Storm overflow register · United Utilities

Sedbergh sewage works: storm overflow spills 2025

Sedbergh sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to River Rawthey. In 2025 it recorded 51 spills totalling 432 hours, against 66 spills and 640 hours in 2024. By hours spilling, it ranks 120 of 289 United Utilities works, where 1 spilled longest.

Works size: 2,561 population equivalent (SEDBURGH STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSedbergh STW1 Jan 2025 00:00 GMT, 42.5 h6 Jan 2025 05:00 GMT, 5.5 h14 Jan 2025 00:45 GMT, 75 min24 Jan 2025 03:45 GMT, 90 min26 Jan 2025 09:44 GMT, 24 min26 Jan 2025 10:12 GMT, 93 min27 Jan 2025 03:00 GMT, 2.5 h24 May 2025 20:30 GMT, 114 min26 May 2025 20:58 GMT, 80 min29 May 2025 06:16 GMT, 3.6 h6 Jun 2025 06:50 GMT, 84 min9 Jun 2025 21:00 GMT, 5.2 h14 Jun 2025 01:10 GMT, 104 min4 Jul 2025 17:34 GMT, 4.5 h6 Jul 2025 04:10 GMT, 98 min15 Jul 2025 14:04 GMT, 76 min15 Jul 2025 15:56 GMT, 5.2 h4 Aug 2025 09:10 GMT, 2.5 h1 Sep 2025 12:36 GMT, 46 min12 Sep 2025 22:22 GMT, 40 min13 Sep 2025 00:14 GMT, 72 min13 Sep 2025 03:10 GMT, 54 min15 Sep 2025 09:58 GMT, 4.3 h15 Sep 2025 15:54 GMT, 22.8 h19 Sep 2025 23:50 GMT, 61.5 h3 Oct 2025 13:40 GMT, 9.1 h3 Nov 2025 04:56 GMT, 11.7 h3 Nov 2025 18:28 GMT, 54.6 h11 Nov 2025 20:34 GMT, 72 min12 Nov 2025 23:42 GMT, 5.6 h13 Nov 2025 06:42 GMT, 102 min13 Nov 2025 12:10 GMT, 4.6 h23 Nov 2025 13:46 GMT, 108 min27 Nov 2025 04:44 GMT, 21 h28 Nov 2025 11:38 GMT, 8.6 h29 Nov 2025 18:22 GMT, 2.3 h1 Dec 2025 05:38 GMT, 44.9 h6 Dec 2025 19:08 GMT, 3.9 h7 Dec 2025 17:26 GMT, 3.3 h9 Dec 2025 05:24 GMT, 19.5 h10 Dec 2025 08:16 GMT, 3.8 h10 Dec 2025 13:20 GMT, 2.8 h15 Dec 2025 01:28 GMT, 21.3 h17 Dec 2025 17:48 GMT, 21.7 h18 Dec 2025 18:40 GMT, 7.4 h19 Dec 2025 12:54 GMT, 110 min19 Dec 2025 17:50 GMT, 106 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

05,00010k15kJan 2025: 55 h spilling ≈ 2,422 m³ (range 965–6,081 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 6.9 h spilling ≈ 303 m³ (range 121–760 m³)MayJun 2025: 8.3 h spilling ≈ 364 m³ (range 145–914 m³)JunJul 2025: 13 h spilling ≈ 553 m³ (range 220–1,388 m³)JulAug 2025: 2.5 h spilling ≈ 110 m³ (range 44–275 m³)AugSep 2025: 92 h spilling ≈ 4,037 m³ (range 1,608–10,135 m³)SepOct 2025: 9.1 h spilling ≈ 399 m³ (range 159–1,003 m³)OctNov 2025: 113 h spilling ≈ 4,959 m³ (range 1,975–12,449 m³)NovDec 2025: 132 h spilling ≈ 5,805 m³ (range 2,312–14,575 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
19 Sep 2025, 23:50Sedbergh STW2.6 days1,074 – 6,772 m³
3 Nov 2025, 18:28Sedbergh STW2.3 days954 – 6,015 m³
1 Dec 2025, 05:38Sedbergh STW1.9 days785 – 4,950 m³
1 Jan 2025, 00:00Sedbergh STW1.8 days743 – 4,682 m³
15 Sep 2025, 15:54Sedbergh STW22.8 h398 – 2,508 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate18,952 m³range 7,549 – 47,581 m³
In litres19.0 millionrange 7.5 million – 47.6 million L
Olympic swimming pools7.6at 2,500 m³ each
Organic load, as people's raw sewage28,428person-days of untreated BOD

Assumed spill rate while spilling: 4.9 – 30.6 L/s (central 12.2 L/s), from a dry-weather flow of 4.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 302 kg1,706 kg9,516 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 793 kg8,055 kg34,306 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 14 kg119 kg442 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 9.1 kg49 kg257 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 754.9 billion organisms19.0 trillion organisms475.8 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Sedbergh STW

Storm tank at sewage works · discharges to River Rawthey

Spills 2025
51 (432 hours) · down 23% on 2024
Spills 2024
66 (640 hours)
Long-term average
53.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
Env Act (SODRP) improvement ongoing
WFD catchment
Rawthey - Lower (GB112072071710)
Outlet location
SD6512091160 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01733 · 017270009 · company name: SEDBERGH WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.