Storm overflow register · United Utilities

Audley sewage works: storm overflow spills 2025

Audley sewage treatment works, run by United Utilities, has 2 monitored storm overflows discharging to Audley Brook. In 2025 they recorded 101 spills totalling 972 hours, against 140 spills and 1,188 hours in 2024. By hours spilling, it ranks 51 of 289 United Utilities works, where 1 spilled longest.

Works size: 8,246 population equivalent (AUDLEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecAudley Wastewater…1 Jan 2025 02:08 GMT, 45.8 h5 Jan 2025 08:30 GMT, 136.9 h12 Jan 2025 14:04 GMT, 11.4 h13 Jan 2025 08:41 GMT, 42.7 h15 Jan 2025 08:48 GMT, 17.2 h16 Jan 2025 21:25 GMT, 3.9 h24 Jan 2025 06:49 GMT, 4.4 h27 Jan 2025 00:51 GMT, 37.5 h29 Jan 2025 03:55 GMT, 20.6 h31 Jan 2025 02:25 GMT, 24.1 h23 Apr 2025 03:21 GMT, 3.5 h27 May 2025 13:37 GMT, 7.7 h6 Jul 2025 07:04 GMT, 3.9 h21 Jul 2025 21:05 GMT, 51 min7 Sep 2025 13:59 GMT, 99 min17 Sep 2025 07:48 GMT, 5.3 h20 Sep 2025 14:15 GMT, 14.7 h3 Oct 2025 15:01 GMT, 7 h4 Nov 2025 21:36 GMT, 3.5 h11 Nov 2025 22:48 GMT, 2.3 h14 Nov 2025 16:15 GMT, 11.1 h15 Nov 2025 03:23 GMT, 22 min15 Nov 2025 03:46 GMT, 14 min15 Nov 2025 05:13 GMT, 2 min15 Nov 2025 05:26 GMT, 5 min15 Nov 2025 05:58 GMT, 2 min18 Nov 2025 20:35 GMT, 16.6 h19 Nov 2025 13:12 GMT, 25 min23 Nov 2025 09:58 GMT, 12.2 h29 Nov 2025 03:51 GMT, 31.1 h30 Nov 2025 11:24 GMT, 2.5 h30 Nov 2025 14:42 GMT, 7.4 h1 Dec 2025 02:25 GMT, 2.2 h1 Dec 2025 04:42 GMT, 4 min1 Dec 2025 18:14 GMT, 28.3 h4 Dec 2025 14:04 GMT, 11.6 h5 Dec 2025 17:54 GMT, 31.1 h7 Dec 2025 18:40 GMT, 6.6 h9 Dec 2025 04:45 GMT, 44.5 h12 Dec 2025 09:22 GMT, 4.1 h15 Dec 2025 08:02 GMT, 44.4 h17 Dec 2025 09:50 GMT, 76.9 h20 Dec 2025 15:29 GMT, 114 min20 Dec 2025 17:30 GMT, 50 min20 Dec 2025 18:22 GMT, 4.5 h20 Dec 2025 22:56 GMT, 52 min21 Dec 2025 12:29 GMT, 1 min22 Dec 2025 02:23 GMT, 2.6 hAudley Wastewater…1 Jan 2025 01:51 GMT, 104 min1 Jan 2025 05:12 GMT, 14.1 h1 Jan 2025 19:19 GMT, 5.5 h2 Jan 2025 09:54 GMT, 28 min5 Jan 2025 08:05 GMT, 45.8 h7 Jan 2025 06:06 GMT, 2.3 h7 Jan 2025 08:28 GMT, 14.4 h7 Jan 2025 22:52 GMT, 5.1 h8 Jan 2025 07:28 GMT, 2 min8 Jan 2025 07:41 GMT, 4.5 h10 Jan 2025 06:14 GMT, 1 min14 Jan 2025 18:43 GMT, 3 min17 Jan 2025 09:29 GMT, 2 min24 Jan 2025 06:42 GMT, 47 min27 Jan 2025 00:39 GMT, 9.5 h27 Jan 2025 10:21 GMT, 51 min27 Jan 2025 13:29 GMT, 1 min28 Jan 2025 09:46 GMT, 57 min29 Jan 2025 04:09 GMT, 44 min31 Jan 2025 02:13 GMT, 2.4 h31 Jan 2025 06:37 GMT, 37 min23 Apr 2025 02:49 GMT, 2.1 h27 May 2025 13:15 GMT, 2.1 h27 May 2025 15:58 GMT, 26 min27 May 2025 17:05 GMT, 3.1 h6 Jul 2025 06:29 GMT, 3 h7 Sep 2025 13:25 GMT, 96 min17 Sep 2025 07:46 GMT, 3.6 h20 Sep 2025 13:55 GMT, 93 min20 Sep 2025 16:11 GMT, 10.4 h3 Oct 2025 14:55 GMT, 103 min31 Oct 2025 08:22 GMT, 5.7 h4 Nov 2025 21:16 GMT, 117 min11 Nov 2025 22:17 GMT, 103 min14 Nov 2025 16:26 GMT, 8.8 h18 Nov 2025 20:07 GMT, 5.3 h29 Nov 2025 03:35 GMT, 11.2 h1 Dec 2025 18:17 GMT, 4.2 h1 Dec 2025 22:29 GMT, 1 min4 Dec 2025 14:07 GMT, 93 min5 Dec 2025 18:01 GMT, 66 min5 Dec 2025 20:43 GMT, 57 min9 Dec 2025 04:29 GMT, 17.2 h12 