Storm overflow register · Southern Water

Paddock Wood sewage works: storm overflow spills 2025

Paddock Wood sewage treatment works, run by Southern Water, has 1 monitored storm overflow discharging to The Rhoden Stream. In 2025 it recorded 22 spills totalling 156 hours, against 39 spills and 313 hours in 2024. By hours spilling, it ranks 124 of 215 Southern Water works, where 1 spilled longest.

Works size: 10,589 population equivalent (PADDOCK WOOD STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecPaddock Wood WwTW1 Jan 2025 16:50 GMT, 7.1 h2 Jan 2025 00:01 GMT, 20 min2 Jan 2025 00:42 GMT, 16 min5 Jan 2025 03:39 GMT, 33.4 h6 Jan 2025 13:03 GMT, 2.4 h6 Jan 2025 15:32 GMT, 39 min6 Jan 2025 16:28 GMT, 59 min6 Jan 2025 17:29 GMT, 64 min6 Jan 2025 18:36 GMT, 26 min6 Jan 2025 20:16 GMT, 37 min26 Jan 2025 17:03 GMT, 21.7 h27 Jan 2025 14:48 GMT, 39 min27 Jan 2025 16:07 GMT, 19 min27 Jan 2025 16:37 GMT, 34 min27 Jan 2025 17:32 GMT, 43 min27 Jan 2025 18:52 GMT, 18 min27 Jan 2025 19:31 GMT, 20 min28 Jan 2025 10:31 GMT, 2.7 h28 Jan 2025 13:12 GMT, 25 min24 Feb 2025 11:17 GMT, 2.9 h24 Feb 2025 14:14 GMT, 52 min6 Jul 2025 19:08 GMT, 2.5 h6 Jul 2025 21:44 GMT, 19 min7 Jul 2025 05:05 GMT, 5.7 h7 Jul 2025 11:11 GMT, 25 min21 Jul 2025 06:52 GMT, 10.9 h3 Sep 2025 15:03 GMT, 2.7 h4 Sep 2025 07:58 GMT, 75 min20 Oct 2025 17:15 GMT, 7.1 h23 Oct 2025 06:44 GMT, 10.6 h23 Oct 2025 17:35 GMT, 19 min29 Oct 2025 17:56 GMT, 2.5 h29 Oct 2025 20:35 GMT, 17 min2 Nov 2025 09:35 GMT, 5.8 h2 Nov 2025 15:28 GMT, 22 min2 Nov 2025 15:50 GMT, 16 min6 Dec 2025 02:25 GMT, 11.7 h6 Dec 2025 14:20 GMT, 30 min6 Dec 2025 15:13 GMT, 22 min7 Dec 2025 16:48 GMT, 16 min18 Dec 2025 15:17 GMT, 12.2 h19 Dec 2025 04:09 GMT, 25 min19 Dec 2025 07:25 GMT, 20 min19 Dec 2025 08:16 GMT, 19 min19 Dec 2025 08:49 GMT, 32 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

010k20k30k40kJan 2025: 75 h spilling ≈ 13,590 m³ (range 5,413–34,117 m³)JanFeb 2025: 3.8 h spilling ≈ 689 m³ (range 275–1,731 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 20 h spilling ≈ 3,592 m³ (range 1,431–9,019 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 4.0 h spilling ≈ 726 m³ (range 289–1,822 m³)SepOct 2025: 21 h spilling ≈ 3,774 m³ (range 1,503–9,474 m³)OctNov 2025: 6.5 h spilling ≈ 1,179 m³ (range 470–2,961 m³)NovDec 2025: 27 h spilling ≈ 4,826 m³ (range 1,922–12,116 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 03:39Paddock Wood WwTW1.4 days2,411 – 15,199 m³
26 Jan 2025, 17:03Paddock Wood WwTW21.7 h1,567 – 9,877 m³
18 Dec 2025, 15:17Paddock Wood WwTW12.2 h882 – 5,557 m³
6 Dec 2025, 02:25Paddock Wood WwTW11.7 h843 – 5,314 m³
21 Jul 2025, 06:52Paddock Wood WwTW10.9 h788 – 4,965 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate28,359 m³range 11,296 – 71,195 m³
In litres28.4 millionrange 11.3 million – 71.2 million L
Olympic swimming pools11at 2,500 m³ each
Organic load, as people's raw sewage42,538person-days of untreated BOD

Assumed spill rate while spilling: 20.1 – 126.5 L/s (central 50.4 L/s), from a dry-weather flow of 20.1 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 452 kg2,552 kg14,239 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,186 kg12,052 kg51,332 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 21 kg179 kg662 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 14 kg74 kg384 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.1 trillion organisms28.4 trillion organisms712.0 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Paddock Wood WwTW

Storm tank at sewage works · discharges to The Rhoden Stream

Spills 2025
22 (156 hours) · down 44% on 2024
Spills 2024
39 (313 hours)
Long-term average
24.2 spills a year (monitored since 2016)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Lower Teise (GB106040018130)
Outlet location
TQ6784045840 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00638 · W00587 · company name: PADDOCK WOOD SSO - 115424

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Southern Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.