Storm overflow register · Wessex Water

Hillsmoor sewage works: storm overflow spills 2025

Hillsmoor sewage treatment works, run by Wessex Water, has 2 monitored storm overflows discharging to Trib of Hillfarrance Brook. In 2025 they recorded 30 spills totalling 89 hours, against 42 spills and 158 hours in 2024. By hours spilling, it ranks 186 of 242 Wessex Water works, where 1 spilled longest.

Works size: 2,513 population equivalent (WIVELISCOMBE {HILLSMOOR) STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHillsmoor Water…4 Jan 2025 22:00 GMT, 8.3 h5 Jan 2025 07:15 GMT, 4.8 h5 Jan 2025 21:00 GMT, 8.3 h24 Jan 2025 04:00 GMT, 60 min24 Jan 2025 05:30 GMT, 60 min26 Jan 2025 13:15 GMT, 2.5 h26 Jan 2025 20:45 GMT, 4.3 h23 Feb 2025 21:45 GMT, 3.8 h26 Feb 2025 07:45 GMT, 2 h23 Apr 2025 01:41 GMT, 36 min12 Jun 2025 09:44 GMT, 76 min12 Jun 2025 12:13 GMT, 22 min3 Sep 2025 12:11 GMT, 38 min3 Sep 2025 13:14 GMT, 26 min14 Sep 2025 13:59 GMT, 52 min14 Sep 2025 16:14 GMT, 44 min14 Sep 2025 17:21 GMT, 28 min9 Nov 2025 21:27 GMT, 10 min12 Nov 2025 05:46 GMT, 46 min12 Nov 2025 07:03 GMT, 36 min13 Nov 2025 20:15 GMT, 4.8 h14 Nov 2025 14:03 GMT, 8.5 h1 Dec 2025 16:12 GMT, 5.3 h5 Dec 2025 16:14 GMT, 116 min9 Dec 2025 01:21 GMT, 4.4 h9 Dec 2025 09:40 GMT, 4 h15 Dec 2025 13:54 GMT, 70 min15 Dec 2025 20:08 GMT, 8 h18 Dec 2025 12:20 GMT, 6.2 hHillsmoor Water…12 Jun 2025 09:29 GMT, 16 min3 Sep 2025 11:14 GMT, 6 min3 Sep 2025 12:02 GMT, 8 min9 Sep 2025 19:21 GMT, 6 min10 Sep 2025 16:02 GMT, 6 min14 Sep 2025 13:48 GMT, 14 min24 Oct 2025 20:42 GMT, 6 min14 Nov 2025 14:44 GMT, 8 min14 Nov 2025 14:57 GMT, 16 min1 Dec 2025 16:45 GMT, 16 min15 Dec 2025 22:32 GMT, 18 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

01,0002,0003,0004,000Jan 2025: 30 h spilling ≈ 1,292 m³ (range 515–3,243 m³)JanFeb 2025: 5.8 h spilling ≈ 250 m³ (range 99–627 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.6 h spilling ≈ 26 m³ (range 10–65 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 1.9 h spilling ≈ 82 m³ (range 33–205 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 3.8 h spilling ≈ 164 m³ (range 65–411 m³)SepOct 2025: 0.1 h spilling ≈ 4.3 m³ (range 1.7–11 m³)OctNov 2025: 15 h spilling ≈ 659 m³ (range 262–1,654 m³)NovDec 2025: 32 h spilling ≈ 1,361 m³ (range 542–3,416 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 14:03Hillsmoor Water Recycling Centre8.5 h146 – 922 m³
5 Jan 2025, 21:00Hillsmoor Water Recycling Centre8.3 h141 – 892 m³
4 Jan 2025, 22:00Hillsmoor Water Recycling Centre8.3 h141 – 892 m³
15 Dec 2025, 20:08Hillsmoor Water Recycling Centre8.0 h138 – 868 m³
18 Dec 2025, 12:20Hillsmoor Water Recycling Centre6.2 h106 – 670 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate3,832 m³range 1,526 – 9,621 m³
In litres3.8 millionrange 1.5 million – 9.6 million L
Olympic swimming pools1.5at 2,500 m³ each
Organic load, as people's raw sewage5,748person-days of untreated BOD

Assumed spill rate while spilling: 4.8 – 30.0 L/s (central 12.0 L/s), from a dry-weather flow of 4.8 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 61 kg345 kg1,924 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 160 kg1,629 kg6,937 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 2.9 kg24 kg89 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1.8 kg10.0 kg52 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 152.6 billion organisms3.8 trillion organisms96.2 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Hillsmoor Water Recycling Centre

Storm tank at sewage works · discharges to Trib of Hillfarrance Brook

Spills 2025
21 (87 hours) · down 38% on 2024
Spills 2024
34 (154 hours)
Long-term average
28.0 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Hillfarrance Bk (GB108052015510)
Outlet location
ST0861827364 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00542 · NPSWQD000307 · company name: WIVELISCOMBE HILLSMOOR STORM TANK

Hillsmoor Water Recycling Centre

Inlet overflow at sewage works · discharges to Trib of Hillfarrance Brook

Spills 2025
9 (2.0 hours) · up 13% on 2024
Spills 2024
8 (3.8 hours)
Long-term average
8.8 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Hillfarrance Bk (GB108052015510)
Outlet location
ST0857727376 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00541 · NPSWQD000307 · company name: WIVELISCOMBE HILLSMOOR INLET

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.