Storm overflow register · Southern Water

Milford Road Pennington sewage works: storm overflow spills 2025

Milford Road Pennington sewage treatment works, run by Southern Water, has 2 monitored storm overflows discharging to The Solent. In 2025 they recorded 67 spills totalling 929 hours, against 132 spills and 2,084 hours in 2024. By hours spilling, it ranks 17 of 215 Southern Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMilford Road…1 Jan 2025 16:28 GMT, 6.6 h5 Jan 2025 00:32 GMT, 73.1 h8 Jan 2025 08:23 GMT, 41.3 h10 Jan 2025 08:26 GMT, 15.7 h11 Jan 2025 10:01 GMT, 12.1 h12 Jan 2025 10:52 GMT, 11 h13 Jan 2025 10:43 GMT, 2.4 h24 Jan 2025 10:09 GMT, 3.7 h26 Jan 2025 12:30 GMT, 62.4 h29 Jan 2025 08:12 GMT, 42.2 h31 Jan 2025 04:30 GMT, 47.7 h2 Feb 2025 08:13 GMT, 16.7 h3 Feb 2025 08:53 GMT, 14.7 h4 Feb 2025 09:20 GMT, 4.3 h4 Feb 2025 18:17 GMT, 4 h5 Feb 2025 10:16 GMT, 107 min7 Feb 2025 17:22 GMT, 4.5 h8 Feb 2025 11:14 GMT, 5.4 h21 Feb 2025 23:32 GMT, 3.9 h22 Feb 2025 10:05 GMT, 4 h23 Feb 2025 18:10 GMT, 3 h24 Feb 2025 00:15 GMT, 48.5 h26 Feb 2025 08:36 GMT, 16.8 h27 Feb 2025 08:30 GMT, 7.8 h27 Feb 2025 19:00 GMT, 4.8 h28 Feb 2025 09:24 GMT, 3.6 h28 Feb 2025 19:59 GMT, 77 min1 Mar 2025 10:42 GMT, 2.6 h7 Jun 2025 18:17 GMT, 3.4 h29 Aug 2025 06:28 GMT, 7.3 h3 Sep 2025 03:33 GMT, 10.7 h13 Sep 2025 07:47 GMT, 9.4 h19 Oct 2025 16:33 GMT, 6 h20 Oct 2025 03:13 GMT, 21 h22 Oct 2025 18:39 GMT, 26 h1 Nov 2025 02:05 GMT, 42 min1 Nov 2025 16:13 GMT, 2.1 h2 Nov 2025 06:18 GMT, 6.6 h22 Nov 2025 17:33 GMT, 9 h23 Nov 2025 07:51 GMT, 16.3 h4 Dec 2025 00:21 GMT, 2.7 h4 Dec 2025 06:56 GMT, 18 h5 Dec 2025 09:25 GMT, 5.1 h5 Dec 2025 16:51 GMT, 32.6 h7 Dec 2025 06:50 GMT, 90.3 h11 Dec 2025 08:29 GMT, 15.3 h12 Dec 2025 09:22 GMT, 4.6 h16 Dec 2025 05:16 GMT, 20.8 h18 Dec 2025 01:35 GMT, 120.3 h23 Dec 2025 08:54 GMT, 13.8 h24 Dec 2025 09:38 GMT, 11.6 h25 Dec 2025 10:59 GMT, 3.2 hMilford Road…18 Dec 2025 13:14 GMT, 6.5 h

Hours spilling by month, 2025

0100200300400Jan 2025: 290 hours spillingJanFeb 2025: 173 hours spillingFebMar 2025: 2.6 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 3.4 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 7.3 hours spillingAugSep 2025: 20 hours spillingSepOct 2025: 53 hours spillingOctNov 2025: 35 hours spillingNovDec 2025: 345 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
18 Dec 2025, 01:35Milford Road Pennington WwTW5.0 days
7 Dec 2025, 06:50Milford Road Pennington WwTW3.8 days
5 Jan 2025, 00:32Milford Road Pennington WwTW3.0 days
26 Jan 2025, 12:30Milford Road Pennington WwTW2.6 days
24 Feb 2025, 00:15Milford Road Pennington WwTW2.0 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate15,911 m³range 6,338 – 39,945 m³
In litres15.9 millionrange 6.3 million – 39.9 million L
Olympic swimming pools6.4at 2,500 m³ each
Organic load, as people's raw sewage23,867person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 254 kg1,432 kg7,989 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 665 kg6,762 kg28,801 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 12 kg100 kg371 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 7.6 kg41 kg216 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 633.8 billion organisms15.9 trillion organisms399.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Milford Road Pennington WwTW

Storm tank at sewage works · discharges to The Solent

Spills 2025
66 (922 hours) · down 48% on 2024
Spills 2024
126 (2,041 hours)
Long-term average
68.9 spills a year (monitored since 2016)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - GW inundation
Investigation
UWWTR investigation ongoing
Improvement
No improvement action in reporting period
Shellfish water
Lymington and Sowley; Pennington; Yarmouth
WFD catchment
Solent (GB650705150000)
Outlet location
SZ3315091870 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00656 · A00665 · company name: MILFORD ROAD PENNINGTON SSO - 115419

Milford Road Pennington WwTW

Inlet overflow at sewage works · discharges to The Solent

Spills 2025
1 (6.5 hours) · down 83% on 2024
Spills 2024
6 (43 hours)
Long-term average
1.9 spills a year (monitored since 2016)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
Shellfish water
Lymington and Sowley; Pennington; Yarmouth
WFD catchment
Solent (GB650705150000)
Outlet location
SZ3315091870 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00655 · A00665 · company name: MILFORD ROAD PENNINGTON CEO - 116102

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Southern Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.