Storm overflow register · United Utilities

Stockport sewage works: storm overflow spills 2025

Stockport sewage treatment works, run by United Utilities, has 2 monitored storm overflows discharging to River Mersey. In 2025 they recorded 100 spills totalling 632 hours, against 105 spills and 590 hours in 2024. By hours spilling, it ranks 82 of 289 United Utilities works, where 1 spilled longest.

Works size: 194,071 population equivalent (STOCKPORT STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecStockport WwTW3 spills, 26.3 h, 1 Jan to 2 Jan6 spills, 43.5 h, 5 Jan to 7 Jan13 Jan 2025 16:04 GMT, 20 min20 Jan 2025 18:53 GMT, 2.3 h4 spills, 3.1 h, 23 Jan to 24 Jan3 spills, 6.4 h, 27 Jan to 27 Jan31 Jan 2025 02:46 GMT, 2.9 h20 Feb 2025 15:13 GMT, 64 min23 Feb 2025 20:42 GMT, 2.9 h4 spills, 7.2 h, 26 Feb to 27 Feb2 spills, 4.5 h, 7 Mar to 7 Mar2 spills, 8.5 h, 22 Mar to 23 Mar24 May 2025 01:06 GMT, 2.8 h4 spills, 8.5 h, 26 May to 28 May29 May 2025 02:29 GMT, 2.3 h2 spills, 3.5 h, 3 Jun to 3 Jun4 spills, 9.9 h, 5 Jun to 5 Jun7 Jun 2025 19:46 GMT, 73 min14 Jun 2025 00:31 GMT, 39 min3 spills, 6.1 h, 22 Jun to 23 Jun25 Jun 2025 02:44 GMT, 6 min2 Jul 2025 00:56 GMT, 3.2 h6 Jul 2025 05:44 GMT, 3.4 h2 spills, 5.3 h, 15 Jul to 16 Jul19 Jul 2025 13:42 GMT, 3 h4 spills, 7.4 h, 20 Jul to 22 Jul4 Aug 2025 11:32 GMT, 3.5 h3 spills, 5 h, 3 Sep to 4 Sep7 Sep 2025 13:17 GMT, 2.3 h11 Sep 2025 15:16 GMT, 41 min6 spills, 23.6 h, 15 Sep to 17 Sep20 Sep 2025 12:00 GMT, 18.2 h27 Sep 2025 22:31 GMT, 5.5 h3 spills, 22 h, 2 Oct to 4 Oct2 spills, 5.9 h, 19 Oct to 20 Oct21 Oct 2025 16:58 GMT, 118 min23 Oct 2025 00:48 GMT, 2.6 h2 spills, 4.4 h, 27 Oct to 27 Oct3 spills, 2.1 h, 29 Oct to 30 Oct1 Nov 2025 09:46 GMT, 6 min2 spills, 5.2 h, 4 Nov to 5 Nov3 spills, 17.2 h, 11 Nov to 13 Nov2 spills, 20 h, 14 Nov to 15 Nov18 Nov 2025 15:07 GMT, 6.1 h22 Nov 2025 04:56 GMT, 2.2 h2 spills, 10.6 h, 23 Nov to 23 Nov6 spills, 20.2 h, 28 Nov to 29 Nov6 spills, 6.7 h, 1 Dec to 2 Dec4 Dec 2025 14:01 GMT, 8 h6 Dec 2025 11:43 GMT, 10.4 h3 spills, 15 h, 8 Dec to 9 Dec12 Dec 2025 07:19 GMT, 5.7 h2 spills, 26 h, 14 Dec to 16 Dec3 spills, 19.9 h, 17 Dec to 19 DecStockport WwTW3 spills, 75.3 h, 1 Jan to 4 Jan10 spills, 48.3 h, 5 Jan to 7 Jan9 spills, 9.4 h, 14 Nov to 15 Nov4 spills, 2.4 h, 9 Dec to 9 Dec3 spills, 5.7 h, 13 Dec to 13 Dec6 spills, 32.1 h, 14 Dec to 16 Dec8 spills, 22.9 h, 17 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0500k1M1.5M2MJan 2025: 209 h spilling ≈ 693,324 m³ (range 276,165-1.7 million m³)JanFeb 2025: 11 h spilling ≈ 36,911 m³ (range 14,702-92,666 m³)FebMar 2025: 13 h spilling ≈ 42,896 m³ (range 17,086-107,693 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 14 h spilling ≈ 45,224 m³ (range 18,014-113,537 m³)MayJun 2025: 22 h spilling ≈ 71,494 m³ (range 28,477-179,488 m³)JunJul 2025: 22 h spilling ≈ 73,822 m³ (range 29,405-185,332 m³)JulAug 2025: 3.5 h spilling ≈ 11,639 m³ (range 4,636-29,219 m³)AugSep 2025: 55 h spilling ≈ 183,889 m³ (range 73,247-461,660 m³)SepOct 2025: 39 h spilling ≈ 129,354 m³ (range 51,524-324,748 m³)OctNov 2025: 91 h spilling ≈ 302,602 m³ (range 120,533-759,694 m³)NovDec 2025: 155 h spilling ≈ 514,091 m³ (range 204,773-1.3 million m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
2 Jan 2025, 14:35Stockport WwTW1.6 days49,692 - 313,200 m³
5 Jan 2025, 10:48Stockport WwTW1.6 days49,449 - 311,669 m³
5 Jan 2025, 10:50Stockport WwTW1.6 days49,295 - 310,695 m³
1 Jan 2025, 00:15Stockport WwTW1.5 days47,705 - 300,677 m³
15 Dec 2025, 03:40Stockport WwTW1.3 days40,752 - 256,849 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate2.1 million m³range 837,636 - 5.3 million m³
In litres2.1 billionrange 837.6 million - 5.3 billion L
Olympic swimming pools841at 2,500 m³ each
Organic load, as people's raw sewage3.2 millionperson-days of untreated BOD

Assumed spill rate while spilling: 367.9 - 2,319.0 L/s (central 923.7 L/s), from a dry-weather flow of 367.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 33,505 kg189,263 kg1.1 million kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 87,952 kg893,740 kg3.8 million kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1,592 kg13,248 kg49,099 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1,005 kg5,468 kg28,509 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 83.8 trillion organisms2.1 × 10¹⁵ organisms5.3 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Stockport WwTW

Inlet overflow at sewage works · discharges to River Mersey

Spills 2025
82 (437 hours) · up 28% on 2024
Spills 2024
64 (346 hours)
Long-term average
79.1 spills a year (monitored since 2017)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - Pump failure / issue
Investigation
Env Act (SODRP) investigation ongoing
Improvement
Env Act (SODRP) improvement ongoing
WFD catchment
Mersey (upstream of Manchester Ship Canal) (GB112069061030)
Outlet location
SJ8652089820 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01867 · 016940151 · company name: STOCKPORT WwTW

Stockport WwTW

Storm tank at sewage works · discharges to River Mersey

Spills 2025
18 (196 hours) · down 56% on 2024
Spills 2024
41 (244 hours)
Long-term average
58.6 spills a year (monitored since 2017)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing
Improvement
Env Act (SODRP) improvement ongoing
WFD catchment
Mersey (upstream of Manchester Ship Canal) (GB112069061030)
Outlet location
SJ8652089820 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP01866 · 016940151 · company name: STOCKPORT WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.