Storm overflow register · United Utilities

Carlisle sewage works: storm overflow spills 2025

Carlisle sewage treatment works, run by United Utilities, has 2 monitored storm overflows discharging to River Eden. In 2025 they recorded 59 spills totalling 360 hours, against 29 spills and 174 hours in 2024. By hours spilling, it ranks 141 of 289 United Utilities works, where 1 spilled longest.

Works size: 116,547 population equivalent (CARLISLE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecCarlisle WwTW1 Jan 2025 00:00 GMT, 10.1 h2 spills, 7.9 h, 29 May to 29 May2 spills, 2.1 h, 3 Jun to 3 Jun9 Jun 2025 23:48 GMT, 2.5 h14 Jun 2025 04:41 GMT, 13.9 h22 Jun 2025 01:12 GMT, 2.4 h26 Jun 2025 08:58 GMT, 58 min3 spills, 6 h, 1 Jul to 2 Jul2 spills, 2.3 h, 6 Jul to 6 Jul4 Aug 2025 09:25 GMT, 80 min5 spills, 13.5 h, 15 Sep to 15 Sep17 Sep 2025 06:25 GMT, 61 min3 spills, 31.5 h, 19 Sep to 21 Sep3 spills, 4.5 h, 3 Oct to 4 Oct1 Nov 2025 06:19 GMT, 3.4 h4 Nov 2025 08:18 GMT, 33.4 h8 spills, 0.6 h, 10 Nov to 10 Nov8 spills, 52.7 h, 11 Nov to 14 Nov23 Nov 2025 08:57 GMT, 6.1 h24 Nov 2025 20:49 GMT, 25.2 h27 Nov 2025 04:08 GMT, 10.4 h28 Nov 2025 12:33 GMT, 39 min29 Nov 2025 13:03 GMT, 112 min3 spills, 25.5 h, 1 Dec to 2 Dec3 spills, 11.4 h, 7 Dec to 8 Dec5 spills, 5.8 h, 9 Dec to 9 Dec10 Dec 2025 12:53 GMT, 5 min15 Dec 2025 02:44 GMT, 2.2 h18 Dec 2025 22:02 GMT, 25 minCarlisle WwTW2 spills, 3.9 h, 1 Jan to 1 Jan23 May 2025 23:48 GMT, 40 min3 Jun 2025 05:04 GMT, 66 min2 spills, 10.8 h, 14 Jun to 14 Jun21 Jun 2025 23:07 GMT, 2.1 h4 spills, 2.8 h, 30 Jul to 30 Jul1 Sep 2025 09:07 GMT, 1 min9 spills, 9.1 h, 15 Sep to 15 Sep3 spills, 14.9 h, 19 Sep to 20 Sep4 Nov 2025 09:35 GMT, 8.1 h2 spills, 21.2 h, 13 Nov to 13 Nov3 spills, 3.7 h, 23 Nov to 23 Nov2 spills, 7.1 h, 1 Dec to 2 Dec13 spills, 7.3 h, 7 Dec to 7 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0250k500k750k1MJan 2025: 14 h spilling ≈ 27,958 m³ (range 11,136-70,188 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 8.6 h spilling ≈ 17,174 m³ (range 6,841-43,116 m³)MayJun 2025: 36 h spilling ≈ 71,292 m³ (range 28,397-178,981 m³)JunJul 2025: 11 h spilling ≈ 22,166 m³ (range 8,829-55,649 m³)JulAug 2025: 1.3 h spilling ≈ 2,596 m³ (range 1,034-6,518 m³)AugSep 2025: 70 h spilling ≈ 139,588 m³ (range 55,601-350,441 m³)SepOct 2025: 4.5 h spilling ≈ 8,986 m³ (range 3,579-22,561 m³)OctNov 2025: 167 h spilling ≈ 334,292 m³ (range 133,156-839,254 m³)NovDec 2025: 60 h spilling ≈ 119,019 m³ (range 47,408-298,802 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
4 Nov 2025, 08:18Carlisle WwTW1.4 days26,528 - 167,199 m³
19 Sep 2025, 21:24Carlisle WwTW1.2 days23,532 - 148,315 m³
13 Nov 2025, 01:27Carlisle WwTW1.1 days20,867 - 131,520 m³
24 Nov 2025, 20:49Carlisle WwTW1.1 days20,071 - 126,506 m³
11 Nov 2025, 19:48Carlisle WwTW1.0 days19,873 - 125,253 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate718,309 m³range 286,117 - 1.8 million m³
In litres718.3 millionrange 286.1 million - 1.8 billion L
Olympic swimming pools287at 2,500 m³ each
Organic load, as people's raw sewage1.1 millionperson-days of untreated BOD

Assumed spill rate while spilling: 221.0 - 1,392.6 L/s (central 554.7 L/s), from a dry-weather flow of 221.0 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 11,445 kg64,648 kg360,669 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 30,042 kg305,281 kg1.3 million kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 544 kg4,525 kg16,771 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 343 kg1,868 kg9,738 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 28.6 trillion organisms718.3 trillion organisms1.8 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Carlisle WwTW

Storm tank at sewage works (with treatment) · discharges to River Eden

Spills 2025
42 (267 hours) · up 950% on 2024
Spills 2024
4 (55 hours)
Long-term average
32.8 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
Treatment
UV (Ultraviolet)
WFD catchment
Eden - Eamont to tidal (GB102076073940)
Outlet location
NY3847056520 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00405 · 017670049 · company name: CARLISLE WwTW

Carlisle WwTW

Inlet overflow at sewage works · discharges to River Eden

Spills 2025
17 (92 hours) · down 32% on 2024
Spills 2024
25 (119 hours)
Long-term average
44.5 spills a year (monitored since 2019)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Eden - Eamont to tidal (GB102076073940)
Outlet location
NY3847056520 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00406 · 017670049 · company name: CARLISLE WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.