Storm overflow register · United Utilities

Bowdon sewage works: storm overflow spills 2025

Bowdon sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to River Bollin. In 2025 it recorded 61 spills totalling 605 hours, against 134 spills and 1,395 hours in 2024. By hours spilling, it ranks 87 of 289 United Utilities works, where 1 spilled longest.

Works size: 7,664 population equivalent (BOWDEN STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBowdon Wastewater…94 spills, 332.1 h, 1 Jan to 18 Jan19 Jan 2025 12:50 GMT, 22 min5 spills, 18.5 h, 20 Jan to 22 Jan12 spills, 29.5 h, 23 Jan to 25 Jan13 spills, 38.4 h, 26 Jan to 29 Jan10 spills, 15.2 h, 31 Jan to 1 Feb3 spills, 0.9 h, 2 Feb to 2 Feb2 spills, 2.6 h, 3 Feb to 3 Feb2 spills, 6.2 h, 7 Mar to 7 Mar3 spills, 5.5 h, 22 Mar to 23 Mar23 Apr 2025 05:26 GMT, 73 min2 spills, 8.5 h, 24 May to 25 May3 spills, 25.6 h, 26 May to 28 May29 May 2025 02:09 GMT, 6.9 h3 Jun 2025 06:57 GMT, 2.7 h6 spills, 14.1 h, 5 Jun to 6 Jun9 Jun 2025 03:44 GMT, 2.9 h10 Jun 2025 00:52 GMT, 6.6 h4 Aug 2025 12:50 GMT, 106 min6 spills, 16.7 h, 16 Sep to 17 Sep5 spills, 23.2 h, 20 Sep to 21 Sep28 spills, 33.6 h, 3 Oct to 5 Oct20 Oct 2025 16:49 GMT, 12.1 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

050k100k150kJan 2025: 433 h spilling ≈ 56,848 m³ (range 22,644-142,718 m³)JanFeb 2025: 4.6 h spilling ≈ 604 m³ (range 241-1,517 m³)FebMar 2025: 12 h spilling ≈ 1,536 m³ (range 612-3,857 m³)MarApr 2025: 1.2 h spilling ≈ 158 m³ (range 63-396 m³)AprMay 2025: 41 h spilling ≈ 5,371 m³ (range 2,139-13,484 m³)MayJun 2025: 26 h spilling ≈ 3,454 m³ (range 1,376-8,671 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 1.8 h spilling ≈ 236 m³ (range 94-593 m³)AugSep 2025: 40 h spilling ≈ 5,240 m³ (range 2,087-13,154 m³)SepOct 2025: 46 h spilling ≈ 6,001 m³ (range 2,390-15,066 m³)OctNov 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)NovDec 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
4 Jan 2025, 08:53Bowdon Wastewater Treatment Works4.7 days5,919 - 37,309 m³
1 Jan 2025, 21:16Bowdon Wastewater Treatment Works1.3 days1,602 - 10,099 m³
3 Jan 2025, 03:55Bowdon Wastewater Treatment Works1.2 days1,504 - 9,478 m³
26 Jan 2025, 23:33Bowdon Wastewater Treatment Works1.1 days1,392 - 8,775 m³
13 Jan 2025, 04:58Bowdon Wastewater Treatment Works23.8 h1,244 - 7,841 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate79,421 m³range 31,635 - 199,390 m³
In litres79.4 millionrange 31.6 million - 199.4 million L
Olympic swimming pools32at 2,500 m³ each
Organic load, as people's raw sewage119,132person-days of untreated BOD

Assumed spill rate while spilling: 14.5 - 91.6 L/s (central 36.5 L/s), from a dry-weather flow of 14.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,265 kg7,148 kg39,878 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 3,322 kg33,754 kg143,760 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 60 kg500 kg1,854 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 38 kg206 kg1,077 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 3.2 trillion organisms79.4 trillion organisms2.0 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Bowdon Wastewater Treatment Works

Storm tank at sewage works · discharges to River Bollin

Spills 2025
61 (605 hours) · down 54% on 2024
Spills 2024
134 (1,395 hours)
Long-term average
148.8 spills a year (monitored since 2020)
Monitor uptime
98% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing
Improvement
Env Act (SODRP) improvement ongoing
WFD catchment
Bollin (Ashley Mill to Manchester Ship Canal) (GB112069061382)
Outlet location
SJ7495085600 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00291 · 016940002 · company name: BOWDON WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.