Storm overflow register · Wessex Water

Alveston sewage works: storm overflow spills 2025

Alveston sewage treatment works, run by Wessex Water, has 2 monitored storm overflows discharging to Tockington Mill Rhine. In 2025 they recorded 57 spills totalling 657 hours, against 143 spills and 2,227 hours in 2024. By hours spilling, it ranks 57 of 242 Wessex Water works, where 1 spilled longest.

Works size: 2,308 population equivalent (ALVESTON STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecAlveston Wastewater…247 spills, 127.7 h, 5 Jan to 11 Jan64 spills, 16.9 h, 26 Jan to 28 Jan22 spills, 5.5 h, 24 Feb to 24 Feb2 spills, 2.4 h, 7 Sep to 7 Sep5 spills, 2.8 h, 11 Sep to 11 Sep82 spills, 90.2 h, 14 Nov to 18 Nov332 spills, 153.1 h, 1 Dec to 13 Dec32 spills, 191.4 h, 15 Dec to 23 Dec13 spills, 0.8 h, 24 Dec to 24 DecAlveston Wastewater…26 spills, 11 h, 5 Jan to 6 Jan2 spills, 0.5 h, 26 Jan to 26 Jan31 Jul 2025 17:03 GMT, 28 min2 spills, 0.5 h, 3 Sep to 3 Sep3 spills, 2.4 h, 7 Sep to 7 Sep8 spills, 1.3 h, 10 Sep to 11 Sep11 spills, 29.9 h, 14 Nov to 15 Nov4 spills, 0.1 h, 5 Dec to 5 Dec9 spills, 0.5 h, 9 Dec to 9 Dec10 Dec 2025 08:30 GMT, 22 min35 spills, 7.5 h, 15 Dec to 16 Dec19 spills, 11.9 h, 18 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30k40kJan 2025: 156 h spilling ≈ 6,169 m³ (range 2,457-15,488 m³)JanFeb 2025: 5.5 h spilling ≈ 218 m³ (range 87-546 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.5 h spilling ≈ 20 m³ (range 7.9-50 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 9.4 h spilling ≈ 372 m³ (range 148-933 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 120 h spilling ≈ 4,750 m³ (range 1,892-11,924 m³)NovDec 2025: 366 h spilling ≈ 14,458 m³ (range 5,759-36,298 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
15 Dec 2025, 11:05Alveston Wastewater Treatment Works7.5 days2,845 - 17,930 m³
5 Jan 2025, 05:55Alveston Wastewater Treatment Works4.8 days1,796 - 11,318 m³
14 Nov 2025, 09:26Alveston Wastewater Treatment Works3.1 days1,180 - 7,440 m³
8 Dec 2025, 23:53Alveston Wastewater Treatment Works2.2 days825 - 5,202 m³
14 Nov 2025, 11:24Alveston Wastewater Treatment Works1.2 days444 - 2,796 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate25,990 m³range 10,352 - 65,248 m³
In litres26.0 millionrange 10.4 million - 65.2 million L
Olympic swimming pools10at 2,500 m³ each
Organic load, as people's raw sewage38,985person-days of untreated BOD

Assumed spill rate while spilling: 4.4 - 27.6 L/s (central 11.0 L/s), from a dry-weather flow of 4.4 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 414 kg2,339 kg13,050 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,087 kg11,046 kg47,044 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 20 kg164 kg607 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 12 kg68 kg352 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.0 trillion organisms26.0 trillion organisms652.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Alveston Wastewater Treatment Works

Storm tank at sewage works · discharges to Tockington Mill Rhine

Spills 2025
40 (591 hours) · down 62% on 2024
Spills 2024
105 (2,045 hours)
Long-term average
55.8 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Chestle Pill (GB109054026650)
Outlet location
ST6214087040 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00080 · 010002 · company name: ALVESTON LOWER HAZEL STORM TANK

Alveston Wastewater Treatment Works

Inlet overflow at sewage works · discharges to Tockington Mill Rhine

Spills 2025
17 (66 hours) · down 55% on 2024
Spills 2024
38 (182 hours)
Long-term average
30.3 spills a year (monitored since 2023)
Monitor uptime
100% of the year
Investigation
Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Chestle Pill (GB109054026650)
Outlet location
ST6213287039 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00079 · 010002 · company name: ALVESTON LOWER HAZEL INLET

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.