Storm overflow register · Wessex Water

Bourton sewage works: storm overflow spills 2025

Bourton sewage treatment works, run by Wessex Water, has 1 monitored storm overflow discharging to River Stour. In 2025 it recorded 62 spills totalling 812 hours, against 180 spills and 2,913 hours in 2024. By hours spilling, it ranks 43 of 242 Wessex Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBourton Water…1 Jan 2025 13:15 GMT, 28.8 h2 Jan 2025 18:15 GMT, 4 h2 Jan 2025 23:45 GMT, 15 min4 Jan 2025 19:45 GMT, 15 min4 Jan 2025 20:15 GMT, 30 min4 Jan 2025 21:00 GMT, 123.3 h10 Jan 2025 00:30 GMT, 30 min10 Jan 2025 10:15 GMT, 2.5 h10 Jan 2025 13:15 GMT, 30 min10 Jan 2025 14:00 GMT, 30 min10 Jan 2025 15:00 GMT, 15 min10 Jan 2025 15:45 GMT, 15 min10 Jan 2025 16:45 GMT, 5 h11 Jan 2025 14:15 GMT, 15 min11 Jan 2025 15:00 GMT, 15 min20 Jan 2025 17:15 GMT, 30 min23 Jan 2025 15:30 GMT, 53 h26 Jan 2025 00:45 GMT, 30 min26 Jan 2025 02:45 GMT, 15 min26 Jan 2025 03:15 GMT, 30 min26 Jan 2025 04:00 GMT, 45 min26 Jan 2025 10:00 GMT, 30 min26 Jan 2025 10:45 GMT, 86.5 h30 Jan 2025 01:30 GMT, 45 min30 Jan 2025 06:45 GMT, 15 min30 Jan 2025 09:30 GMT, 75 min30 Jan 2025 11:16 GMT, 15 min30 Jan 2025 11:45 GMT, 30 min30 Jan 2025 12:45 GMT, 15 min30 Jan 2025 13:30 GMT, 15 min31 Jan 2025 02:45 GMT, 19.5 h31 Jan 2025 22:31 GMT, 89 min1 Feb 2025 00:00 GMT, 1 min1 Feb 2025 00:30 GMT, 15 min1 Feb 2025 12:15 GMT, 30 min1 Feb 2025 13:00 GMT, 75 min1 Feb 2025 14:45 GMT, 15 min1 Feb 2025 16:00 GMT, 30 min1 Feb 2025 16:45 GMT, 15 min1 Feb 2025 17:15 GMT, 15 min1 Feb 2025 18:15 GMT, 90 min1 Feb 2025 20:00 GMT, 45 min10 Feb 2025 00:15 GMT, 29.5 h11 Feb 2025 06:00 GMT, 15 min11 Feb 2025 06:45 GMT, 17.5 h12 Feb 2025 10:15 GMT, 2 h12 Feb 2025 12:30 GMT, 30 min12 Feb 2025 20:30 GMT, 45 min12 Feb 2025 21:30 GMT, 15 min15 Feb 2025 18:30 GMT, 15 min15 Feb 2025 19:00 GMT, 60 min15 Feb 2025 20:30 GMT, 15 min15 Feb 2025 21:00 GMT, 30 min20 Feb 2025 12:45 GMT, 12.5 h21 Feb 2025 01:30 GMT, 30 min21 Feb 2025 02:15 GMT, 45.8 h23 Feb 2025 00:15 GMT, 45 min23 Feb 2025 10:45 GMT, 110.5 h28 Feb 2025 02:00 GMT, 15 min28 Feb 2025 08:15 GMT, 2.3 h28 Feb 2025 11:00 GMT, 30 min28 Feb 2025 12:15 GMT, 30 min28 Feb 2025 13:15 GMT, 15 min28 Feb 2025 13:45 GMT, 30 min28 Feb 2025 14:45 GMT, 15 min28 Feb 2025 15:16 GMT, 30 min28 Feb 2025 16:16 GMT, 45 min28 Feb 2025 17:15 GMT, 30 min28 Feb 2025 18:00 GMT, 3.5 h28 Feb 2025 21:45 GMT, 75 min28 Feb 2025 23:30 GMT, 15 min1 Mar 2025 11:01 GMT, 15 min1 Mar 2025 12:00 GMT, 31 min1 Mar 2025 13:01 GMT, 60 min1 Mar 2025 14:30 GMT, 75 min1 Mar 2025 16:15 GMT, 16 min1 Mar 2025 16:46 GMT, 15 min1 Mar 2025 17:16 GMT, 30 min1 Mar 2025 18:01 GMT, 30 min1 Mar 2025 18:46 GMT, 74 min1 Mar 2025 20:15 GMT, 31 min1 Mar 2025 21:16 GMT, 30 min2 Mar 2025 12:30 GMT, 46 min2 Mar 2025 13:45 GMT, 15 min2 Mar 2025 14:30 GMT, 15 min2 Mar 2025 15:45 GMT, 15 min2 Mar 2025 16:46 GMT, 30 min2 Mar 2025 18:30 GMT, 76 min2 Mar 2025 20:01 GMT, 15 min2 Mar 2025 20:31 GMT, 15 min5 Jun 2025 08:21 GMT, 2.9 h5 Jun 2025 11:55 GMT, 58 min12 Jun 2025 12:42 GMT, 2 h12 Jun 2025 14:46 GMT, 4 min31 Oct 2025 23:15 GMT, 28 min1 Nov 2025 00:04 GMT, 2.3 h7 Nov 2025 21:02 GMT, 3.3 h10 Nov 2025 09:53 GMT, 10.7 h11 Nov 2025 22:21 GMT, 3.2 h12 Nov 2025 04:59 GMT, 6.6 h13 Nov 2025 22:09 GMT, 3.9 h14 Nov 2025 08:48 GMT, 28.9 h15 Nov 2025 14:08 GMT, 16 min29 Nov 2025 09:54 GMT, 9.1 h29 Nov 2025 19:47 GMT, 26 min1 Dec 2025 09:49 GMT, 25.6 h2 Dec 2025 16:50 GMT, 86 min2 Dec 2025 18:20 GMT, 2.1 h4 Dec 2025 09:18 GMT, 12.7 h4 Dec 2025 22:11 GMT, 44 min4 Dec 2025 23:05 GMT, 4 min4 Dec 2025 23:10 GMT, 14 min5 Dec 2025 17:44 GMT, 12.3 h6 Dec 2025 09:15 GMT, 56 min6 Dec 2025 10:16 GMT, 18 min6 Dec 2025 10:39 GMT, 14 min6 Dec 2025 11:15 GMT, 12 min7 Dec 2025 12:42 GMT, 8.8 h9 Dec 2025 05:06 GMT, 20.3 h15 Dec 2025 20:48 GMT, 23.6 h16 Dec 2025 20:35 GMT, 18 min16 Dec 2025 20:55 GMT, 18 min16 Dec 2025 21:20 GMT, 6 min18 Dec 2025 02:35 GMT, 41.3 h19 Dec 2025 19:54 GMT, 80 min19 Dec 2025 21:17 GMT, 2 min19 Dec 2025 21:31 GMT, 30 min19 Dec 2025 22:05 GMT, 2 min

