Storm overflow register · Wessex Water

Haselbury Plucknett sewage works: storm overflow spills 2025

Haselbury Plucknett sewage treatment works, run by Wessex Water, has 1 monitored storm overflow discharging to Small Brook. In 2025 it recorded 83 spills totalling 1,315 hours, against 107 spills and 1,739 hours in 2024. By hours spilling, it ranks 16 of 242 Wessex Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHaselbury Plucknett…6 spills, 3.3 h, 1 Jan to 1 Jan17 spills, 143.3 h, 4 Jan to 12 Jan81 spills, 278.4 h, 23 Jan to 5 Feb7 Feb 2025 10:04 GMT, 4 min11 spills, 207.9 h, 20 Feb to 1 Mar23 Apr 2025 01:41 GMT, 64 min29 Aug 2025 03:22 GMT, 30 min7 Sep 2025 10:14 GMT, 32 min3 spills, 1.2 h, 9 Sep to 10 Sep4 spills, 4.1 h, 19 Oct to 19 Oct3 spills, 0.2 h, 20 Oct to 20 Oct9 spills, 2.6 h, 4 Nov to 5 Nov21 spills, 9.8 h, 9 Nov to 10 Nov40 spills, 52.2 h, 11 Nov to 15 Nov7 spills, 6 h, 22 Nov to 23 Nov4 spills, 1.8 h, 24 Nov to 24 Nov2 spills, 0.3 h, 25 Nov to 25 Nov66 spills, 601.8 h, 1 Dec to 30 Dec

Hours spilling by month, 2025

0200400600800Jan 2025: 346 hours spillingJanFeb 2025: 267 hours spillingFebMar 2025: 20 hours spillingMarApr 2025: 1.1 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 0.0 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.5 hours spillingAugSep 2025: 1.8 hours spillingSepOct 2025: 4.3 hours spillingOctNov 2025: 73 hours spillingNovDec 2025: 602 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
15 Dec 2025, 18:44Haselbury Plucknett WRC11.2 days
23 Feb 2025, 14:24Haselbury Plucknett WRC5.4 days
4 Jan 2025, 22:48Haselbury Plucknett WRC5.1 days
26 Jan 2025, 00:16Haselbury Plucknett WRC4.1 days
7 Dec 2025, 03:02Haselbury Plucknett WRC3.4 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate22,535 m³range 8,976 - 56,576 m³
In litres22.5 millionrange 9.0 million - 56.6 million L
Olympic swimming pools9.0at 2,500 m³ each
Organic load, as people's raw sewage33,803person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 359 kg2,028 kg11,315 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 943 kg9,577 kg40,791 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 17 kg142 kg526 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 11 kg59 kg306 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 897.6 billion organisms22.5 trillion organisms565.8 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Haselbury Plucknett WRC

Storm tank at sewage works · discharges to Small Brook

Spills 2025
83 (1,315 hours) · down 22% on 2024
Spills 2024
107 (1,739 hours)
Long-term average
84.7 spills a year (monitored since 2019)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Broad (GB108052015270)
Outlet location
ST4731011275 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00509 · 102389 · company name: HASELBURY PLUCKNETT NEW LANE STORM TANK

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.