Storm overflow register · Wessex Water

Podimore Behind Greystones sewage works: storm overflow spills 2025

Podimore Behind Greystones sewage treatment works, run by Wessex Water, has 1 monitored storm overflow discharging to Unnamed tributary of the River Cary. In 2025 it recorded 124 spills totalling 2,198 hours, against 0 spills and 0.0 hours in 2024. By hours spilling, it ranks 4 of 242 Wessex Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecPodimore - Behind…14 spills, 7.3 h, 1 Jan to 1 Jan352 spills, 1644.7 h, 4 Jan to 19 Mar14 spills, 2.8 h, 21 Mar to 22 Mar2 spills, 1.4 h, 23 Mar to 23 Mar15 spills, 1.4 h, 25 Mar to 25 Mar13 spills, 1.1 h, 27 Mar to 27 Mar7 spills, 1.8 h, 28 Mar to 28 Mar6 spills, 1.6 h, 29 Mar to 29 Mar10 spills, 3.5 h, 30 Mar to 30 Mar9 spills, 0.7 h, 5 Apr to 5 Apr10 spills, 1.1 h, 6 Apr to 6 Apr6 spills, 1.5 h, 7 Jun to 7 Jun2 spills, 1.3 h, 12 Jun to 12 Jun3 spills, 1 h, 20 Jul to 20 Jul20 Aug 2025 09:35 GMT, 5 min2 spills, 0.3 h, 28 Aug to 28 Aug29 Aug 2025 12:31 GMT, 7 min2 spills, 1.6 h, 7 Sep to 7 Sep8 Sep 2025 17:07 GMT, 51 min23 Sep 2025 12:27 GMT, 47 min12 spills, 22.9 h, 13 Nov to 15 Nov30 spills, 205.2 h, 4 Dec to 13 Dec8 spills, 2.2 h, 14 Dec to 14 Dec87 spills, 292.8 h, 15 Dec to 29 Dec

Hours spilling by month, 2025

0200400600800Jan 2025: 660 hours spillingJanFeb 2025: 664 hours spillingFebMar 2025: 342 hours spillingMarApr 2025: 1.8 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 2.8 hours spillingJunJul 2025: 1.0 hours spillingJulAug 2025: 0.5 hours spillingAugSep 2025: 3.2 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 23 hours spillingNovDec 2025: 500 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
4 Jan 2025, 19:47Podimore - Behind Greystones - Sewage Treatment Works44.3 days
21 Feb 2025, 02:40Podimore - Behind Greystones - Sewage Treatment Works12.0 days
16 Dec 2025, 00:30Podimore - Behind Greystones - Sewage Treatment Works9.3 days
5 Dec 2025, 16:03Podimore - Behind Greystones - Sewage Treatment Works7.0 days
4 Dec 2025, 06:05Podimore - Behind Greystones - Sewage Treatment Works22.6 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate37,661 m³range 15,001 - 94,551 m³
In litres37.7 millionrange 15.0 million - 94.6 million L
Olympic swimming pools15at 2,500 m³ each
Organic load, as people's raw sewage56,492person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 600 kg3,390 kg18,910 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,575 kg16,006 kg68,171 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 29 kg237 kg879 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 18 kg98 kg511 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.5 trillion organisms37.7 trillion organisms945.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Podimore - Behind Greystones - Sewage Treatment Works

Inlet overflow at sewage works · discharges to Unnamed tributary of the River Cary

Spills 2025
124 (2,198 hours)
Spills 2024
- (- hours)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
Cary - source to conf with KSD (GB108052015140)
Outlet location
ST5443124710 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW01342 · Unpermitted

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.