Dec 2025 09:31 GMT, 25 min15 Dec 2025 07:40 GMT, 14.9 h16 Dec 2025 07:12 GMT, 58 min17 Dec 2025 10:05 GMT, 3.1 h17 Dec 2025 20:33 GMT, 6.6 h18 Dec 2025 13:01 GMT, 9.6 h19 Dec 2025 04:14 GMT, 1 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150k200kJan 2025: 452 h spilling ≈ 63,807 m³ (range 25,416–160,189 m³)JanFeb 2025: 2.5 h spilling ≈ 353 m³ (range 141–887 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 5.5 h spilling ≈ 777 m³ (range 310–1,951 m³)AprMay 2025: 13 h spilling ≈ 1,879 m³ (range 749–4,718 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 7.7 h spilling ≈ 1,088 m³ (range 433–2,731 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 39 h spilling ≈ 5,468 m³ (range 2,178–13,727 m³)SepOct 2025: 14 h spilling ≈ 2,035 m³ (range 810–5,108 m³)OctNov 2025: 117 h spilling ≈ 16,503 m³ (range 6,573–41,431 m³)NovDec 2025: 321 h spilling ≈ 45,354 m³ (range 18,066–113,864 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 08:30Audley Wastewater Treatment Works5.7 days7,703 – 48,549 m³
17 Dec 2025, 09:50Audley Wastewater Treatment Works3.2 days4,326 – 27,266 m³
5 Jan 2025, 08:05Audley Wastewater Treatment Works1.9 days2,576 – 16,234 m³
1 Jan 2025, 02:08Audley Wastewater Treatment Works1.9 days2,576 – 16,234 m³
9 Dec 2025, 04:45Audley Wastewater Treatment Works1.9 days2,505 – 15,791 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate137,264 m³range 54,675 – 344,606 m³
In litres137.3 millionrange 54.7 million – 344.6 million L
Olympic swimming pools55at 2,500 m³ each
Organic load, as people's raw sewage205,896person-days of untreated BOD

Assumed spill rate while spilling: 15.6 – 98.5 L/s (central 39.2 L/s), from a dry-weather flow of 15.6 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,187 kg12,354 kg68,921 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 5,741 kg58,337 kg248,461 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 104 kg865 kg3,205 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 66 kg357 kg1,861 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 5.5 trillion organisms137.3 trillion organisms3.4 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Audley Wastewater Treatment Works

Inlet overflow at sewage works · discharges to Audley Brook

Spills 2025
62 (737 hours) · down 6% on 2024
Spills 2024
66 (746 hours)
Long-term average
74.1 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Valley Brook (Source to Englesea Brook) (GB112068074630)
Outlet location
SJ7953051750 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00159 · 016810045 · company name: AUDLEY WwTW

Audley Wastewater Treatment Works

Storm tank at sewage works · discharges to Audley Brook

Spills 2025
39 (234 hours) · down 47% on 2024
Spills 2024
74 (442 hours)
Long-term average
74.0 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
Env Act (SODRP) improvement ongoing
WFD catchment
Valley Brook (Source to Englesea Brook) (GB112068074630)
Outlet location
SJ7953051750 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00158 · 016810045 · company name: AUDLEY WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.