Storm overflow register · United Utilities

Holme sewage works: storm overflow spills 2025

Holme sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to Holme Beck via SWS. In 2025 it recorded 34 spills totalling 253 hours, against 57 spills and 606 hours in 2024. By hours spilling, it ranks 173 of 289 United Utilities works, where 1 spilled longest.

Works size: 3,539 population equivalent (HOLME STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHolme WwTW3 spills, 47.8 h, 1 Jan to 3 Jan2 spills, 4 h, 5 Jan to 5 Jan2 spills, 15.5 h, 14 Jan to 14 Jan4 spills, 3.6 h, 29 May to 29 May10 spills, 13.9 h, 7 Jun to 7 Jun15 spills, 17.5 h, 9 Jun to 10 Jun5 spills, 2.2 h, 14 Jun to 14 Jun12 spills, 11.1 h, 4 Jul to 5 Jul15 Jul 2025 16:08 GMT, 106 min9 spills, 5.6 h, 20 Jul to 20 Jul3 spills, 0.8 h, 4 Aug to 4 Aug17 spills, 23.7 h, 20 Sep to 21 Sep3 spills, 1.7 h, 3 Oct to 3 Oct23 spills, 55.1 h, 3 Nov to 5 Nov13 Nov 2025 12:24 GMT, 6 min2 spills, 0.7 h, 27 Nov to 27 Nov15 spills, 2.8 h, 1 Dec to 2 Dec58 spills, 37.6 h, 6 Dec to 10 Dec18 spills, 2.1 h, 15 Dec to 15 Dec32 spills, 5.6 h, 17 Dec to 18 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

05,00010k15kJan 2025: 67 h spilling ≈ 4,075 m³ (range 1,623-10,230 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 3.6 h spilling ≈ 218 m³ (range 87-548 m³)MayJun 2025: 34 h spilling ≈ 2,037 m³ (range 812-5,115 m³)JunJul 2025: 18 h spilling ≈ 1,116 m³ (range 444-2,801 m³)JulAug 2025: 0.8 h spilling ≈ 49 m³ (range 19-122 m³)AugSep 2025: 24 h spilling ≈ 1,437 m³ (range 572-3,608 m³)SepOct 2025: 1.7 h spilling ≈ 103 m³ (range 41-259 m³)OctNov 2025: 56 h spilling ≈ 3,390 m³ (range 1,350-8,510 m³)NovDec 2025: 48 h spilling ≈ 2,917 m³ (range 1,162-7,323 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
1 Jan 2025, 00:00Holme WwTW1.9 days1,111 - 7,003 m³
3 Nov 2025, 23:06Holme WwTW1.8 days1,062 - 6,693 m³
20 Sep 2025, 13:52Holme WwTW20.3 h490 - 3,085 m³
9 Dec 2025, 03:14Holme WwTW17.4 h420 - 2,649 m³
14 Jan 2025, 00:45Holme WwTW15.0 h362 - 2,284 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate15,348 m³range 6,113 - 38,531 m³
In litres15.3 millionrange 6.1 million - 38.5 million L
Olympic swimming pools6.1at 2,500 m³ each
Organic load, as people's raw sewage23,022person-days of untreated BOD

Assumed spill rate while spilling: 6.7 - 42.3 L/s (central 16.8 L/s), from a dry-weather flow of 6.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 245 kg1,381 kg7,706 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 642 kg6,523 kg27,781 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 12 kg97 kg358 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 7.3 kg40 kg208 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 611.3 billion organisms15.3 trillion organisms385.3 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Holme WwTW

Storm tank at sewage works · discharges to Holme Beck via SWS

Spills 2025
34 (253 hours) · down 40% on 2024
Spills 2024
57 (606 hours)
Long-term average
44.4 spills a year (monitored since 2017)
Monitor uptime
99% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Holme Beck (GB112073071050)
Outlet location
SD5179078540 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP00981 · 017370138 · company name: HOLME WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.