Storm overflow register · United Utilities

Kidsgrove sewage works: storm overflow spills 2025

Kidsgrove sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to Kidsgrove Stream Wheelock. In 2025 it recorded 27 spills totalling 274 hours, against 52 spills and 741 hours in 2024. By hours spilling, it ranks 168 of 289 United Utilities works, where 1 spilled longest.

Works size: 25,095 population equivalent (KIDSGROVE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecKidsgrove WwTW1 Jan 2025 17:51 GMT, 8.7 h2 Jan 2025 02:53 GMT, 20 min2 Jan 2025 03:25 GMT, 19 min5 Jan 2025 18:48 GMT, 67 h8 Jan 2025 13:45 GMT, 52 min8 Jan 2025 14:59 GMT, 1 min8 Jan 2025 15:29 GMT, 25 min8 Jan 2025 16:38 GMT, 50 min8 Jan 2025 17:29 GMT, 1 min8 Jan 2025 17:44 GMT, 1 min27 Jan 2025 10:21 GMT, 4 h27 Jan 2025 16:29 GMT, 1 min27 Jan 2025 16:44 GMT, 1 min27 Jan 2025 21:44 GMT, 1 min27 Jan 2025 21:59 GMT, 1 min27 Jan 2025 22:28 GMT, 3 min27 Jan 2025 23:14 GMT, 1 min28 Jan 2025 00:29 GMT, 1 min28 Jan 2025 04:44 GMT, 1 min28 Jan 2025 07:14 GMT, 1 min28 Jan 2025 07:29 GMT, 1 min28 Jan 2025 10:14 GMT, 1 min28 Jan 2025 11:57 GMT, 56 min28 Jan 2025 23:29 GMT, 1 min29 Jan 2025 04:57 GMT, 5 min29 Jan 2025 05:07 GMT, 16 min29 Jan 2025 08:43 GMT, 1 min29 Jan 2025 09:14 GMT, 2 min20 Sep 2025 21:03 GMT, 10.8 h21 Sep 2025 07:59 GMT, 70 min21 Sep 2025 09:16 GMT, 18 min21 Sep 2025 09:58 GMT, 22 min29 Sep 2025 08:29 GMT, 1 min12 Nov 2025 21:59 GMT, 1 min14 Nov 2025 23:17 GMT, 7.1 h15 Nov 2025 06:27 GMT, 30 min15 Nov 2025 07:48 GMT, 3.2 h19 Nov 2025 06:09 GMT, 4.4 h19 Nov 2025 10:44 GMT, 21 min29 Nov 2025 12:33 GMT, 15 h30 Nov 2025 03:35 GMT, 14 min4 Dec 2025 18:28 GMT, 7.5 h5 Dec 2025 01:59 GMT, 19 min5 Dec 2025 02:31 GMT, 14 min5 Dec 2025 21:16 GMT, 7.3 h6 Dec 2025 04:53 GMT, 18.6 h6 Dec 2025 23:37 GMT, 28 min7 Dec 2025 22:09 GMT, 3.7 h9 Dec 2025 11:28 GMT, 20.6 h10 Dec 2025 08:29 GMT, 1 min10 Dec 2025 08:43 GMT, 1 min10 Dec 2025 10:13 GMT, 1 min10 Dec 2025 11:46 GMT, 43 min10 Dec 2025 13:14 GMT, 1 min10 Dec 2025 16:14 GMT, 1 min10 Dec 2025 19:12 GMT, 7 min15 Dec 2025 13:19 GMT, 33 h16 Dec 2025 22:34 GMT, 30 min17 Dec 2025 14:23 GMT, 48.5 h19 Dec 2025 14:57 GMT, 28 min19 Dec 2025 15:55 GMT, 2.4 h19 Dec 2025 18:31 GMT, 33 min19 Dec 2025 19:26 GMT, 2.3 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150k200kJan 2025: 84 h spilling ≈ 36,119 m³ (range 14,387–90,678 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 13 h spilling ≈ 5,418 m³ (range 2,158–13,602 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 31 h spilling ≈ 13,201 m³ (range 5,258–33,141 m³)NovDec 2025: 147 h spilling ≈ 63,294 m³ (range 25,211–158,903 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 18:48Kidsgrove WwTW2.8 days11,467 – 72,273 m³
17 Dec 2025, 14:23Kidsgrove WwTW2.0 days8,301 – 52,320 m³
15 Dec 2025, 13:19Kidsgrove WwTW1.4 days5,649 – 35,606 m³
9 Dec 2025, 11:28Kidsgrove WwTW20.6 h3,523 – 22,202 m³
6 Dec 2025, 04:53Kidsgrove WwTW18.6 h3,180 – 20,043 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate117,989 m³range 46,997 – 296,216 m³
In litres118.0 millionrange 47.0 million – 296.2 million L
Olympic swimming pools47at 2,500 m³ each
Organic load, as people's raw sewage176,983person-days of untreated BOD

Assumed spill rate while spilling: 47.6 – 299.9 L/s (central 119.4 L/s), from a dry-weather flow of 47.6 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,880 kg10,619 kg59,243 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 4,935 kg50,145 kg213,572 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 89 kg743 kg2,755 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 56 kg307 kg1,600 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 4.7 trillion organisms118.0 trillion organisms3.0 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Kidsgrove WwTW

Storm tank at sewage works · discharges to Kidsgrove Stream Wheelock

Spills 2025
27 (274 hours) · down 48% on 2024
Spills 2024
52 (741 hours)
Long-term average
23.0 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Kidsgrove Stream (including Day Green Stream) (GB112068055390)
Outlet location
SJ8284055210 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01061 · 016810083 · company name: KIDSGROVE WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.