Storm overflow register · Yorkshire Water

Earby sewage works: storm overflow spills 2025

Earby sewage treatment works, run by Yorkshire Water, has 2 monitored storm overflows discharging to Earby Beck. In 2025 they recorded 135 spills totalling 419 hours, against 178 spills and 718 hours in 2024. By hours spilling, it ranks 108 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 8,413 population equivalent (EARBY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecEarby Sewage…3 spills, 23 h, 1 Jan to 1 Jan9 spills, 19.3 h, 5 Jan to 7 Jan14 Jan 2025 08:00 GMT, 5.5 h5 spills, 5.5 h, 26 Jan to 27 Jan3 spills, 2 h, 20 Feb to 20 Feb23 Feb 2025 20:30 GMT, 30 min7 Mar 2025 00:30 GMT, 90 min23 Mar 2025 03:00 GMT, 45 min5 spills, 3.3 h, 26 May to 26 May29 May 2025 04:00 GMT, 6.8 h30 May 2025 06:15 GMT, 90 min3 spills, 1.5 h, 3 Jun to 3 Jun2 spills, 0.5 h, 7 Jun to 7 Jun8 Jun 2025 12:30 GMT, 15 min9 Jun 2025 22:00 GMT, 8.3 h3 spills, 0.8 h, 22 Jun to 22 Jun5 Jul 2025 09:00 GMT, 15 min6 Jul 2025 18:30 GMT, 2.5 h15 Jul 2025 16:00 GMT, 5 h2 spills, 5.5 h, 20 Jul to 20 Jul4 spills, 1.3 h, 23 Jul to 23 Jul4 spills, 1.8 h, 4 Aug to 4 Aug28 Aug 2025 16:15 GMT, 45 min2 spills, 1 h, 30 Aug to 30 Aug3 Sep 2025 03:45 GMT, 15 min8 Sep 2025 16:00 GMT, 30 min10 Sep 2025 21:30 GMT, 15 min12 Sep 2025 07:15 GMT, 6.8 h13 Sep 2025 21:15 GMT, 90 min11 spills, 9 h, 15 Sep to 16 Sep4 spills, 1 h, 17 Sep to 17 Sep8 spills, 18 h, 20 Sep to 21 Sep27 Sep 2025 21:45 GMT, 2.5 h12 spills, 30.8 h, 2 Oct to 5 Oct3 spills, 3 h, 19 Oct to 19 Oct29 Oct 2025 21:00 GMT, 15 min12 spills, 5 h, 3 Nov to 5 Nov3 spills, 5 h, 11 Nov to 11 Nov12 Nov 2025 18:00 GMT, 7.3 h14 Nov 2025 19:30 GMT, 15.8 h2 spills, 7 h, 18 Nov to 18 Nov2 spills, 0.5 h, 22 Nov to 22 Nov6 spills, 1.8 h, 23 Nov to 23 Nov28 Nov 2025 12:30 GMT, 3 h29 Nov 2025 12:45 GMT, 90 min7 spills, 8.3 h, 1 Dec to 1 Dec2 spills, 0.8 h, 5 Dec to 5 Dec7 spills, 7.8 h, 6 Dec to 7 Dec3 spills, 6 h, 9 Dec to 9 Dec3 spills, 0.8 h, 10 Dec to 10 Dec8 spills, 18 h, 14 Dec to 15 Dec6 spills, 12.3 h, 17 Dec to 19 DecEarby Sewage…3 spills, 20.3 h, 1 Jan to 1 Jan2 spills, 0.8 h, 6 Jan to 6 Jan5 spills, 6.3 h, 26 Jan to 27 Jan20 Feb 2025 14:30 GMT, 30 min2 spills, 0.8 h, 7 Mar to 7 Mar2 spills, 1.5 h, 26 May to 26 May4 spills, 2.5 h, 29 May to 29 May30 May 2025 07:00 GMT, 15 min2 spills, 0.5 h, 3 Jun to 3 Jun8 Jun 2025 13:15 GMT, 15 min4 spills, 1.8 h, 9 Jun to 10 Jun22 Jun 2025 18:30 GMT, 15 min2 spills, 0.5 h, 6 Jul to 6 Jul2 spills, 2.8 h, 15 Jul to 15 Jul3 spills, 0.8 h, 20 Jul to 20 Jul3 spills, 1 h, 23 Jul to 23 Jul4 Aug 2025 12:00 GMT, 15 min30 Aug 2025 20:30 GMT, 15 min3 Sep 2025 03:00 GMT, 30 min4 Sep 2025 11:15 GMT, 15 min3 spills, 1.5 h, 12 Sep to 12 Sep2 spills, 0.5 h, 13 Sep to 13 Sep7 spills, 5.3 h, 15 Sep to 16 Sep17 Sep 2025 11:15 GMT, 2.5 h7 spills, 17 h, 20 Sep to 21 Sep27 Sep 2025 23:15 GMT, 15 min10 spills, 28 h, 2 Oct to 5 Oct3 spills, 1.5 h, 19 Oct to 20 Oct2 spills, 0.5 h, 29 Oct to 29 Oct11 spills, 7.3 h, 3 Nov to 5 Nov2 spills, 0.8 h, 11 Nov to 11 Nov12 Nov 2025 22:00 GMT, 2.5 h5 spills, 6 h, 14 Nov to 15 Nov4 spills, 1.5 h, 18 Nov to 18 Nov22 Nov 2025 05:00 GMT, 15 min5 