Storm overflow register · Yorkshire Water

Boroughbridge sewage works: storm overflow spills 2025

Boroughbridge sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to Unnamed Trib of Ure. In 2025 it recorded 75 spills totalling 990 hours, against 130 spills and 1,908 hours in 2024. By hours spilling, it ranks 44 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 10,183 population equivalent (BOROUGHBRIDGE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBoroughbridge STW8 spills, 46.8 h, 1 Jan to 3 Jan46 spills, 97.5 h, 5 Jan to 10 Jan36 spills, 38 h, 14 Jan to 16 Jan15 spills, 10.5 h, 24 Jan to 25 Jan42 spills, 63.3 h, 27 Jan to 31 Jan6 spills, 1.5 h, 23 Feb to 24 Feb7 spills, 5.3 h, 23 Mar to 23 Mar2 spills, 6 h, 15 Jul to 16 Jul19 Jul 2025 15:00 GMT, 6.8 h5 spills, 15.3 h, 20 Jul to 21 Jul2 spills, 3 h, 4 Sep to 4 Sep15 Sep 2025 23:00 GMT, 90 min4 spills, 32.5 h, 20 Sep to 22 Sep3 spills, 1.3 h, 28 Sep to 28 Sep14 spills, 23.8 h, 3 Oct to 4 Oct17 spills, 14.3 h, 19 Oct to 20 Oct3 spills, 2.3 h, 24 Oct to 25 Oct46 spills, 78 h, 12 Nov to 16 Nov14 spills, 11.8 h, 19 Nov to 19 Nov16 spills, 14.3 h, 23 Nov to 24 Nov235 spills, 515 h, 29 Nov to 25 Dec5 spills, 1.3 h, 26 Dec to 26 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0100k200k300kJan 2025: 256 h spilling ≈ 44,667 m³ (range 17,792-112,138 m³)JanFeb 2025: 1.5 h spilling ≈ 262 m³ (range 104-657 m³)FebMar 2025: 5.2 h spilling ≈ 907 m³ (range 361-2,278 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 28 h spilling ≈ 4,885 m³ (range 1,946-12,265 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 38 h spilling ≈ 6,665 m³ (range 2,655-16,733 m³)SepOct 2025: 40 h spilling ≈ 7,014 m³ (range 2,794-17,609 m³)OctNov 2025: 136 h spilling ≈ 23,642 m³ (range 9,417-59,354 m³)NovDec 2025: 485 h spilling ≈ 84,588 m³ (range 33,693-212,361 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
4 Dec 2025, 17:30Boroughbridge STW4.4 days7,315 - 46,104 m³
17 Dec 2025, 09:30Boroughbridge STW3.7 days6,203 - 39,095 m³
5 Jan 2025, 17:00Boroughbridge STW3.3 days5,473 - 34,496 m³
9 Dec 2025, 03:30Boroughbridge STW3.0 days4,934 - 31,101 m³
14 Nov 2025, 04:15Boroughbridge STW2.0 days3,353 - 21,135 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate172,648 m³range 68,769 - 433,439 m³
In litres172.6 millionrange 68.8 million - 433.4 million L
Olympic swimming pools69at 2,500 m³ each
Organic load, as people's raw sewage258,972person-days of untreated BOD

Assumed spill rate while spilling: 19.3 - 121.7 L/s (central 48.5 L/s), from a dry-weather flow of 19.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,751 kg15,538 kg86,688 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 7,221 kg73,375 kg312,510 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 131 kg1,088 kg4,031 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 83 kg449 kg2,341 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 6.9 trillion organisms172.6 trillion organisms4.3 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Boroughbridge STW

Storm tank at sewage works · discharges to Unnamed Trib of Ure

Spills 2025
75 (990 hours) · down 42% on 2024
Spills 2024
130 (1,908 hours)
Long-term average
104.8 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Ure from River Tutt to River Swale (GB104027064162)
Outlet location
SE4080067170 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00304 · 27/22/0095 · company name: BOROUGHBRIDGE/NO 2 STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.