Storm overflow register · Thames Water

Markyate sewage works: storm overflow spills 2025

Markyate sewage treatment works, run by Thames Water, has 1 monitored storm overflow discharging to River Ver. In 2025 it recorded 155 spills totalling 3,531 hours, against 187 spills and 3,383 hours in 2024. By hours spilling, it ranks 1 of 233 Thames Water works, where 1 spilled longest.

Works size: 6,155 population equivalent (MARKYATE, MARKYATE, HERTS STW", UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMarkyate Wastewater…1 Jan 2025 00:00 GMT, 3194 h14 May 2025 02:30 GMT, 2 h14 May 2025 05:00 GMT, 10.5 h14 May 2025 16:00 GMT, 33.3 h16 May 2025 01:45 GMT, 3.3 h16 May 2025 05:30 GMT, 18.8 h17 May 2025 02:00 GMT, 60 min17 May 2025 06:00 GMT, 19.8 h18 May 2025 06:45 GMT, 19 h19 May 2025 06:00 GMT, 9.3 h19 May 2025 15:45 GMT, 8.8 h20 May 2025 06:00 GMT, 5.3 h20 May 2025 12:15 GMT, 75 min20 May 2025 17:15 GMT, 6 h21 May 2025 00:00 GMT, 30 min21 May 2025 06:30 GMT, 4.5 h21 May 2025 12:45 GMT, 30 min21 May 2025 16:45 GMT, 7 h22 May 2025 06:00 GMT, 5.5 h22 May 2025 12:00 GMT, 3.3 h22 May 2025 15:45 GMT, 7.3 h23 May 2025 05:30 GMT, 43 h25 May 2025 04:00 GMT, 45 min25 May 2025 08:30 GMT, 7.8 h25 May 2025 16:45 GMT, 6.5 h26 May 2025 08:45 GMT, 6.8 h26 May 2025 16:00 GMT, 10.3 h27 May 2025 06:30 GMT, 78 h7 Jun 2025 15:30 GMT, 30 min7 Jun 2025 18:45 GMT, 2 h14 Nov 2025 12:15 GMT, 9.3 h15 Nov 2025 09:15 GMT, 105 min18 Dec 2025 16:15 GMT, 3.8 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150k200kJan 2025: 744 h spilling ≈ 78,464 m³ (range 31,254–196,987 m³)JanFeb 2025: 672 h spilling ≈ 70,871 m³ (range 28,229–177,924 m³)FebMar 2025: 744 h spilling ≈ 78,464 m³ (range 31,254–196,987 m³)MarApr 2025: 720 h spilling ≈ 75,933 m³ (range 30,246–190,633 m³)AprMay 2025: 634 h spilling ≈ 66,810 m³ (range 26,612–167,730 m³)MayJun 2025: 2.5 h spilling ≈ 264 m³ (range 105–662 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 11 h spilling ≈ 1,160 m³ (range 462–2,912 m³)NovDec 2025: 3.8 h spilling ≈ 401 m³ (range 160–1,006 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
1 Jan 2025, 00:00Markyate Wastewater Treatment Works133.1 days134,173 – 845,668 m³
27 May 2025, 06:30Markyate Wastewater Treatment Works3.3 days3,277 – 20,652 m³
23 May 2025, 05:30Markyate Wastewater Treatment Works1.8 days1,806 – 11,385 m³
14 May 2025, 16:00Markyate Wastewater Treatment Works1.4 days1,397 – 8,804 m³
17 May 2025, 06:00Markyate Wastewater Treatment Works19.8 h830 – 5,229 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate372,367 m³range 148,321 – 934,841 m³
In litres372.4 millionrange 148.3 million – 934.8 million L
Olympic swimming pools149at 2,500 m³ each
Organic load, as people's raw sewage558,550person-days of untreated BOD

Assumed spill rate while spilling: 11.7 – 73.5 L/s (central 29.3 L/s), from a dry-weather flow of 11.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 5,933 kg33,513 kg186,968 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 15,574 kg158,256 kg674,021 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 282 kg2,346 kg8,694 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 178 kg968 kg5,048 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 14.8 trillion organisms372.4 trillion organisms9.3 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Markyate Wastewater Treatment Works

Storm tank at sewage works · discharges to River Ver

Spills 2025
155 (3,531 hours) · down 17% on 2024
Spills 2024
187 (3,383 hours)
Long-term average
71.0 spills a year (monitored since 2019)
Monitor uptime
97% of the year
High-spill reason (company)
Performance - Asset configuration (e.g. PS/rising main/storm tanks)
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Ver (GB106039029920)
Outlet location
TL0749015410 (OS grid reference) · View on Apple Maps
EA ID / permit
TWL00292 · CSSC.8549 · company name: Markyate STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Thames Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.