Storm overflow register · Yorkshire Water

Bolsover sewage works: storm overflow spills 2025

Bolsover sewage treatment works, run by Yorkshire Water, has 2 monitored storm overflows discharging to River Doe Lea. In 2025 they recorded 121 spills totalling 768 hours, against 142 spills and 947 hours in 2024. By hours spilling, it ranks 59 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 10,698 population equivalent (BOLSOVER STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBolsover WwTW2 spills, 17.5 h, 1 Jan to 2 Jan3 Jan 2025 14:12 GMT, 4 min4 Jan 2025 09:24 GMT, 4 min206 spills, 90.6 h, 5 Jan to 14 Jan15 Jan 2025 10:52 GMT, 2 min6 spills, 0.5 h, 16 Jan to 16 Jan8 spills, 6.2 h, 24 Jan to 25 Jan28 spills, 42.4 h, 26 Jan to 29 Jan4 spills, 0.3 h, 31 Jan to 31 Jan6 spills, 0.9 h, 2 Feb to 2 Feb7 spills, 3.3 h, 10 Feb to 11 Feb3 spills, 0.2 h, 12 Feb to 12 Feb3 spills, 2.3 h, 13 Feb to 13 Feb2 spills, 1.8 h, 20 Feb to 21 Feb22 Feb 2025 11:06 GMT, 2 min23 Feb 2025 20:06 GMT, 5.5 h22 Mar 2025 17:12 GMT, 2.7 h2 spills, 1 h, 6 Jul to 6 Jul20 Jul 2025 18:32 GMT, 96 min3 Sep 2025 17:02 GMT, 44 min2 spills, 4.1 h, 14 Sep to 14 Sep3 spills, 4 h, 17 Sep to 17 Sep3 spills, 9.8 h, 20 Sep to 21 Sep7 spills, 6 h, 3 Oct to 3 Oct10 spills, 4.1 h, 19 Oct to 20 Oct7 spills, 7 h, 23 Oct to 23 Oct8 spills, 2.9 h, 4 Nov to 4 Nov15 spills, 14.3 h, 10 Nov to 12 Nov60 spills, 59.7 h, 14 Nov to 16 Nov3 spills, 3.2 h, 19 Nov to 19 Nov6 spills, 12.6 h, 23 Nov to 23 Nov5 spills, 45.5 h, 29 Nov to 2 Dec69 spills, 67.4 h, 4 Dec to 10 Dec101 spills, 121.6 h, 15 Dec to 23 DecBolsover WwTW2 spills, 5.8 h, 1 Jan to 1 Jan8 spills, 41 h, 5 Jan to 7 Jan24 Jan 2025 03:30 GMT, 2.3 h10 spills, 14.8 h, 26 Jan to 28 Jan2 spills, 2.5 h, 20 Feb to 20 Feb24 Feb 2025 14:15 GMT, 30 min22 Mar 2025 15:45 GMT, 2.8 h24 May 2025 01:00 GMT, 2.3 h28 May 2025 05:15 GMT, 30 min4 spills, 5 h, 6 Jul to 7 Jul19 Jul 2025 12:45 GMT, 60 min20 Jul 2025 17:00 GMT, 3.3 h2 spills, 2.3 h, 3 Sep to 3 Sep3 spills, 4.5 h, 14 Sep to 14 Sep17 Sep 2025 05:45 GMT, 2.5 h2 spills, 9 h, 20 Sep to 21 Sep2 spills, 1.5 h, 3 Oct to 3 Oct3 spills, 1.5 h, 19 Oct to 20 Oct2 spills, 1 h, 23 Oct to 23 Oct31 Oct 2025 02:15 GMT, 15 min4 Nov 2025 19:15 GMT, 75 min2 spills, 1.5 h, 10 Nov to 10 Nov11 Nov 2025 22:00 GMT, 45 min14 Nov 2025 07:15 GMT, 24 h3 spills, 5.5 h, 23 Nov to 23 Nov5 spills, 15.3 h, 28 Nov to 29 Nov1 Dec 2025 20:00 GMT, 2.5 h18 spills, 66.5 h, 4 Dec to 9 Dec2 spills, 1.8 h, 15 Dec to 15 Dec3 spills, 4.5 h, 17 Dec to 18 Dec21 Dec 2025 21:45 GMT, 45 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

050k100k150kJan 2025: 221 h spilling ≈ 40,584 m³ (range 16,165-101,887 m³)JanFeb 2025: 17 h spilling ≈ 3,116 m³ (range 1,241-7,823 m³)FebMar 2025: 5.5 h spilling ≈ 1,008 m³ (range 402-2,531 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 2.8 h spilling ≈ 513 m³ (range 204-1,289 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 12 h spilling ≈ 2,163 m³ (range 862-5,430 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 37 h spilling ≈ 6,746 m³ (range 2,687-16,935 m³)SepOct 2025: 21 h spilling ≈ 3,886 m³ (range 1,548-9,756 m³)OctNov 2025: 162 h spilling ≈ 29,622 m³ (range 11,799-74,367 m³)NovDec 2025: 290 h spilling ≈ 53,103 m³ (range 21,152-133,318 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 16:30Bolsover WwTW1.4 days2,409 - 15,186 m³
5 Jan 2025, 09:20Bolsover WwTW1.4 days2,366 - 14,910 m³
5 Dec 2025, 17:00Bolsover WwTW1.3 days2,209 - 13,921 m³
18 Dec 2025, 19:10Bolsover WwTW1.2 days2,049 - 12,916 m³
15 Dec 2025, 20:58Bolsover WwTW1.1 days1,850 - 11,658 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate140,741 m³range 56,060 - 353,336 m³
In litres140.7 millionrange 56.1 million - 353.3 million L
Olympic swimming pools56at 2,500 m³ each
Organic load, as people's raw sewage211,111person-days of untreated BOD

Assumed spill rate while spilling: 20.3 - 127.8 L/s (central 50.9 L/s), from a dry-weather flow of 20.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,242 kg12,667 kg70,667 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 5,886 kg59,815 kg254,755 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 107 kg887 kg3,286 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 67 kg366 kg1,908 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 5.6 trillion organisms140.7 trillion organisms3.5 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Bolsover WwTW

Storm tank at sewage works · discharges to River Doe Lea

Spills 2025
76 (540 hours) · down 16% on 2024
Spills 2024
91 (786 hours)
Long-term average
80.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Doe Lea from Source to Hawke Brook (GB104027057290)
Outlet location
SK4591070150 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00062 · 1866 · company name: BOLSOVER/STW

Bolsover WwTW

Inlet overflow at sewage works · discharges to River Doe Lea

Spills 2025
45 (228 hours) · down 12% on 2024
Spills 2024
51 (161 hours)
Long-term average
53.7 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Doe Lea from Source to Hawke Brook (GB104027057290)
Outlet location
SK4591070150 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00063 · 1866 · company name: BOLSOVER/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.