Storm overflow register · Wessex Water

Nether Stowey Water Recycling Centr sewage works: storm overflow spills 2025

Nether Stowey Water Recycling Centr sewage treatment works, run by Wessex Water, has 1 monitored storm overflow discharging to Fiddington Brook. In 2025 it recorded 19 spills totalling 220 hours, against 37 spills and 424 hours in 2024. By hours spilling, it ranks 151 of 242 Wessex Water works, where 1 spilled longest.

Works size: 2,902 population equivalent (NETHER STOWEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecNether Stowey Water…5 Jan 2025 01:15 GMT, 36.3 h6 Jan 2025 13:45 GMT, 45 min6 Jan 2025 14:45 GMT, 3.3 h6 Jan 2025 18:15 GMT, 105 min6 Jan 2025 20:15 GMT, 15 min6 Jan 2025 21:30 GMT, 15 min6 Jan 2025 22:00 GMT, 30 min7 Jan 2025 03:30 GMT, 15 min7 Jan 2025 04:00 GMT, 30 min7 Jan 2025 05:30 GMT, 3 h7 Jan 2025 08:45 GMT, 15 min7 Jan 2025 09:30 GMT, 15 min26 Jan 2025 14:45 GMT, 20.8 h27 Jan 2025 12:45 GMT, 28 h28 Jan 2025 17:00 GMT, 60 min28 Jan 2025 18:15 GMT, 2.5 h28 Jan 2025 21:00 GMT, 45 min14 Nov 2025 00:20 GMT, 8 min14 Nov 2025 00:42 GMT, 4 min14 Nov 2025 11:44 GMT, 19.7 h15 Nov 2025 07:25 GMT, 12 min15 Nov 2025 07:39 GMT, 64 min15 Nov 2025 08:46 GMT, 6 min15 Nov 2025 08:53 GMT, 4 min15 Nov 2025 09:02 GMT, 4 min15 Nov 2025 09:08 GMT, 6 min15 Nov 2025 09:15 GMT, 12 min15 Nov 2025 09:29 GMT, 6 min15 Nov 2025 09:38 GMT, 6 min15 Nov 2025 09:45 GMT, 6 min15 Nov 2025 09:54 GMT, 6 min15 Nov 2025 10:03 GMT, 4 min15 Nov 2025 10:09 GMT, 4 min15 Nov 2025 10:18 GMT, 12 min15 Nov 2025 10:32 GMT, 2 min15 Nov 2025 10:36 GMT, 2 min15 Nov 2025 10:39 GMT, 4 min15 Nov 2025 10:48 GMT, 4 min15 Nov 2025 10:56 GMT, 2 min15 Nov 2025 11:03 GMT, 2 min15 Nov 2025 11:14 GMT, 2 min15 Nov 2025 11:28 GMT, 2 min15 Nov 2025 11:50 GMT, 4 min1 Dec 2025 20:19 GMT, 3.2 h1 Dec 2025 23:33 GMT, 8 min1 Dec 2025 23:50 GMT, 6 min2 Dec 2025 00:00 GMT, 4 min5 Dec 2025 18:31 GMT, 5 h5 Dec 2025 23:35 GMT, 16 min5 Dec 2025 23:53 GMT, 12 min6 Dec 2025 00:09 GMT, 8 min6 Dec 2025 00:20 GMT, 14 min6 Dec 2025 00:38 GMT, 2 min6 Dec 2025 00:44 GMT, 6 min6 Dec 2025 00:54 GMT, 4 min6 Dec 2025 01:00 GMT, 6 min6 Dec 2025 01:16 GMT, 6 min6 Dec 2025 01:34 GMT, 6 min6 Dec 2025 01:48 GMT, 4 min6 Dec 2025 02:06 GMT, 8 min6 Dec 2025 02:50 GMT, 2 min6 Dec 2025 03:00 GMT, 6 min6 Dec 2025 03:09 GMT, 70 min6 Dec 2025 04:23 GMT, 10 min6 Dec 2025 04:36 GMT, 10 min6 Dec 2025 04:50 GMT, 8 min6 Dec 2025 05:01 GMT, 36 min6 Dec 2025 05:42 GMT, 8 min6 Dec 2025 05:51 GMT, 10 min6 Dec 2025 06:08 GMT, 6 min6 Dec 2025 06:15 GMT, 8 min6 Dec 2025 06:29 GMT, 4 min6 Dec 2025 06:40 GMT, 8 min6 Dec 2025 06:54 GMT, 4 min6 Dec 2025 07:02 GMT, 6 min6 Dec 2025 07:14 GMT, 4 min6 Dec 2025 07:23 GMT, 6 min6 Dec 2025 07:36 GMT, 8 min6 Dec 2025 07:48 GMT, 2 min6 Dec 2025 07:54 GMT, 6 min6 Dec 2025 08:03 GMT, 24 min6 Dec 2025 08:30 GMT, 8 min6 Dec 2025 08:42 GMT, 4 min6 Dec 2025 