Storm overflow register · Thames Water

Berkhamsted sewage works: storm overflow spills 2025

Berkhamsted sewage treatment works, run by Thames Water, has 1 monitored storm overflow discharging to The Grand Union Canal. In 2025 it recorded 35 spills totalling 210 hours, against 157 spills and 1,776 hours in 2024. By hours spilling, it ranks 124 of 233 Thames Water works, where 1 spilled longest.

Works size: 24,886 population equivalent (BERKHAMSTED SEWAGE WORKS, BULLBEGGA STW", UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBerkhamsted Sewage…1 Jan 2025 12:00 GMT, 6.5 h5 Jan 2025 09:00 GMT, 39.8 h7 Jan 2025 08:00 GMT, 3.3 h7 Jan 2025 20:00 GMT, 105 min8 Jan 2025 09:00 GMT, 60 min9 Jan 2025 20:45 GMT, 30 min23 Jan 2025 13:45 GMT, 2.3 h24 Jan 2025 07:45 GMT, 3.8 h26 Jan 2025 11:45 GMT, 45 min26 Jan 2025 13:30 GMT, 8.5 h26 Jan 2025 23:45 GMT, 5.3 h27 Jan 2025 05:45 GMT, 30 min27 Jan 2025 07:15 GMT, 17.8 h28 Jan 2025 06:45 GMT, 16.5 h29 Jan 2025 08:30 GMT, 90 min29 Jan 2025 20:00 GMT, 45 min29 Jan 2025 21:15 GMT, 105 min30 Jan 2025 19:45 GMT, 45 min30 Jan 2025 21:00 GMT, 30 min31 Jan 2025 07:45 GMT, 5.3 h31 Jan 2025 19:45 GMT, 75 min1 Feb 2025 10:15 GMT, 2 h2 Feb 2025 19:15 GMT, 30 min8 Feb 2025 12:30 GMT, 60 min9 Feb 2025 12:30 GMT, 30 min9 Feb 2025 19:30 GMT, 5 h10 Feb 2025 08:15 GMT, 4 h10 Feb 2025 16:15 GMT, 60 min10 Feb 2025 17:45 GMT, 5.3 h11 Feb 2025 08:45 GMT, 2 h13 Feb 2025 08:45 GMT, 30 min15 Feb 2025 15:45 GMT, 30 min21 Feb 2025 10:30 GMT, 30 min21 Feb 2025 23:00 GMT, 4.8 h22 Feb 2025 09:45 GMT, 2.8 h23 Feb 2025 11:00 GMT, 30 min23 Feb 2025 23:15 GMT, 18.3 h24 Feb 2025 18:00 GMT, 6 h25 Feb 2025 08:00 GMT, 3 h26 Feb 2025 08:30 GMT, 30 min26 Feb 2025 09:45 GMT, 15.3 h27 Feb 2025 08:15 GMT, 105 min27 Feb 2025 20:00 GMT, 45 min28 Feb 2025 09:15 GMT, 45 min2 Mar 2025 20:45 GMT, 30 min23 Apr 2025 07:00 GMT, 3 h14 Nov 2025 13:45 GMT, 3.5 h18 Dec 2025 15:15 GMT, 6 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150kJan 2025: 120 h spilling ≈ 51,084 m³ (range 20,348–128,247 m³)JanFeb 2025: 77 h spilling ≈ 32,833 m³ (range 13,078–82,429 m³)FebMar 2025: 0.5 h spilling ≈ 213 m³ (range 85–535 m³)MarApr 2025: 3.0 h spilling ≈ 1,279 m³ (range 510–3,212 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 3.5 h spilling ≈ 1,492 m³ (range 594–3,747 m³)NovDec 2025: 6.0 h spilling ≈ 2,558 m³ (range 1,019–6,423 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 09:00Berkhamsted Sewage Treatment Works1.7 days6,751 – 42,553 m³
23 Feb 2025, 23:15Berkhamsted Sewage Treatment Works18.3 h3,100 – 19,537 m³
27 Jan 2025, 07:15Berkhamsted Sewage Treatment Works17.8 h3,015 – 19,002 m³
28 Jan 2025, 06:45Berkhamsted Sewage Treatment Works16.5 h2,802 – 17,663 m³
26 Feb 2025, 09:45Berkhamsted Sewage Treatment Works15.3 h2,590 – 16,325 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate89,460 m³range 35,634 – 224,594 m³
In litres89.5 millionrange 35.6 million – 224.6 million L
Olympic swimming pools36at 2,500 m³ each
Organic load, as people's raw sewage134,190person-days of untreated BOD

Assumed spill rate while spilling: 47.2 – 297.4 L/s (central 118.4 L/s), from a dry-weather flow of 47.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,425 kg8,051 kg44,919 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 3,742 kg38,021 kg161,932 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 68 kg564 kg2,089 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 43 kg233 kg1,213 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 3.6 trillion organisms89.5 trillion organisms2.2 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Berkhamsted Sewage Treatment Works

Storm tank at sewage works · discharges to The Grand Union Canal

Spills 2025
35 (210 hours) · down 78% on 2024
Spills 2024
157 (1,776 hours)
Long-term average
92.6 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - Asset configuration (e.g. PS/rising main/storm tanks)
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Grand Union Canal, Berkhamstead to Maple Lodge (RIvers Bulbourne, Gade and Colne) (GB70610185)
Outlet location
TL0131006810 (OS grid reference) · View on Apple Maps
EA ID / permit
TWL00037 · CATM.3074 · company name: Berkhamsted STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Thames Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.