Storm overflow register · Yorkshire Water

Beverley sewage works: storm overflow spills 2025

Beverley sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to River Hull. In 2025 it recorded 47 spills totalling 455 hours, against 136 spills and 2,620 hours in 2024. By hours spilling, it ranks 104 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 38,758 population equivalent (BEVERLEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBeverley STW1 Jan 2025 02:00 GMT, 18.8 h5 Jan 2025 07:30 GMT, 65 h9 Jan 2025 18:00 GMT, 3.5 h27 Jan 2025 04:00 GMT, 60 min27 Jan 2025 05:15 GMT, 17 h27 Jan 2025 23:15 GMT, 7 h28 Jan 2025 07:15 GMT, 16 h20 Feb 2025 19:45 GMT, 90 min24 Feb 2025 02:15 GMT, 105 min19 Jul 2025 17:00 GMT, 3.3 h20 Jul 2025 15:30 GMT, 5.3 h21 Jul 2025 02:00 GMT, 15 min4 Sep 2025 14:30 GMT, 5.8 h4 Sep 2025 20:30 GMT, 15 min5 Sep 2025 01:30 GMT, 15 min5 Sep 2025 03:00 GMT, 30 min5 Sep 2025 11:15 GMT, 15 min20 Sep 2025 12:45 GMT, 22.8 h21 Sep 2025 12:45 GMT, 15 min3 Oct 2025 02:30 GMT, 60 min3 Oct 2025 16:45 GMT, 6.8 h4 Nov 2025 20:45 GMT, 2.5 h10 Nov 2025 07:00 GMT, 2 h10 Nov 2025 15:15 GMT, 12 h11 Nov 2025 09:30 GMT, 4.3 h11 Nov 2025 19:15 GMT, 15 min11 Nov 2025 23:30 GMT, 2 h12 Nov 2025 20:45 GMT, 6.5 h14 Nov 2025 06:45 GMT, 40.8 h16 Nov 2025 04:30 GMT, 15 min16 Nov 2025 06:00 GMT, 15 min19 Nov 2025 04:45 GMT, 90 min19 Nov 2025 12:15 GMT, 5 h19 Nov 2025 20:00 GMT, 3 h23 Nov 2025 09:45 GMT, 4.3 h23 Nov 2025 14:15 GMT, 7.5 h29 Nov 2025 07:15 GMT, 40.8 h1 Dec 2025 02:30 GMT, 26.3 h2 Dec 2025 09:15 GMT, 4.5 h2 Dec 2025 14:45 GMT, 15 min4 Dec 2025 20:15 GMT, 4.5 h5 Dec 2025 21:15 GMT, 19 h6 Dec 2025 16:30 GMT, 15 min6 Dec 2025 17:45 GMT, 7.8 h7 Dec 2025 16:15 GMT, 7.3 h9 Dec 2025 05:45 GMT, 32.8 h10 Dec 2025 15:30 GMT, 15 min16 Dec 2025 07:45 GMT, 15.8 h18 Dec 2025 01:00 GMT, 3 h18 Dec 2025 15:00 GMT, 3.8 h18 Dec 2025 19:15 GMT, 2.8 h19 Dec 2025 09:00 GMT, 16.5 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

0100k200k300kJan 2025: 128 h spilling ≈ 85,137 m³ (range 33,912–213,740 m³)JanFeb 2025: 3.2 h spilling ≈ 2,125 m³ (range 846–5,335 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 8.8 h spilling ≈ 5,844 m³ (range 2,328–14,672 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 30 h spilling ≈ 19,923 m³ (range 7,936–50,017 m³)SepOct 2025: 7.8 h spilling ≈ 5,180 m³ (range 2,063–13,004 m³)OctNov 2025: 133 h spilling ≈ 88,192 m³ (range 35,129–221,409 m³)NovDec 2025: 145 h spilling ≈ 95,962 m³ (range 38,224–240,916 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 07:30Beverley STW2.7 days17,194 – 108,371 m³
29 Nov 2025, 07:15Beverley STW1.7 days10,779 – 67,940 m³
14 Nov 2025, 06:45Beverley STW1.7 days10,779 – 67,940 m³
9 Dec 2025, 05:45Beverley STW1.4 days8,663 – 54,602 m³
1 Dec 2025, 02:30Beverley STW1.1 days6,944 – 43,765 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate302,297 m³range 120,411 – 758,928 m³
In litres302.3 millionrange 120.4 million – 758.9 million L
Olympic swimming pools121at 2,500 m³ each
Organic load, as people's raw sewage453,445person-days of untreated BOD

Assumed spill rate while spilling: 73.5 – 463.1 L/s (central 184.5 L/s), from a dry-weather flow of 73.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 4,816 kg27,207 kg151,786 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 12,643 kg128,476 kg547,187 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 229 kg1,904 kg7,058 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 144 kg786 kg4,098 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 12.0 trillion organisms302.3 trillion organisms7.6 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Beverley STW

Storm tank at sewage works · discharges to River Hull

Spills 2025
47 (455 hours) · down 65% on 2024
Spills 2024
136 (2,620 hours)
Long-term average
69.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Hull from Arram Beck to Humber (GB104026067212)
Outlet location
TA0582039340 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01000 · H174 · company name: BEVERLEY/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.