8 h31 Jan 2025 05:10 GMT, 43.8 h2 Feb 2025 01:24 GMT, 5 min2 Feb 2025 09:32 GMT, 4.6 h2 Feb 2025 14:34 GMT, 59 min2 Feb 2025 16:16 GMT, 6 min2 Feb 2025 17:35 GMT, 6 min2 Feb 2025 18:07 GMT, 3.4 h21 Feb 2025 22:54 GMT, 4.5 h24 Feb 2025 04:32 GMT, 21.6 h26 Feb 2025 10:40 GMT, 14.1 h27 Feb 2025 01:33 GMT, 23 min27 Feb 2025 08:15 GMT, 3.4 h27 Feb 2025 12:28 GMT, 22 min27 Feb 2025 13:18 GMT, 22 min27 Feb 2025 20:13 GMT, 5 min27 Feb 2025 22:06 GMT, 7 min7 Jun 2025 17:48 GMT, 3 h3 Sep 2025 04:13 GMT, 5.8 h20 Oct 2025 09:43 GMT, 11.2 h22 Oct 2025 21:36 GMT, 14.1 h10 Nov 2025 12:55 GMT, 16.5 h22 Nov 2025 18:58 GMT, 3.2 h23 Nov 2025 06:14 GMT, 6.7 h4 Dec 2025 10:01 GMT, 9.6 h5 Dec 2025 17:31 GMT, 21.4 h7 Dec 2025 07:34 GMT, 19 h9 Dec 2025 03:44 GMT, 19.9 h16 Dec 2025 08:35 GMT, 5.2 h18 Dec 2025 01:24 GMT, 47.8 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

010k20k30kJan 2025: 245 h spilling ≈ 10,936 m³ (range 4,356–27,456 m³)JanFeb 2025: 79 h spilling ≈ 3,532 m³ (range 1,407–8,868 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 3.0 h spilling ≈ 134 m³ (range 53–336 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 5.8 h spilling ≈ 259 m³ (range 103–649 m³)SepOct 2025: 25 h spilling ≈ 1,128 m³ (range 449–2,833 m³)OctNov 2025: 26 h spilling ≈ 1,169 m³ (range 465–2,934 m³)NovDec 2025: 123 h spilling ≈ 5,477 m³ (range 2,182–13,750 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 01:36Flexford Lane Sway WwTW5.0 days2,122 – 13,375 m³
26 Jan 2025, 17:03Flexford Lane Sway WwTW3.9 days1,648 – 10,389 m³
18 Dec 2025, 01:24Flexford Lane Sway WwTW2.0 days849 – 5,350 m³
31 Jan 2025, 05:10Flexford Lane Sway WwTW1.8 days778 – 4,901 m³
24 Feb 2025, 04:32Flexford Lane Sway WwTW21.6 h384 – 2,420 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate22,639 m³range 9,018 – 56,837 m³
In litres22.6 millionrange 9.0 million – 56.8 million L
Olympic swimming pools9.1at 2,500 m³ each
Organic load, as people's raw sewage33,959person-days of untreated BOD

Assumed spill rate while spilling: 4.9 – 31.1 L/s (central 12.4 L/s), from a dry-weather flow of 4.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 361 kg2,038 kg11,367 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 947 kg9,622 kg40,980 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 17 kg143 kg529 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 11 kg59 kg307 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 901.8 billion organisms22.6 trillion organisms568.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Flexford Lane Sway WwTW

Storm tank at sewage works · discharges to Avon Water

Spills 2025
43 (508 hours) · down 67% on 2024
Spills 2024
132 (2,303 hours)
Long-term average
68.4 spills a year (monitored since 2017)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - GW inundation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
Shellfish water
Pennington
WFD catchment
Avon Water (GB107042011300)
Outlet location
SZ2888096570 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00318 · W00244 · company name: FLEXFORD LANE SWAY SSO - 115913

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Southern Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.