Storm overflow register · Yorkshire Water

Selby Sewage Treament Works sewage works: storm overflow spills 2025

Selby Sewage Treament Works sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to The River Ouse (Tidal). In 2025 it recorded 38 spills totalling 219 hours, against 43 spills and 374 hours in 2024. By hours spilling, it ranks 169 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 27,187 population equivalent (SELBY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSelby Sewage Treament…9 spills, 17 h, 1 Jan to 1 Jan54 spills, 51 h, 5 Jan to 8 Jan7 spills, 5 h, 27 Jan to 28 Jan2 spills, 1.3 h, 23 Feb to 24 Feb26 Feb 2025 09:30 GMT, 105 min2 spills, 3.8 h, 23 Mar to 23 Mar4 spills, 1.3 h, 6 Jul to 6 Jul2 spills, 2 h, 19 Jul to 19 Jul5 spills, 4.5 h, 20 Jul to 20 Jul21 Jul 2025 16:30 GMT, 2.3 h13 spills, 7.3 h, 20 Sep to 21 Sep3 Oct 2025 16:45 GMT, 3.3 h8 spills, 4.8 h, 19 Oct to 20 Oct31 Oct 2025 18:45 GMT, 2.3 h10 Nov 2025 21:45 GMT, 15 min13 spills, 18.5 h, 14 Nov to 15 Nov47 spills, 26 h, 29 Nov to 1 Dec24 spills, 11.8 h, 4 Dec to 6 Dec2 spills, 1.5 h, 6 Dec to 6 Dec33 spills, 14.5 h, 9 Dec to 10 Dec56 spills, 18.8 h, 15 Dec to 16 Dec28 spills, 20.3 h, 18 Dec to 20 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

025k50k75k100kJan 2025: 73 h spilling ≈ 34,006 m³ (range 13,545-85,373 m³)JanFeb 2025: 3.0 h spilling ≈ 1,398 m³ (range 557-3,508 m³)FebMar 2025: 3.8 h spilling ≈ 1,770 m³ (range 705-4,444 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 10 h spilling ≈ 4,658 m³ (range 1,856-11,695 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 7.2 h spilling ≈ 3,354 m³ (range 1,336-8,420 m³)SepOct 2025: 10 h spilling ≈ 4,752 m³ (range 1,893-11,929 m³)OctNov 2025: 37 h spilling ≈ 17,003 m³ (range 6,773-42,687 m³)NovDec 2025: 75 h spilling ≈ 34,938 m³ (range 13,916-87,712 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
1 Jan 2025, 07:00Selby Sewage Treament Works11.3 h2,087 - 13,157 m³
15 Nov 2025, 04:00Selby Sewage Treament Works11.0 h2,041 - 12,864 m³
7 Jan 2025, 10:45Selby Sewage Treament Works10.3 h1,902 - 11,987 m³
6 Jan 2025, 16:45Selby Sewage Treament Works10.3 h1,902 - 11,987 m³
18 Dec 2025, 22:45Selby Sewage Treament Works6.8 h1,252 - 7,894 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate101,924 m³range 40,599 - 255,885 m³
In litres101.9 millionrange 40.6 million - 255.9 million L
Olympic swimming pools41at 2,500 m³ each
Organic load, as people's raw sewage152,887person-days of untreated BOD

Assumed spill rate while spilling: 51.5 - 324.9 L/s (central 129.4 L/s), from a dry-weather flow of 51.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,624 kg9,173 kg51,177 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 4,263 kg43,318 kg184,493 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 77 kg642 kg2,380 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 49 kg265 kg1,382 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 4.1 trillion organisms101.9 trillion organisms2.6 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Selby Sewage Treament Works

Storm tank at sewage works · discharges to The River Ouse (Tidal)

Spills 2025
38 (219 hours) · down 12% on 2024
Spills 2024
43 (374 hours)
Long-term average
42.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Ouse from R Wharfe to Upper Humber (GB104027064270)
Outlet location
SE6356031650 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS01047 · QR.27/24/0096 · company name: SELBY/NO 2 STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.