Storm overflow register · Thames Water

Epping sewage works: storm overflow spills 2025

Epping sewage treatment works, run by Thames Water, has 1 monitored storm overflow discharging to The Brookhouse Brook. In 2025 it recorded 49 spills totalling 603 hours, against 68 spills and 1,079 hours in 2024. By hours spilling, it ranks 53 of 233 Thames Water works, where 1 spilled longest.

Works size: 12,942 population equivalent (EPPING, FIDDLERS HAMLET, EPPING STW", UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecEpping Wastewater…1 Jan 2025 17:15 GMT, 11.3 h5 Jan 2025 07:15 GMT, 71.8 h10 Feb 2025 00:30 GMT, 51.8 h24 Feb 2025 08:15 GMT, 26.3 h25 Feb 2025 20:15 GMT, 10.5 h26 Feb 2025 13:15 GMT, 16.8 h15 Apr 2025 08:30 GMT, 6.3 h15 Apr 2025 17:15 GMT, 10.8 h23 Apr 2025 06:30 GMT, 22 h3 Jun 2025 16:45 GMT, 15.3 h5 Jun 2025 14:00 GMT, 11.5 h7 Jul 2025 07:00 GMT, 3.8 h19 Jul 2025 13:00 GMT, 3.5 h19 Jul 2025 21:30 GMT, 34.8 h21 Jul 2025 08:45 GMT, 21.3 h22 Jul 2025 06:30 GMT, 75 min22 Jul 2025 11:00 GMT, 20.5 h29 Aug 2025 10:15 GMT, 3.3 h12 Sep 2025 16:45 GMT, 8.8 h14 Sep 2025 20:00 GMT, 7.8 h20 Oct 2025 11:30 GMT, 15 h22 Oct 2025 23:30 GMT, 23.3 h31 Oct 2025 22:45 GMT, 22.3 h10 Nov 2025 15:15 GMT, 14.3 h14 Nov 2025 11:45 GMT, 31 h23 Nov 2025 09:00 GMT, 26.3 h2 Dec 2025 22:30 GMT, 15.5 h4 Dec 2025 16:00 GMT, 25 h9 Dec 2025 07:30 GMT, 30.8 h18 Dec 2025 14:30 GMT, 41 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

020k40k60k80kJan 2025: 83 h spilling ≈ 18,406 m³ (range 7,331–46,208 m³)JanFeb 2025: 105 h spilling ≈ 23,329 m³ (range 9,292–58,567 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 39 h spilling ≈ 8,648 m³ (range 3,445–21,712 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 27 h spilling ≈ 5,943 m³ (range 2,367–14,920 m³)JunJul 2025: 85 h spilling ≈ 18,849 m³ (range 7,508–47,321 m³)JulAug 2025: 3.2 h spilling ≈ 710 m³ (range 283–1,782 m³)AugSep 2025: 17 h spilling ≈ 3,659 m³ (range 1,457–9,186 m³)SepOct 2025: 40 h spilling ≈ 8,759 m³ (range 3,489–21,991 m³)OctNov 2025: 93 h spilling ≈ 20,512 m³ (range 8,170–51,497 m³)NovDec 2025: 112 h spilling ≈ 24,881 m³ (range 9,911–62,464 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 07:15Epping Wastewater Treatment Works3.0 days6,338 – 39,945 m³
10 Feb 2025, 00:30Epping Wastewater Treatment Works2.2 days4,571 – 28,810 m³
18 Dec 2025, 14:30Epping Wastewater Treatment Works1.7 days3,621 – 22,826 m³
19 Jul 2025, 21:30Epping Wastewater Treatment Works1.4 days3,069 – 19,346 m³
14 Nov 2025, 11:45Epping Wastewater Treatment Works1.3 days2,738 – 17,258 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate133,718 m³range 53,262 – 335,703 m³
In litres133.7 millionrange 53.3 million – 335.7 million L
Olympic swimming pools53at 2,500 m³ each
Organic load, as people's raw sewage200,576person-days of untreated BOD

Assumed spill rate while spilling: 24.5 – 154.6 L/s (central 61.6 L/s), from a dry-weather flow of 24.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,130 kg12,035 kg67,141 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 5,593 kg56,830 kg242,042 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 101 kg842 kg3,122 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 64 kg348 kg1,813 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 5.3 trillion organisms133.7 trillion organisms3.4 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Epping Wastewater Treatment Works

Storm tank at sewage works · discharges to The Brookhouse Brook

Spills 2025
49 (603 hours) · down 28% on 2024
Spills 2024
68 (1,079 hours)
Long-term average
53.7 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - Asset configuration (e.g. PS/rising main/storm tanks)
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Brookhouse Brook (GB106037028150)
Outlet location
TL4781000380 (OS grid reference) · View on Apple Maps
EA ID / permit
TWL00172 · CSSC.0295 · company name: Fiddlers Hamlet STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Thames Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.