08:48 GMT, 24 min6 Dec 2025 09:13 GMT, 8 min6 Dec 2025 09:24 GMT, 46 min6 Dec 2025 10:14 GMT, 4 min6 Dec 2025 10:20 GMT, 6 min6 Dec 2025 10:30 GMT, 4 min6 Dec 2025 10:41 GMT, 6 min9 Dec 2025 07:38 GMT, 13.2 h9 Dec 2025 20:53 GMT, 14 min9 Dec 2025 21:11 GMT, 14 min9 Dec 2025 21:29 GMT, 4 min9 Dec 2025 21:38 GMT, 6 min9 Dec 2025 21:47 GMT, 2 min9 Dec 2025 21:54 GMT, 2 min9 Dec 2025 22:02 GMT, 8 min9 Dec 2025 22:21 GMT, 2 min9 Dec 2025 22:27 GMT, 8 min9 Dec 2025 22:38 GMT, 2 min9 Dec 2025 22:48 GMT, 4 min9 Dec 2025 23:15 GMT, 4 min15 Dec 2025 21:40 GMT, 14.4 h16 Dec 2025 12:08 GMT, 2 min16 Dec 2025 12:11 GMT, 4 min16 Dec 2025 12:18 GMT, 12 min16 Dec 2025 12:31 GMT, 8 min16 Dec 2025 12:51 GMT, 7.1 h16 Dec 2025 20:01 GMT, 18 min16 Dec 2025 20:21 GMT, 10 min16 Dec 2025 20:35 GMT, 4 min16 Dec 2025 20:44 GMT, 12 min16 Dec 2025 20:57 GMT, 18 min16 Dec 2025 21:26 GMT, 4 min16 Dec 2025 21:31 GMT, 6 min16 Dec 2025 21:42 GMT, 4 min16 Dec 2025 21:49 GMT, 4 min16 Dec 2025 21:56 GMT, 8 min16 Dec 2025 22:07 GMT, 2 min16 Dec 2025 22:23 GMT, 2 min16 Dec 2025 22:34 GMT, 4 min16 Dec 2025 22:41 GMT, 2 min16 Dec 2025 22:48 GMT, 4 min16 Dec 2025 23:06 GMT, 2 min17 Dec 2025 22:25 GMT, 3.3 h18 Dec 2025 01:48 GMT, 36 min18 Dec 2025 02:28 GMT, 20 min18 Dec 2025 02:51 GMT, 8 min18 Dec 2025 03:02 GMT, 24 min18 Dec 2025 03:29 GMT, 12 min18 Dec 2025 03:45 GMT, 26 min18 Dec 2025 04:14 GMT, 10 min18 Dec 2025 04:25 GMT, 20 min18 Dec 2025 04:48 GMT, 20 min18 Dec 2025 05:12 GMT, 8 min18 Dec 2025 05:24 GMT, 4 min18 Dec 2025 05:30 GMT, 8 min18 Dec 2025 05:39 GMT, 4 min18 Dec 2025 05:48 GMT, 6 min18 Dec 2025 05:57 GMT, 2 min18 Dec 2025 06:02 GMT, 4 min18 Dec 2025 06:11 GMT, 8 min18 Dec 2025 06:31 GMT, 10 min18 Dec 2025 06:44 GMT, 14 min18 Dec 2025 07:00 GMT, 38 min18 Dec 2025 07:39 GMT, 56 min18 Dec 2025 08:39 GMT, 20 min18 Dec 2025 09:02 GMT, 8 min18 Dec 2025 09:11 GMT, 4 min18 Dec 2025 09:18 GMT, 10 min18 Dec 2025 09:31 GMT, 12 min18 Dec 2025 09:45 GMT, 6 min18 Dec 2025 09:54 GMT, 12 min18 Dec 2025 10:09 GMT, 2 min18 Dec 2025 10:16 GMT, 6 min18 Dec 2025 10:36 GMT, 8 min18 Dec 2025 10:56 GMT, 6 min18 Dec 2025 11:08 GMT, 4 min18 Dec 2025 11:14 GMT, 22.3 h19 Dec 2025 09:33 GMT, 4 min19 Dec 2025 09:42 GMT, 4 min19 Dec 2025 09:47 GMT, 8 min19 Dec 2025 10:00 GMT, 2 min19 Dec 2025 15:24 GMT, 4 min19 Dec 2025 15:47 GMT, 2 min19 Dec 2025 16:18 GMT, 2 min19 Dec 2025 16:56 GMT, 4 min19 Dec 2025 17:28 GMT, 2 min19 Dec 2025 18:38 GMT, 4 min22 Dec 2025 01:41 GMT, 62 min22 Dec 2025 02:46 GMT, 3 h22 Dec 2025 05:50 GMT, 3.8 h22 Dec 2025 09:38 GMT, 14 min22 Dec 2025 09:54 GMT, 32 min22 Dec 2025 10:30 GMT, 6 min22 Dec 2025 10:38 GMT, 4 min22 Dec 2025 10:45 GMT, 8 min22 Dec 2025 10:56 GMT, 6 min22 Dec 2025 11:03 GMT, 12 min22 Dec 2025 11:17 GMT, 4 min22 Dec 2025 11:26 GMT, 2 min22 Dec 2025 13:09 GMT, 2 min22 Dec 2025 13:36 GMT, 2 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

