Storm overflow register · Thames Water

Bletchingdon sewage works: storm overflow spills 2025

Bletchingdon sewage treatment works, run by Thames Water, has 1 monitored storm overflow discharging to Bletchingdon Brook. In 2025 it recorded 32 spills totalling 302 hours, against 120 spills and 1,871 hours in 2024. By hours spilling, it ranks 103 of 233 Thames Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBletchingdon WwTW5 Jan 2025 12:15 GMT, 37 h7 Jan 2025 07:00 GMT, 8.8 h7 Jan 2025 17:00 GMT, 7.5 h8 Jan 2025 07:00 GMT, 7.3 h8 Jan 2025 15:15 GMT, 7.8 h8 Jan 2025 23:30 GMT, 45 min9 Jan 2025 06:45 GMT, 7.8 h9 Jan 2025 16:30 GMT, 60 min9 Jan 2025 18:30 GMT, 6.3 h10 Jan 2025 07:45 GMT, 5.8 h26 Jan 2025 17:00 GMT, 45 min27 Jan 2025 01:30 GMT, 75 min8 Feb 2025 22:30 GMT, 2.3 h9 Feb 2025 13:45 GMT, 10.5 h10 Feb 2025 07:00 GMT, 17 h11 Feb 2025 09:15 GMT, 5.3 h11 Feb 2025 15:30 GMT, 30 min11 Feb 2025 17:45 GMT, 7.3 h12 Feb 2025 17:15 GMT, 7.3 h13 Feb 2025 09:45 GMT, 5.8 h13 Feb 2025 16:30 GMT, 7.3 h14 Feb 2025 20:45 GMT, 4 h15 Feb 2025 12:45 GMT, 11.3 h16 Feb 2025 13:00 GMT, 10.5 h17 Feb 2025 19:45 GMT, 3.8 h19 Feb 2025 22:00 GMT, 3 h20 Feb 2025 10:30 GMT, 5.5 h20 Feb 2025 17:00 GMT, 6.5 h21 Feb 2025 20:45 GMT, 2.5 h23 Feb 2025 17:30 GMT, 10.5 h24 Feb 2025 05:30 GMT, 13.5 h24 Feb 2025 19:30 GMT, 3.8 h26 Feb 2025 20:45 GMT, 4 h23 Apr 2025 05:30 GMT, 3 h7 Jun 2025 18:15 GMT, 3.8 h14 Nov 2025 00:15 GMT, 4.5 h14 Nov 2025 08:00 GMT, 13 h14 Nov 2025 21:30 GMT, 5.3 h15 Nov 2025 03:15 GMT, 30 min9 Dec 2025 05:30 GMT, 9.3 h9 Dec 2025 20:00 GMT, 2.5 h16 Dec 2025 21:45 GMT, 75 min18 Dec 2025 12:45 GMT, 12.8 h19 Dec 2025 08:30 GMT, 7 h19 Dec 2025 17:30 GMT, 3.8 h19 Dec 2025 21:45 GMT, 105 min

Hours spilling by month, 2025

050100150Jan 2025: 92 hours spillingJanFeb 2025: 142 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 3.0 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 3.8 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 0.0 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 23 hours spillingNovDec 2025: 38 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
5 Jan 2025, 12:15Bletchingdon WwTW1.5 days
10 Feb 2025, 07:00Bletchingdon WwTW17.0 h
24 Feb 2025, 05:30Bletchingdon WwTW13.5 h
14 Nov 2025, 08:00Bletchingdon WwTW13.0 h
18 Dec 2025, 12:45Bletchingdon WwTW12.8 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate5,171 m³range 2,060 – 12,982 m³
In litres5.2 millionrange 2.1 million – 13.0 million L
Olympic swimming pools2.1at 2,500 m³ each
Organic load, as people's raw sewage7,757person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 82 kg465 kg2,596 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 216 kg2,198 kg9,360 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 3.9 kg33 kg121 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 2.5 kg13 kg70 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 206.0 billion organisms5.2 trillion organisms129.8 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Bletchingdon WwTW

Storm tank at sewage works · discharges to Bletchingdon Brook

Spills 2025
32 (302 hours) · down 73% on 2024
Spills 2024
120 (1,871 hours)
Long-term average
75.1 spills a year (monitored since 2018)
Monitor uptime
95% of the year
High-spill reason (company)
Performance - Asset configuration (e.g. PS/rising main/storm tanks)
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Bletchingdon Stream (GB106039030080)
Outlet location
SP5066017380 (OS grid reference) · View on Apple Maps
EA ID / permit
TWL00043 · CTCR.1722 · company name: Bletchingdon STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Thames Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.