Storm overflow register · Yorkshire Water

Hollym sewage works: storm overflow spills 2025

Hollym sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to Trib of Winestead Drain. In 2025 it recorded 101 spills totalling 1,242 hours, against 173 spills and 2,164 hours in 2024. By hours spilling, it ranks 27 of 283 Yorkshire Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHollym WwTW1 Jan 2025 01:15 GMT, 75 min1 Jan 2025 07:00 GMT, 3.3 h1 Jan 2025 14:00 GMT, 90 min1 Jan 2025 19:30 GMT, 30 min1 Jan 2025 20:15 GMT, 30 min2 Jan 2025 02:15 GMT, 45 min4 Jan 2025 11:30 GMT, 30 min4 Jan 2025 21:45 GMT, 45 min5 Jan 2025 04:15 GMT, 106 h9 Jan 2025 14:30 GMT, 30 min14 Jan 2025 19:15 GMT, 60 min24 Jan 2025 04:15 GMT, 17.5 h24 Jan 2025 22:45 GMT, 45 min26 Jan 2025 16:30 GMT, 179.5 h3 Feb 2025 05:00 GMT, 20.5 h4 Feb 2025 10:00 GMT, 3.3 h5 Feb 2025 09:30 GMT, 60 min5 Feb 2025 12:00 GMT, 30 min5 Feb 2025 14:45 GMT, 45 min6 Feb 2025 09:30 GMT, 30 min6 Feb 2025 11:00 GMT, 60 min9 Feb 2025 00:15 GMT, 2.8 h10 Feb 2025 10:45 GMT, 57.3 h15 Feb 2025 09:30 GMT, 90 min15 Feb 2025 18:00 GMT, 30 min15 Feb 2025 18:45 GMT, 60 min16 Feb 2025 04:30 GMT, 3.5 h16 Feb 2025 08:15 GMT, 8.3 h16 Feb 2025 19:15 GMT, 60 min20 Feb 2025 17:15 GMT, 51.8 h23 Feb 2025 09:00 GMT, 5.8 h24 Feb 2025 01:00 GMT, 7.3 h24 Feb 2025 09:30 GMT, 45 min25 Feb 2025 10:00 GMT, 45 min25 Feb 2025 11:15 GMT, 60 min26 Feb 2025 09:00 GMT, 5 h13 Mar 2025 12:30 GMT, 15 min15 Apr 2025 08:00 GMT, 5.5 h21 Apr 2025 17:15 GMT, 75 min24 May 2025 05:00 GMT, 75 min5 Jun 2025 18:30 GMT, 45 min6 Jun 2025 09:30 GMT, 75 min7 Jun 2025 13:30 GMT, 2 h7 Jul 2025 19:15 GMT, 75 min7 Jul 2025 23:15 GMT, 45 min19 Jul 2025 16:15 GMT, 60 min20 Jul 2025 14:30 GMT, 3 h24 Jul 2025 06:45 GMT, 2.5 h27 Aug 2025 20:45 GMT, 75 min3 Sep 2025 15:45 GMT, 2 h4 Sep 2025 13:00 GMT, 2.5 h16 Sep 2025 12:45 GMT, 30 min17 Sep 2025 05:45 GMT, 90 min17 Sep 2025 08:45 GMT, 60 min20 Sep 2025 17:45 GMT, 90 min21 Sep 2025 00:00 GMT, 4.3 h28 Sep 2025 09:15 GMT, 105 min3 Oct 2025 16:15 GMT, 105 min3 Oct 2025 21:15 GMT, 90 min19 Oct 2025 22:30 GMT, 2.5 h20 Oct 2025 15:00 GMT, 90 min23 Oct 2025 02:30 GMT, 9.8 h23 Oct 2025 17:30 GMT, 75 min25 Oct 2025 02:15 GMT, 5.5 h4 Nov 2025 20:45 GMT, 90 min10 Nov 2025 02:30 GMT, 6 h10 Nov 2025 15:00 GMT, 11.3 h12 Nov 2025 00:00 GMT, 3 h14 Nov 2025 07:30 GMT, 46 h18 Nov 2025 15:15 GMT, 2.3 h19 Nov 2025 01:45 GMT, 10.3 h19 Nov 2025 18:15 GMT, 12 h20 Nov 2025 11:45 GMT, 18 h22 Nov 2025 16:00 GMT, 4.5 h23 Nov 2025 08:00 GMT, 39 h25 Nov 2025 12:15 GMT, 105 min28 Nov 2025 14:45 GMT, 5.3 h28 Nov 2025 20:30 GMT, 15 min29 Nov 2025 05:15 GMT, 345.5 h13 Dec 2025 15:00 GMT, 15 min16 Dec 2025 02:30 GMT, 181 h23 Dec 2025 16:15 GMT, 45 min23 Dec 2025 17:30 GMT, 3.3 h

Hours spilling by month, 2025

0200400600Jan 2025: 262 hours spillingJanFeb 2025: 228 hours spillingFebMar 2025: 0.2 hours spillingMarApr 2025: 6.8 hours spillingAprMay 2025: 1.2 hours spillingMayJun 2025: 4.0 hours spillingJunJul 2025: 8.5 hours spillingJulAug 2025: 1.2 hours spillingAugSep 2025: 15 hours spillingSepOct 2025: 24 hours spillingOctNov 2025: 204 hours spillingNovDec 2025: 488 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
29 Nov 2025, 05:15Hollym WwTW14.4 days
16 Dec 2025, 02:30Hollym WwTW7.5 days
26 Jan 2025, 16:30Hollym WwTW7.5 days
5 Jan 2025, 04:15Hollym WwTW4.4 days
10 Feb 2025, 10:45Hollym WwTW2.4 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate21,284 m³range 8,478 – 53,435 m³
In litres21.3 millionrange 8.5 million – 53.4 million L
Olympic swimming pools8.5at 2,500 m³ each
Organic load, as people's raw sewage31,927person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 339 kg1,916 kg10,687 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 890 kg9,046 kg38,527 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 16 kg134 kg497 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 10 kg55 kg289 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 847.8 billion organisms21.3 trillion organisms534.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Hollym WwTW

Inlet overflow at sewage works · discharges to Trib of Winestead Drain

Spills 2025
101 (1,242 hours) · down 42% on 2024
Spills 2024
173 (2,164 hours)
Long-term average
119.7 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Winestead Drain from Source to Humber (GB104026066570)
Outlet location
TA3397025000 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01559 · WRA8060 · company name: HOLLYM/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.