Storm overflow register · United Utilities

Wreay Wreay sewage works: storm overflow spills 2025

Wreay Wreay sewage treatment works, run by United Utilities, has 1 monitored storm overflow discharging to The River Petteril. In 2025 it recorded 32 spills totalling 83 hours, against 41 spills and 78 hours in 2024. By hours spilling, it ranks 234 of 289 United Utilities works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWreay WwTW Wreay29 spills, 9 h, 1 Jan to 2 Jan9 Jan 2025 09:11 GMT, 16 min12 Mar 2025 16:44 GMT, 1 min7 Apr 2025 20:29 GMT, 1 min4 spills, 3.2 h, 14 Apr to 14 Apr23 May 2025 07:13 GMT, 2 min29 May 2025 05:46 GMT, 43 min4 spills, 0.4 h, 4 Jun to 4 Jun7 Jun 2025 05:43 GMT, 12 min8 Jun 2025 22:48 GMT, 13 min22 spills, 6.5 h, 14 Jun to 14 Jun2 spills, 1 h, 21 Jun to 21 Jun22 Jun 2025 18:07 GMT, 23 min5 spills, 2.4 h, 1 Jul to 2 Jul14 Jul 2025 10:45 GMT, 15 min19 Jul 2025 12:54 GMT, 21 min4 spills, 0.9 h, 11 Sep to 11 Sep7 spills, 4.6 h, 15 Sep to 15 Sep32 spills, 21.5 h, 19 Sep to 21 Sep3 spills, 0.4 h, 3 Oct to 3 Oct11 spills, 5.3 h, 4 Nov to 4 Nov32 spills, 8 h, 12 Nov to 13 Nov11 spills, 4.7 h, 23 Nov to 23 Nov6 spills, 3.6 h, 1 Dec to 1 Dec22 spills, 6.6 h, 6 Dec to 7 Dec2 spills, 0.4 h, 9 Dec to 9 Dec5 spills, 2.2 h, 15 Dec to 15 Dec

Hours spilling by month, 2025

0102030Jan 2025: 9.2 hours spillingJanFeb 2025: 0.0 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 3.2 hours spillingAprMay 2025: 0.8 hours spillingMayJun 2025: 8.7 hours spillingJunJul 2025: 3.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 27 hours spillingSepOct 2025: 0.4 hours spillingOctNov 2025: 18 hours spillingNovDec 2025: 13 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
19 Sep 2025, 23:25Wreay WwTW Wreay4.5 h
4 Nov 2025, 10:24Wreay WwTW Wreay2.7 h
14 Apr 2025, 11:00Wreay WwTW Wreay2.6 h
20 Sep 2025, 05:18Wreay WwTW Wreay2.3 h
7 Dec 2025, 20:01Wreay WwTW Wreay2.3 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate1,415 m³range 564 - 3,553 m³
In litres1.4 millionrange 563,745 - 3.6 million L
Olympic swimming pools0.6at 2,500 m³ each
Organic load, as people's raw sewage2,123person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 23 kg127 kg711 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 59 kg602 kg2,562 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1.1 kg8.9 kg33 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 0.7 kg3.7 kg19 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 56.4 billion organisms1.4 trillion organisms35.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Wreay WwTW Wreay

Inlet overflow at sewage works · discharges to The River Petteril

Spills 2025
32 (83 hours) · down 22% on 2024
Spills 2024
41 (78 hours)
Long-term average
31.4 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Petteril d/s Blackrack Beck (GB102076074030)
Outlet location
NY4366248788 (OS grid reference) · View on Apple Maps
EA ID / permit
UUP02180 · 017680463 · company name: WREAY WwTW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All United Utilities works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.