spills, 1.8 h, 23 Nov to 23 Nov2 spills, 0.5 h, 28 Nov to 28 Nov29 Nov 2025 13:30 GMT, 15 min4 spills, 8.3 h, 1 Dec to 1 Dec4 Dec 2025 15:30 GMT, 15 min5 spills, 4.8 h, 6 Dec to 7 Dec7 spills, 7 h, 9 Dec to 10 Dec14 Dec 2025 13:15 GMT, 15 min3 spills, 3 h, 15 Dec to 15 Dec3 spills, 2.3 h, 17 Dec to 18 Dec18 Dec 2025 19:15 GMT, 30 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30kJan 2025: 80 h spilling ≈ 11,590 m³ (range 4,616-29,097 m³)JanFeb 2025: 3.0 h spilling ≈ 432 m³ (range 172-1,086 m³)FebMar 2025: 3.0 h spilling ≈ 432 m³ (range 172-1,086 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 16 h spilling ≈ 2,263 m³ (range 901-5,682 m³)MayJun 2025: 14 h spilling ≈ 2,018 m³ (range 804-5,067 m³)JunJul 2025: 20 h spilling ≈ 2,811 m³ (range 1,120-7,057 m³)JulAug 2025: 4.0 h spilling ≈ 577 m³ (range 230-1,448 m³)AugSep 2025: 68 h spilling ≈ 9,745 m³ (range 3,882-24,464 m³)SepOct 2025: 64 h spilling ≈ 9,226 m³ (range 3,675-23,162 m³)OctNov 2025: 68 h spilling ≈ 9,745 m³ (range 3,882-24,464 m³)NovDec 2025: 80 h spilling ≈ 11,532 m³ (range 4,593-28,952 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
1 Jan 2025, 00:00Earby Sewage Treatment Works19.5 h1,120 - 7,057 m³
20 Sep 2025, 16:15Earby Sewage Treatment Works16.3 h933 - 5,881 m³
14 Nov 2025, 19:30Earby Sewage Treatment Works15.8 h904 - 5,700 m³
4 Oct 2025, 08:00Earby Sewage Treatment Works15.8 h904 - 5,700 m³
1 Jan 2025, 08:45Earby Sewage Treatment Works14.8 h847 - 5,338 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate60,371 m³range 24,047 - 151,563 m³
In litres60.4 millionrange 24.0 million - 151.6 million L
Olympic swimming pools24at 2,500 m³ each
Organic load, as people's raw sewage90,556person-days of untreated BOD

Assumed spill rate while spilling: 15.9 - 100.5 L/s (central 40.0 L/s), from a dry-weather flow of 15.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 962 kg5,433 kg30,313 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,525 kg25,658 kg109,277 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 46 kg380 kg1,410 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 29 kg157 kg818 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.4 trillion organisms60.4 trillion organisms1.5 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Earby Sewage Treatment Works

Inlet overflow at sewage works · discharges to Earby Beck

Spills 2025
73 (273 hours) · down 23% on 2024
Spills 2024
95 (458 hours)
Long-term average
99.4 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Earby Beck from Source to Langber beck (GB104027062980)
Outlet location
SD9095047240 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00758 · 3761(SS) · company name: EARBY/STW

Earby Sewage Treatment Works

Inlet overflow at sewage works · discharges to Earby Beck

Spills 2025
62 (146 hours) · down 25% on 2024
Spills 2024
83 (260 hours)
Long-term average
70.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Earby Beck from Source to Langber beck (GB104027062980)
Outlet location
SD9095047240 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00757 · 3761(SS) · company name: EARBY/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.