Storm overflow register · United Utilities

Altrincham sewage works: storm overflow spills 2025

Altrincham sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to Sinderland Brook. In 2025 it recorded 57 spills totalling 346 hours, against 90 spills and 482 hours in 2024. By hours spilling, it ranks 144 of 289 United Utilities works, where 1 spilled longest.

Works size: 44,401 population equivalent (ALTRINCHAM STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecAltrincham STW27 spills, 40 h, 1 Jan to 2 Jan53 spills, 72 h, 5 Jan to 8 Jan4 spills, 4 h, 23 Jan to 24 Jan2 spills, 1.5 h, 27 Jan to 27 Jan31 Jan 2025 03:13 GMT, 47 min2 spills, 3.7 h, 20 Feb to 20 Feb23 Feb 2025 20:00 GMT, 3.4 h2 spills, 4.4 h, 26 Feb to 26 Feb7 Mar 2025 06:11 GMT, 90 min5 Jun 2025 14:02 GMT, 63 min9 Jun 2025 03:35 GMT, 66 min13 Jun 2025 23:42 GMT, 68 min2 spills, 3.1 h, 22 Jun to 23 Jun25 Jun 2025 02:00 GMT, 34 min2 Jul 2025 01:53 GMT, 97 min6 Jul 2025 05:46 GMT, 81 min20 Jul 2025 19:36 GMT, 22 min7 Sep 2025 13:06 GMT, 27 min17 Sep 2025 05:28 GMT, 6 h4 spills, 24.4 h, 20 Sep to 21 Sep27 Sep 2025 21:50 GMT, 3.6 h5 spills, 17.8 h, 3 Oct to 4 Oct27 Oct 2025 09:08 GMT, 8 min29 Oct 2025 22:12 GMT, 74 min4 spills, 8.2 h, 11 Nov to 12 Nov13 spills, 24.7 h, 14 Nov to 15 Nov7 spills, 12.8 h, 18 Nov to 19 Nov2 spills, 7.6 h, 23 Nov to 23 Nov13 spills, 8.8 h, 28 Nov to 29 Nov9 spills, 9.3 h, 1 Dec to 1 Dec4 Dec 2025 14:25 GMT, 2.1 h15 spills, 15.8 h, 5 Dec to 7 Dec6 spills, 12.7 h, 9 Dec to 9 Dec2 spills, 1.4 h, 12 Dec to 12 Dec15 spills, 23 h, 15 Dec to 16 Dec22 spills, 24.6 h, 17 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0100k200k300kJan 2025: 118 h spilling ≈ 90,001 m³ (range 35,849-225,951 m³)JanFeb 2025: 12 h spilling ≈ 8,749 m³ (range 3,485-21,965 m³)FebMar 2025: 1.5 h spilling ≈ 1,141 m³ (range 455-2,865 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 6.9 h spilling ≈ 5,249 m³ (range 2,091-13,179 m³)JunJul 2025: 3.3 h spilling ≈ 2,511 m³ (range 1,000-6,303 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 34 h spilling ≈ 26,171 m³ (range 10,424-65,703 m³)SepOct 2025: 19 h spilling ≈ 14,531 m³ (range 5,788-36,481 m³)OctNov 2025: 62 h spilling ≈ 47,169 m³ (range 18,788-118,419 m³)NovDec 2025: 89 h spilling ≈ 67,634 m³ (range 26,940-169,797 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
6 Jan 2025, 01:49Altrincham STW1.2 days8,450 - 53,257 m³
15 Dec 2025, 05:07Altrincham STW19.0 h5,753 - 36,258 m³
20 Sep 2025, 11:41Altrincham STW18.9 h5,717 - 36,035 m³
14 Nov 2025, 11:28Altrincham STW18.3 h5,535 - 34,889 m³
7 Jan 2025, 07:43Altrincham STW16.2 h4,909 - 30,942 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate263,308 m³range 104,881 - 661,045 m³
In litres263.3 millionrange 104.9 million - 661.0 million L
Olympic swimming pools105at 2,500 m³ each
Organic load, as people's raw sewage394,962person-days of untreated BOD

Assumed spill rate while spilling: 84.2 - 530.6 L/s (central 211.3 L/s), from a dry-weather flow of 84.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 4,195 kg23,698 kg132,209 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 11,013 kg111,906 kg476,614 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 199 kg1,659 kg6,148 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 126 kg685 kg3,570 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 10.5 trillion organisms263.3 trillion organisms6.6 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Altrincham STW

Storm tank at sewage works · discharges to Sinderland Brook

Spills 2025
57 (346 hours) · down 37% on 2024
Spills 2024
90 (482 hours)
Long-term average
78.0 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - Asset configuration (e.g. PS/rising main/storm tanks)
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Sinderland Brook (GB112069060980)
Outlet location
SJ7504090440 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00111 · 016940141 · company name: ALTRINCHAM WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.