Storm overflow register · United Utilities

High Newton sewage works: storm overflow spills 2025

High Newton sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to Trib Ayside Pool. In 2025 it recorded 111 spills totalling 720 hours, against 164 spills and 1,341 hours in 2024. By hours spilling, it ranks 68 of 289 United Utilities works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHigh Newton STW3 spills, 27.7 h, 1 Jan to 2 Jan2 spills, 6.6 h, 5 Jan to 6 Jan9 spills, 39.2 h, 13 Jan to 15 Jan21 Jan 2025 11:00 GMT, 48 min3 spills, 4.3 h, 23 Jan to 24 Jan6 spills, 8.7 h, 27 Jan to 28 Jan2 spills, 3 h, 31 Jan to 31 Jan2 spills, 6.4 h, 4 Feb to 4 Feb19 Feb 2025 21:32 GMT, 80 min21 Feb 2025 14:58 GMT, 4 min2 spills, 3.2 h, 23 Feb to 23 Feb2 spills, 0.9 h, 29 Mar to 29 Mar14 Apr 2025 19:54 GMT, 42 min16 Apr 2025 15:02 GMT, 18 min19 May 2025 19:00 GMT, 10 min23 May 2025 23:02 GMT, 26 min24 May 2025 19:40 GMT, 24 min6 spills, 6 h, 29 May to 29 May3 Jun 2025 01:20 GMT, 3.8 h5 spills, 3.3 h, 5 Jun to 6 Jun4 spills, 1.4 h, 7 Jun to 7 Jun3 spills, 5.3 h, 9 Jun to 10 Jun10 spills, 7.7 h, 13 Jun to 14 Jun2 spills, 0.4 h, 21 Jun to 22 Jun24 Jun 2025 06:58 GMT, 14 min4 spills, 2.4 h, 26 Jun to 26 Jun2 spills, 2.9 h, 27 Jun to 27 Jun4 Jul 2025 14:16 GMT, 4.7 h2 spills, 1.1 h, 6 Jul to 6 Jul11 spills, 6.8 h, 14 Jul to 15 Jul2 spills, 1.2 h, 20 Jul to 20 Jul3 Aug 2025 06:20 GMT, 30 min3 spills, 4.4 h, 4 Aug to 4 Aug2 spills, 1.2 h, 7 Aug to 7 Aug26 Aug 2025 11:10 GMT, 10 min12 spills, 3.2 h, 27 Aug to 29 Aug1 Sep 2025 10:18 GMT, 12 min2 spills, 0.7 h, 2 Sep to 2 Sep2 spills, 1 h, 3 Sep to 3 Sep5 spills, 1.5 h, 7 Sep to 8 Sep2 spills, 0.3 h, 10 Sep to 10 Sep11 Sep 2025 19:56 GMT, 20 min9 spills, 5.1 h, 12 Sep to 13 Sep46 spills, 184.9 h, 14 Sep to 24 Sep27 Sep 2025 18:10 GMT, 88 min1 Oct 2025 02:52 GMT, 112 min20 spills, 30 h, 2 Oct to 4 Oct3 spills, 1.1 h, 19 Oct to 19 Oct2 spills, 1.2 h, 27 Oct to 27 Oct7 spills, 3.4 h, 1 Nov to 2 Nov15 spills, 69.1 h, 3 Nov to 5 Nov5 spills, 7.9 h, 9 Nov to 10 Nov2 spills, 5.8 h, 11 Nov to 11 Nov9 spills, 25.7 h, 12 Nov to 15 Nov5 spills, 5.3 h, 18 Nov to 18 Nov5 spills, 3.8 h, 22 Nov to 23 Nov6 spills, 5.2 h, 26 Nov to 27 Nov28 Nov 2025 11:02 GMT, 54 min2 spills, 23.2 h, 1 Dec to 2 Dec5 spills, 4.5 h, 4 Dec to 4 Dec11 spills, 113.9 h, 5 Dec to 11 Dec12 Dec 2025 23:08 GMT, 28 min3 spills, 40.4 h, 14 Dec to 15 Dec6 spills, 19.5 h, 17 Dec to 18 Dec19 Dec 2025 16:30 GMT, 4 min

Hours spilling by month, 2025

0100200300Jan 2025: 90 hours spillingJanFeb 2025: 11 hours spillingFebMar 2025: 0.9 hours spillingMarApr 2025: 1.0 hours spillingAprMay 2025: 7.0 hours spillingMayJun 2025: 28 hours spillingJunJul 2025: 14 hours spillingJulAug 2025: 9.4 hours spillingAugSep 2025: 196 hours spillingSepOct 2025: 34 hours spillingOctNov 2025: 127 hours spillingNovDec 2025: 202 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
20 Sep 2025, 17:40High Newton STW3.6 days
4 Nov 2025, 07:32High Newton STW1.6 days
7 Dec 2025, 16:28High Newton STW1.5 days
6 Dec 2025, 11:12High Newton STW1.2 days
14 Dec 2025, 18:14High Newton STW1.2 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate12,330 m³range 4,911 - 30,955 m³
In litres12.3 millionrange 4.9 million - 31.0 million L
Olympic swimming pools4.9at 2,500 m³ each
Organic load, as people's raw sewage18,495person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 196 kg1,110 kg6,191 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 516 kg5,240 kg22,318 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 9.3 kg78 kg288 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 5.9 kg32 kg167 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 491.1 billion organisms12.3 trillion organisms309.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

High Newton STW

Inlet overflow at sewage works · discharges to Trib Ayside Pool

Spills 2025
111 (720 hours) · down 32% on 2024
Spills 2024
164 (1,341 hours)
Long-term average
137.5 spills a year (monitored since 2024)
Monitor uptime
99% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Eea (GB112073071270)
Outlet location
SD3988082900 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP02264 · Unpermitted · company name: High Newton WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.