Storm overflow register · Wessex Water

Toller Porcorum sewage works: storm overflow spills 2025

Toller Porcorum sewage treatment works, run by Wessex Water, has 1 monitored storm overflow discharging to River Hooke. In 2025 it recorded 35 spills totalling 521 hours, against 67 spills and 575 hours in 2024. By hours spilling, it ranks 78 of 242 Wessex Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecToller Porcorum WRC5 Jan 2025 09:04 GMT, 26.3 h6 Jan 2025 12:19 GMT, 15 min26 Jan 2025 14:19 GMT, 46.5 h28 Jan 2025 13:04 GMT, 15 min28 Jan 2025 15:04 GMT, 30 min20 Feb 2025 09:19 GMT, 2.8 h20 Feb 2025 13:04 GMT, 105 min24 Feb 2025 00:49 GMT, 12.8 h24 Feb 2025 13:49 GMT, 20 h26 Feb 2025 10:04 GMT, 3 h26 Feb 2025 13:34 GMT, 52 min26 Feb 2025 15:00 GMT, 6 min26 Feb 2025 15:08 GMT, 2 min26 Feb 2025 16:14 GMT, 32 min26 Feb 2025 18:18 GMT, 2 min26 Feb 2025 18:24 GMT, 10 min26 Feb 2025 18:38 GMT, 2 min26 Feb 2025 18:42 GMT, 26 min26 Feb 2025 19:10 GMT, 26 min26 Feb 2025 19:38 GMT, 4 min4 Sep 2025 05:48 GMT, 2.1 h10 Nov 2025 12:40 GMT, 4.5 h14 Nov 2025 18:02 GMT, 6.9 h22 Nov 2025 13:47 GMT, 12 h23 Nov 2025 04:03 GMT, 9.3 h1 Dec 2025 07:47 GMT, 22.4 h2 Dec 2025 06:15 GMT, 32 min2 Dec 2025 06:53 GMT, 4 min4 Dec 2025 07:47 GMT, 3.8 h4 Dec 2025 11:37 GMT, 2 min4 Dec 2025 11:41 GMT, 2 min5 Dec 2025 17:03 GMT, 28.5 h7 Dec 2025 05:48 GMT, 33.4 h8 Dec 2025 15:24 GMT, 45.1 h10 Dec 2025 12:35 GMT, 4 min10 Dec 2025 12:41 GMT, 38.8 h12 Dec 2025 05:46 GMT, 5.3 h12 Dec 2025 11:08 GMT, 4 min12 Dec 2025 11:15 GMT, 4 min12 Dec 2025 11:21 GMT, 4 min12 Dec 2025 11:28 GMT, 2 min12 Dec 2025 11:33 GMT, 4 min12 Dec 2025 11:39 GMT, 2 min12 Dec 2025 11:51 GMT, 2 min12 Dec 2025 14:17 GMT, 4 min12 Dec 2025 14:23 GMT, 2 min12 Dec 2025 14:28 GMT, 6.8 h12 Dec 2025 21:18 GMT, 72 min12 Dec 2025 22:32 GMT, 4 min12 Dec 2025 22:41 GMT, 6 min12 Dec 2025 22:52 GMT, 6 min12 Dec 2025 23:21 GMT, 2 min12 Dec 2025 23:24 GMT, 2 min15 Dec 2025 22:23 GMT, 28.8 h17 Dec 2025 03:15 GMT, 4 min17 Dec 2025 03:27 GMT, 6 min17 Dec 2025 03:40 GMT, 2 min17 Dec 2025 06:06 GMT, 6.4 h17 Dec 2025 12:35 GMT, 4 min17 Dec 2025 12:42 GMT, 2 min17 Dec 2025 12:53 GMT, 2 min17 Dec 2025 21:49 GMT, 62.7 h20 Dec 2025 12:31 GMT, 6 min20 Dec 2025 12:38 GMT, 8 min20 Dec 2025 12:49 GMT, 12 min20 Dec 2025 13:03 GMT, 83.7 h

Hours spilling by month, 2025

0100200300400Jan 2025: 74 hours spillingJanFeb 2025: 43 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 0.0 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 2.1 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 33 hours spillingNovDec 2025: 369 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
20 Dec 2025, 13:03Toller Porcorum WRC3.5 days
17 Dec 2025, 21:49Toller Porcorum WRC2.6 days
26 Jan 2025, 14:19Toller Porcorum WRC1.9 days
8 Dec 2025, 15:24Toller Porcorum WRC1.9 days
10 Dec 2025, 12:41Toller Porcorum WRC1.6 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate8,922 m³range 3,554 – 22,399 m³
In litres8.9 millionrange 3.6 million – 22.4 million L
Olympic swimming pools3.6at 2,500 m³ each
Organic load, as people's raw sewage13,383person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 142 kg803 kg4,480 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 373 kg3,792 kg16,150 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 6.8 kg56 kg208 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 4.3 kg23 kg121 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 355.4 billion organisms8.9 trillion organisms224.0 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Toller Porcorum WRC

Inlet overflow at sewage works · discharges to River Hooke

Spills 2025
35 (521 hours) · down 48% on 2024
Spills 2024
67 (575 hours)
Long-term average
51.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Hooke (GB108044009800)
Outlet location
SY5669897970 (OS grid reference) · View on Apple Maps
EA ID / permit
WXW01143 · 400607 · company name: TOLLER PORCORUM TOLLER LANE INLET

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Wessex Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.