Storm overflow register · Wessex Water

Cannington sewage works: storm overflow spills 2025

Cannington sewage treatment works, run by Wessex Water, has 2 monitored storm overflows discharging to Cannington Brook (S). In 2025 they recorded 51 spills totalling 564 hours, against 116 spills and 1,170 hours in 2024. By hours spilling, it ranks 70 of 242 Wessex Water works, where 1 spilled longest.

Works size: 3,162 population equivalent (CANNINGTON STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecCannington Sewage…3 spills, 1.3 h, 1 Jan to 1 Jan31 spills, 97.3 h, 4 Jan to 9 Jan5 spills, 6 h, 24 Jan to 24 Jan33 spills, 88.3 h, 26 Jan to 31 Jan10 spills, 6 h, 23 Feb to 24 Feb3 Sep 2025 14:19 GMT, 42 min12 Nov 2025 08:44 GMT, 4 min11 spills, 28.9 h, 13 Nov to 15 Nov4 spills, 2.5 h, 1 Dec to 1 Dec3 spills, 3 h, 4 Dec to 4 Dec15 spills, 5.2 h, 5 Dec to 6 Dec11 spills, 16.3 h, 9 Dec to 10 Dec12 Dec 2025 10:16 GMT, 10 min81 spills, 159.4 h, 15 Dec to 23 DecCannington Sewage…2 spills, 47.3 h, 4 Jan to 6 Jan3 spills, 52.8 h, 26 Jan to 28 Jan2 spills, 10 h, 13 Nov to 14 Nov15 Dec 2025 21:54 GMT, 18 h6 spills, 21.1 h, 18 Dec to 19 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30k40kJan 2025: 293 h spilling ≈ 15,864 m³ (range 6,319-39,826 m³)JanFeb 2025: 6.0 h spilling ≈ 325 m³ (range 129-816 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.7 h spilling ≈ 38 m³ (range 15-95 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 39 h spilling ≈ 2,113 m³ (range 842-5,305 m³)NovDec 2025: 226 h spilling ≈ 12,234 m³ (range 4,873-30,713 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
26 Jan 2025, 12:30Cannington Sewage Treatment Works2.9 days1,500 - 9,453 m³
4 Jan 2025, 22:45Cannington Sewage Treatment Works2.8 days1,441 - 9,079 m³
4 Jan 2025, 23:00Cannington Sewage Treatment Works1.9 days1,009 - 6,359 m³
26 Jan 2025, 20:00Cannington Sewage Treatment Works1.3 days664 - 4,183 m³
18 Dec 2025, 11:17Cannington Sewage Treatment Works1.3 days661 - 4,167 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate30,568 m³range 12,176 - 76,742 m³
In litres30.6 millionrange 12.2 million - 76.7 million L
Olympic swimming pools12at 2,500 m³ each
Organic load, as people's raw sewage45,852person-days of untreated BOD

Assumed spill rate while spilling: 6.0 - 37.8 L/s (central 15.0 L/s), from a dry-weather flow of 6.0 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 487 kg2,751 kg15,348 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,278 kg12,991 kg55,331 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 23 kg193 kg714 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 15 kg79 kg414 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.2 trillion organisms30.6 trillion organisms767.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Cannington Sewage Treatment Works

Storm tank at sewage works · discharges to Cannington Brook (S)

Spills 2025
38 (415 hours) · down 60% on 2024
Spills 2024
94 (1,023 hours)
Long-term average
56.3 spills a year (monitored since 2018)
Monitor uptime
99% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Cannington Bk - Lower (GB108052021310)
Outlet location
ST2693039370 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00231 · 101442 · company name: CANNINGTON STORM TANK

Cannington Sewage Treatment Works

Inlet overflow at sewage works · discharges to Cannington Brook (S)

Spills 2025
13 (149 hours) · down 41% on 2024
Spills 2024
22 (148 hours)
Long-term average
11.0 spills a year (monitored since 2018)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Cannington Bk - Lower (GB108052021310)
Outlet location
ST2693039370 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00230 · 101442 · company name: CANNINGTON INLET

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.