Storm overflow register · Yorkshire Water

Balby sewage works: storm overflow spills 2025

Balby sewage treatment works, run by Yorkshire Water, has 2 monitored storm overflows discharging to Trib of Mother Drain. In 2025 they recorded 15 spills totalling 110 hours, against 20 spills and 176 hours in 2024. By hours spilling, it ranks 211 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 19,200 population equivalent (BALBY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBalby STW (Yws)5 Jan 2025 20:00 GMT, 28.5 h7 Jan 2025 00:45 GMT, 45 min7 Jan 2025 01:30 GMT, 30 min7 Jan 2025 02:00 GMT, 30 min7 Jan 2025 10:45 GMT, 15 min7 Jan 2025 11:00 GMT, 2.8 h7 Jan 2025 13:45 GMT, 15 min7 Jan 2025 15:15 GMT, 15 min7 Jan 2025 15:30 GMT, 15 min7 Jan 2025 16:15 GMT, 15 min7 Jan 2025 16:45 GMT, 15 min7 Jan 2025 17:00 GMT, 15 min7 Jan 2025 17:30 GMT, 15 min7 Jan 2025 19:15 GMT, 15 min7 Jan 2025 19:30 GMT, 15 min7 Jan 2025 19:45 GMT, 15 min7 Jan 2025 20:00 GMT, 15 min7 Jan 2025 20:15 GMT, 30 min7 Jan 2025 21:00 GMT, 15 min7 Jan 2025 21:15 GMT, 15 min20 Sep 2025 18:30 GMT, 15 min20 Sep 2025 18:45 GMT, 15 min20 Sep 2025 19:00 GMT, 6.8 h21 Sep 2025 01:45 GMT, 30 min21 Sep 2025 02:15 GMT, 60 min21 Sep 2025 03:15 GMT, 15 min21 Sep 2025 03:30 GMT, 15 min21 Sep 2025 03:45 GMT, 15 min21 Sep 2025 04:00 GMT, 15 min14 Nov 2025 14:30 GMT, 30.8 h15 Nov 2025 21:15 GMT, 15 min15 Nov 2025 21:30 GMT, 15 min15 Nov 2025 21:45 GMT, 15 min15 Nov 2025 22:15 GMT, 15 min15 Nov 2025 22:30 GMT, 15 min15 Nov 2025 22:45 GMT, 15 min29 Nov 2025 11:30 GMT, 16 h30 Nov 2025 03:30 GMT, 15 min30 Nov 2025 04:30 GMT, 15 min4 Dec 2025 23:15 GMT, 15 min4 Dec 2025 23:30 GMT, 15 min4 Dec 2025 23:45 GMT, 15 min5 Dec 2025 21:30 GMT, 2 h5 Dec 2025 23:30 GMT, 15 min5 Dec 2025 23:45 GMT, 15 min18 Dec 2025 17:15 GMT, 5.3 h18 Dec 2025 22:30 GMT, 15 min18 Dec 2025 22:45 GMT, 15 min18 Dec 2025 23:00 GMT, 15 minBalby STW (Yws)3 Oct 2025 15:15 GMT, 45 min4 Oct 2025 14:15 GMT, 30 min19 Oct 2025 18:00 GMT, 60 min19 Oct 2025 20:30 GMT, 2.8 h23 Oct 2025 00:45 GMT, 15 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

020k40k60kJan 2025: 37 h spilling ≈ 12,172 m³ (range 4,848–30,559 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 9.8 h spilling ≈ 3,224 m³ (range 1,284–8,094 m³)SepOct 2025: 5.2 h spilling ≈ 1,711 m³ (range 681–4,295 m³)OctNov 2025: 49 h spilling ≈ 16,054 m³ (range 6,395–40,305 m³)NovDec 2025: 9.2 h spilling ≈ 3,027 m³ (range 1,206–7,598 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 14:30Balby STW (Yws)1.3 days4,029 – 25,397 m³
5 Jan 2025, 20:00Balby STW (Yws)1.2 days3,735 – 23,539 m³
29 Nov 2025, 11:30Balby STW (Yws)16.0 h2,097 – 13,215 m³
20 Sep 2025, 19:00Balby STW (Yws)6.8 h885 – 5,575 m³
18 Dec 2025, 17:15Balby STW (Yws)5.3 h688 – 4,336 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate36,188 m³range 14,414 – 90,851 m³
In litres36.2 millionrange 14.4 million – 90.9 million L
Olympic swimming pools14at 2,500 m³ each
Organic load, as people's raw sewage54,282person-days of untreated BOD

Assumed spill rate while spilling: 36.4 – 229.4 L/s (central 91.4 L/s), from a dry-weather flow of 36.4 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 577 kg3,257 kg18,170 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,514 kg15,380 kg65,504 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 27 kg228 kg845 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 17 kg94 kg491 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.4 trillion organisms36.2 trillion organisms908.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Balby STW (Yws)

Storm tank at sewage works · discharges to Trib of Mother Drain

Spills 2025
11 (105 hours) · down 45% on 2024
Spills 2024
20 (176 hours)
Long-term average
31.5 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Mother Drain from Source to R Torne (GB104028058440)
Outlet location
SE5719001070 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01081 · T/83/45405/R · company name: BALBY/STW/STORM TREATMENT

Balby STW (Yws)

Inlet overflow at sewage works · discharges to Trib of Mother Drain

Spills 2025
4 (5.3 hours) · up from 0 on 2024
Spills 2024
0 (0.0 hours)
Long-term average
3.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Mother Drain from Source to R Torne (GB104028058440)
Outlet location
SE5688001130 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01082 · T/83/45405/R · company name: BALBY/STW/6XDWF OVERFLOW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.