Storm overflow register · Southern Water

Sandhurst sewage works: storm overflow spills 2025

Sandhurst sewage treatment works, run by Southern Water, has 1 monitored storm overflow discharging to Hexden Channel. In 2025 it recorded 50 spills totalling 524 hours, against 116 spills and 1,627 hours in 2024. By hours spilling, it ranks 38 of 215 Southern Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSandhurst WwTW1 Jan 2025 16:51 GMT, 7.2 h4 Jan 2025 23:22 GMT, 73.6 h8 Jan 2025 23:32 GMT, 25.8 h24 Jan 2025 06:15 GMT, 18 h25 Jan 2025 00:36 GMT, 15 min25 Jan 2025 01:14 GMT, 15 min25 Jan 2025 02:00 GMT, 15 min25 Jan 2025 09:00 GMT, 2.1 h25 Jan 2025 11:22 GMT, 15 min25 Jan 2025 11:56 GMT, 15 min26 Jan 2025 13:03 GMT, 61.3 h29 Jan 2025 02:35 GMT, 57 min29 Jan 2025 05:17 GMT, 29 min29 Jan 2025 06:30 GMT, 4.6 h29 Jan 2025 14:55 GMT, 16 min29 Jan 2025 16:19 GMT, 15 min29 Jan 2025 16:55 GMT, 8.1 h30 Jan 2025 01:16 GMT, 15 min30 Jan 2025 07:24 GMT, 3.1 h30 Jan 2025 10:53 GMT, 15 min30 Jan 2025 12:37 GMT, 15 min31 Jan 2025 07:31 GMT, 3.9 h31 Jan 2025 11:53 GMT, 42 min31 Jan 2025 13:04 GMT, 19 min31 Jan 2025 13:38 GMT, 46 min31 Jan 2025 14:53 GMT, 34 min31 Jan 2025 15:43 GMT, 34 min31 Jan 2025 17:20 GMT, 23 min31 Jan 2025 18:20 GMT, 57 min31 Jan 2025 19:54 GMT, 27 min31 Jan 2025 20:36 GMT, 15 min31 Jan 2025 21:14 GMT, 19 min31 Jan 2025 21:59 GMT, 43 min1 Feb 2025 08:16 GMT, 6.6 h8 Feb 2025 00:25 GMT, 39 min8 Feb 2025 04:10 GMT, 59 min8 Feb 2025 08:11 GMT, 4.2 h9 Feb 2025 08:49 GMT, 51.6 h11 Feb 2025 14:08 GMT, 6 h22 Feb 2025 03:00 GMT, 11.9 h24 Feb 2025 03:00 GMT, 22.1 h26 Feb 2025 13:15 GMT, 11.5 h23 Apr 2025 06:43 GMT, 8.5 h7 Jun 2025 19:45 GMT, 102 min21 Jul 2025 13:16 GMT, 3.7 h23 Jul 2025 04:16 GMT, 107 min23 Jul 2025 09:30 GMT, 70 min26 Jul 2025 21:34 GMT, 3.5 h3 Sep 2025 13:01 GMT, 6.5 h13 Sep 2025 08:55 GMT, 7.1 h20 Oct 2025 18:56 GMT, 4 h22 Oct 2025 22:19 GMT, 19.6 h1 Nov 2025 06:49 GMT, 8 h2 Nov 2025 08:34 GMT, 10.9 h10 Nov 2025 11:30 GMT, 14.5 h24 Nov 2025 13:04 GMT, 32 min5 Dec 2025 20:33 GMT, 23.4 h7 Dec 2025 14:14 GMT, 14.8 h8 Dec 2025 14:18 GMT, 12.7 h9 Dec 2025 05:24 GMT, 20.9 h18 Dec 2025 16:00 GMT, 11.5 h21 Dec 2025 18:52 GMT, 16.4 h

Hours spilling by month, 2025

0100200300Jan 2025: 218 hours spillingJanFeb 2025: 115 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 8.5 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 1.7 hours spillingJunJul 2025: 10 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 14 hours spillingSepOct 2025: 24 hours spillingOctNov 2025: 34 hours spillingNovDec 2025: 100 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
4 Jan 2025, 23:22Sandhurst WwTW3.1 days
26 Jan 2025, 13:03Sandhurst WwTW2.6 days
9 Feb 2025, 08:49Sandhurst WwTW2.1 days
8 Jan 2025, 23:32Sandhurst WwTW1.1 days
5 Dec 2025, 20:33Sandhurst WwTW23.4 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate8,978 m³range 3,576 – 22,541 m³
In litres9.0 millionrange 3.6 million – 22.5 million L
Olympic swimming pools3.6at 2,500 m³ each
Organic load, as people's raw sewage13,468person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 143 kg808 kg4,508 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 376 kg3,816 kg16,252 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 6.8 kg57 kg210 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 4.3 kg23 kg122 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 357.6 billion organisms9.0 trillion organisms225.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Sandhurst WwTW

Storm tank at sewage works · discharges to Hexden Channel

Spills 2025
50 (524 hours) · down 57% on 2024
Spills 2024
116 (1,627 hours)
Long-term average
91.8 spills a year (monitored since 2019)
Monitor uptime
98% of the year
High-spill reason (company)
Performance - GW inundation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Hexden Channel (GB107040019670)
Outlet location
TQ8120029140 (OS grid reference) · View on Apple Maps
EA ID / permit
SWS00738 · W00549 · company name: SANDHURST SSO - 115755

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Southern Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.