Storm overflow register · Yorkshire Water

High Royd sewage works: storm overflow spills 2025

High Royd sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to River Calder. In 2025 it recorded 57 spills totalling 548 hours, against 91 spills and 1,052 hours in 2024. By hours spilling, it ranks 83 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 11,595 population equivalent (HIGH ROYD STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHigh Royd Sewage…125 spills, 200.1 h, 1 Jan to 10 Jan69 spills, 43 h, 13 Jan to 15 Jan6 spills, 0.6 h, 27 Jan to 27 Jan4 spills, 0.9 h, 23 Feb to 23 Feb8 spills, 0.3 h, 26 May to 27 May12 Sep 2025 06:52 GMT, 112 min43 spills, 12.3 h, 20 Sep to 21 Sep25 spills, 8.1 h, 3 Oct to 4 Oct9 spills, 5.1 h, 19 Oct to 20 Oct8 spills, 0.4 h, 27 Oct to 27 Oct4 spills, 4 h, 29 Oct to 29 Oct6 spills, 4.6 h, 1 Nov to 1 Nov3 Nov 2025 08:16 GMT, 2 min4 spills, 0.3 h, 4 Nov to 4 Nov12 spills, 1 h, 5 Nov to 5 Nov27 spills, 59.9 h, 14 Nov to 17 Nov29 spills, 5.4 h, 18 Nov to 19 Nov22 Nov 2025 05:36 GMT, 2 min37 spills, 5.6 h, 23 Nov to 24 Nov16 spills, 1.4 h, 28 Nov to 28 Nov29 Nov 2025 20:56 GMT, 2 min225 spills, 33 h, 1 Dec to 3 Dec11 spills, 0.5 h, 4 Dec to 4 Dec164 spills, 98.2 h, 6 Dec to 12 Dec28 spills, 18.8 h, 15 Dec to 15 Dec140 spills, 35.6 h, 17 Dec to 20 Dec5 spills, 6.9 h, 21 Dec to 22 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

050k100k150kJan 2025: 244 h spilling ≈ 48,437 m³ (range 19,293-121,602 m³)JanFeb 2025: 0.9 h spilling ≈ 179 m³ (range 71-449 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.3 h spilling ≈ 60 m³ (range 24-150 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 14 h spilling ≈ 2,821 m³ (range 1,124-7,083 m³)SepOct 2025: 18 h spilling ≈ 3,477 m³ (range 1,385-8,729 m³)OctNov 2025: 78 h spilling ≈ 15,576 m³ (range 6,204-39,104 m³)NovDec 2025: 193 h spilling ≈ 38,384 m³ (range 15,289-96,364 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 07:02High Royd Sewage Treatment Works2.7 days5,205 - 32,803 m³
2 Jan 2025, 18:38High Royd Sewage Treatment Works2.3 days4,400 - 27,732 m³
14 Nov 2025, 11:40High Royd Sewage Treatment Works1.8 days3,448 - 21,730 m³
9 Dec 2025, 14:26High Royd Sewage Treatment Works1.6 days2,968 - 18,704 m³
1 Jan 2025, 00:00High Royd Sewage Treatment Works1.0 days1,905 - 12,004 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate108,913 m³range 43,382 - 273,430 m³
In litres108.9 millionrange 43.4 million - 273.4 million L
Olympic swimming pools44at 2,500 m³ each
Organic load, as people's raw sewage163,369person-days of untreated BOD

Assumed spill rate while spilling: 22.0 - 138.5 L/s (central 55.2 L/s), from a dry-weather flow of 22.0 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,735 kg9,802 kg54,686 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 4,555 kg46,288 kg197,143 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 82 kg686 kg2,543 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 52 kg283 kg1,477 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 4.3 trillion organisms108.9 trillion organisms2.7 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

High Royd Sewage Treatment Works

Storm tank at sewage works · discharges to River Calder

Spills 2025
57 (548 hours) · down 37% on 2024
Spills 2024
91 (1,052 hours)
Long-term average
78.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Calder from Colden Water to Ryburn Confluence (GB104027062641)
Outlet location
SE0469223871 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00815 · 967 · company name: HIGH ROYD/NO 2 STW/3XDWF OVERFLOW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.