Storm overflow register · Yorkshire Water

Market Weighton sewage works: storm overflow spills 2025

Market Weighton sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to Market Weighton Beck. In 2025 it recorded 41 spills totalling 497 hours, against 104 spills and 1,225 hours in 2024. By hours spilling, it ranks 91 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 7,731 population equivalent (MARKET WEIGHTON STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMarket Weighton STW16 spills, 23.8 h, 1 Jan to 2 Jan68 spills, 85.8 h, 5 Jan to 9 Jan4 spills, 1 h, 10 Jan to 10 Jan41 spills, 22.5 h, 27 Jan to 28 Jan20 Sep 2025 18:30 GMT, 9 h4 Nov 2025 21:30 GMT, 75 min10 Nov 2025 20:45 GMT, 2 h18 spills, 24.5 h, 14 Nov to 15 Nov48 spills, 65.5 h, 29 Nov to 2 Dec199 spills, 129.5 h, 4 Dec to 14 Dec169 spills, 132.3 h, 15 Dec to 23 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

025k50k75k100kJan 2025: 133 h spilling ≈ 17,618 m³ (range 7,018-44,231 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 9.0 h spilling ≈ 1,192 m³ (range 475-2,993 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 63 h spilling ≈ 8,372 m³ (range 3,335-21,018 m³)NovDec 2025: 292 h spilling ≈ 38,654 m³ (range 15,397-97,042 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 11:15Market Weighton STW1.9 days2,414 - 15,215 m³
9 Dec 2025, 04:15Market Weighton STW1.1 days1,398 - 8,813 m³
1 Dec 2025, 03:45Market Weighton STW21.3 h1,121 - 7,067 m³
15 Dec 2025, 07:00Market Weighton STW20.8 h1,095 - 6,901 m³
18 Dec 2025, 14:30Market Weighton STW20.3 h1,068 - 6,734 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate65,836 m³range 26,224 - 165,283 m³
In litres65.8 millionrange 26.2 million - 165.3 million L
Olympic swimming pools26at 2,500 m³ each
Organic load, as people's raw sewage98,754person-days of untreated BOD

Assumed spill rate while spilling: 14.7 - 92.4 L/s (central 36.8 L/s), from a dry-weather flow of 14.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,049 kg5,925 kg33,057 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,753 kg27,980 kg119,169 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 50 kg415 kg1,537 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 31 kg171 kg893 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.6 trillion organisms65.8 trillion organisms1.7 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Market Weighton STW

Storm tank at sewage works · discharges to Market Weighton Beck

Spills 2025
41 (497 hours) · down 61% on 2024
Spills 2024
104 (1,225 hours)
Long-term average
55.5 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Foulness from Black Beck to Market Weighton Canal (GB104026066690)
Outlet location
SE8681040700 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01001 · H226 · company name: MARKET WEIGHTON/NO 2 STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.