Storm overflow register · United Utilities

Mere Brow sewage works: storm overflow spills 2025

Mere Brow sewage treatment works, run by United Utilities, has 2 monitored storm overflows discharging to Tarleton Runner, tributary of The Sluice. In 2025 they recorded 107 spills totalling 989 hours, against 158 spills and 1,491 hours in 2024. By hours spilling, it ranks 48 of 289 United Utilities works, where 1 spilled longest.

Works size: 4,254 population equivalent (MERE BROW STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMere Brow WwTW3 spills, 33.5 h, 1 Jan to 2 Jan4 spills, 42.7 h, 5 Jan to 7 Jan8 Jan 2025 12:00 GMT, 2.3 h14 Jan 2025 23:30 GMT, 105 min21 Jan 2025 17:45 GMT, 60 min3 spills, 6 h, 23 Jan to 24 Jan8 spills, 4.8 h, 27 Jan to 28 Jan31 Jan 2025 10:00 GMT, 30 min20 Feb 2025 14:15 GMT, 30 min2 spills, 1 h, 23 Feb to 23 Feb24 Feb 2025 18:45 GMT, 75 min4 spills, 3.3 h, 26 Feb to 27 Feb5 spills, 2.8 h, 23 Mar to 23 Mar26 May 2025 19:38 GMT, 4.7 h29 May 2025 10:06 GMT, 28 min3 Jun 2025 06:34 GMT, 78 min9 spills, 20.2 h, 6 Jun to 8 Jun2 spills, 28.7 h, 9 Jun to 11 Jun2 spills, 10 h, 7 Sep to 8 Sep60 spills, 81.2 h, 12 Sep to 17 Sep18 Sep 2025 16:18 GMT, 32 min14 spills, 9.8 h, 20 Sep to 21 Sep30 spills, 7.2 h, 3 Oct to 5 Oct62 spills, 142.9 h, 24 Oct to 3 Nov12 spills, 8.5 h, 6 Nov to 7 Nov5 spills, 15 h, 10 Nov to 11 Nov4 spills, 1.3 h, 12 Nov to 12 Nov11 spills, 74.1 h, 13 Nov to 17 Nov62 spills, 261 h, 18 Nov to 3 Dec84 spills, 87.4 h, 4 Dec to 11 Dec31 spills, 60.5 h, 14 Dec to 19 DecMere Brow WwTW1 Jan 2025 00:00 GMT, 21 h5 Jan 2025 16:30 GMT, 20.5 h30 Jan 2025 12:49 GMT, 84 min2 spills, 3.3 h, 7 Jun to 7 Jun9 Jun 2025 22:58 GMT, 2.4 h2 spills, 1.4 h, 17 Sep to 17 Sep20 Sep 2025 15:22 GMT, 13.5 h2 spills, 6 h, 3 Oct to 4 Oct1 Dec 2025 14:02 GMT, 16 min2 spills, 3.5 h, 15 Dec to 15 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60k80kJan 2025: 135 h spilling ≈ 9,862 m³ (range 3,928-24,759 m³)JanFeb 2025: 6.0 h spilling ≈ 437 m³ (range 174-1,098 m³)FebMar 2025: 2.8 h spilling ≈ 204 m³ (range 81-512 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 5.1 h spilling ≈ 372 m³ (range 148-933 m³)MayJun 2025: 56 h spilling ≈ 4,075 m³ (range 1,623-10,229 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 117 h spilling ≈ 8,492 m³ (range 3,382-21,319 m³)SepOct 2025: 117 h spilling ≈ 8,535 m³ (range 3,400-21,428 m³)OctNov 2025: 372 h spilling ≈ 27,086 m³ (range 10,789-68,000 m³)NovDec 2025: 179 h spilling ≈ 13,047 m³ (range 5,197-32,756 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
20 Nov 2025, 15:12Mere Brow WwTW2.9 days2,015 - 12,700 m³
25 Nov 2025, 15:38Mere Brow WwTW1.8 days1,261 - 7,948 m³
13 Nov 2025, 20:40Mere Brow WwTW1.6 days1,083 - 6,826 m³
5 Jan 2025, 10:15Mere Brow WwTW1.5 days1,067 - 6,725 m³
1 Jan 2025, 00:00Mere Brow WwTW1.2 days842 - 5,307 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate72,117 m³range 28,726 - 181,053 m³
In litres72.1 millionrange 28.7 million - 181.1 million L
Olympic swimming pools29at 2,500 m³ each
Organic load, as people's raw sewage108,176person-days of untreated BOD

Assumed spill rate while spilling: 8.1 - 50.8 L/s (central 20.2 L/s), from a dry-weather flow of 8.1 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,149 kg6,491 kg36,211 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 3,016 kg30,650 kg130,539 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 55 kg454 kg1,684 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 34 kg188 kg978 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.9 trillion organisms72.1 trillion organisms1.8 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Mere Brow WwTW

Storm tank at sewage works · discharges to Tarleton Runner, tributary of The Sluice

Spills 2025
93 (916 hours) · down 24% on 2024
Spills 2024
123 (1,283 hours)
Long-term average
100.6 spills a year (monitored since 2017)
Monitor uptime
96% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing
Improvement
Env Act (SODRP) improvement ongoing
Bathing water
St Annes
Shellfish water
Ribble
WFD catchment
Back Drain and Sluice (GB112070064880)
Outlet location
SD4240018870 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01284 · 017030002 · company name: MERE BROW WwTW

Mere Brow WwTW

Inlet overflow at sewage works · discharges to Tarleton Runner, tributary of The Sluice

Spills 2025
14 (73 hours) · down 60% on 2024
Spills 2024
35 (208 hours)
Long-term average
36.9 spills a year (monitored since 2017)
Monitor uptime
92% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
Bathing water
St Annes
Shellfish water
Ribble
WFD catchment
Back Drain and Sluice (GB112070064880)
Outlet location
SD4240018870 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01285 · 017030002 · company name: MERE BROW WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.