Hours spilling by month, 2025

0100200300400Jan 2025: 334 hours spillingJanFeb 2025: 240 hours spillingFebMar 2025: 11 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 6.0 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 0.0 hours spillingSepOct 2025: 0.5 hours spillingOctNov 2025: 69 hours spillingNovDec 2025: 153 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
4 Jan 2025, 21:00Bourton Water Recycling Centre5.1 days
23 Feb 2025, 10:45Bourton Water Recycling Centre4.6 days
26 Jan 2025, 10:45Bourton Water Recycling Centre3.6 days
23 Jan 2025, 15:30Bourton Water Recycling Centre2.2 days
21 Feb 2025, 02:15Bourton Water Recycling Centre1.9 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate13,920 m³range 5,545 – 34,947 m³
In litres13.9 millionrange 5.5 million – 34.9 million L
Olympic swimming pools5.6at 2,500 m³ each
Organic load, as people's raw sewage20,880person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 222 kg1,253 kg6,989 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 582 kg5,916 kg25,197 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 11 kg88 kg325 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 6.7 kg36 kg189 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 554.5 billion organisms13.9 trillion organisms349.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Bourton Water Recycling Centre

Storm tank at sewage works · discharges to River Stour

Spills 2025
62 (812 hours) · down 66% on 2024
Spills 2024
180 (2,913 hours)
Long-term average
123.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Stour (Headwaters) (GB108043022490)
Outlet location
ST7863929787 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00157 · 040010 · company name: BOURTON SILTON STORM TANK

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.