05,00010k15kJan 2025: 100 h spilling ≈ 4,982 m³ (range 1,985–12,508 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 23 h spilling ≈ 1,134 m³ (range 452–2,846 m³)NovDec 2025: 97 h spilling ≈ 4,818 m³ (range 1,919–12,096 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 01:15Nether Stowey Water Recycling Centr1.5 days718 – 4,525 m³
27 Jan 2025, 12:45Nether Stowey Water Recycling Centr1.2 days555 – 3,495 m³
18 Dec 2025, 11:14Nether Stowey Water Recycling Centr22.3 h441 – 2,780 m³
26 Jan 2025, 14:45Nether Stowey Water Recycling Centr20.8 h411 – 2,590 m³
14 Nov 2025, 11:44Nether Stowey Water Recycling Centr19.7 h390 – 2,455 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate10,934 m³range 4,355 – 27,451 m³
In litres10.9 millionrange 4.4 million – 27.5 million L
Olympic swimming pools4.4at 2,500 m³ each
Organic load, as people's raw sewage16,402person-days of untreated BOD

Assumed spill rate while spilling: 5.5 – 34.7 L/s (central 13.8 L/s), from a dry-weather flow of 5.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 174 kg984 kg5,490 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 457 kg4,647 kg19,792 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 8.3 kg69 kg255 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 5.2 kg28 kg148 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 435.5 billion organisms10.9 trillion organisms274.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Nether Stowey Water Recycling Centr

Storm tank at sewage works · discharges to Fiddington Brook

Spills 2025
19 (220 hours) · down 49% on 2024
Spills 2024
37 (424 hours)
Long-term average
24.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Fiddington Brook (GB108052021320)
Outlet location
ST2118240192 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW00782 · 102162 · company name: NETHER STOWEY STORM TANK

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.