Storm overflow register · Yorkshire Water

Skelton On Ure Wpc Works sewage works: storm overflow spills 2025

Skelton On Ure Wpc Works sewage treatment works, run by Yorkshire Water, has 2 monitored storm overflows discharging to Scour Gutter. In 2025 they recorded 171 spills totalling 1,798 hours, against 252 spills and 3,057 hours in 2024. By hours spilling, it ranks 6 of 283 Yorkshire Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSkelton on Ure Wpc…14 spills, 34 h, 1 Jan to 2 Jan218 spills, 230.5 h, 5 Jan to 22 Jan19 spills, 25.3 h, 24 Jan to 25 Jan65 spills, 134.5 h, 26 Jan to 3 Feb9 Feb 2025 04:30 GMT, 45 min8 spills, 4.8 h, 20 Feb to 22 Feb43 spills, 27.8 h, 23 Feb to 25 Feb2 spills, 0.5 h, 26 Feb to 26 Feb2 spills, 7.3 h, 22 Mar to 23 Mar25 Mar 2025 04:30 GMT, 60 min24 May 2025 01:30 GMT, 2 h27 May 2025 00:00 GMT, 15 min30 May 2025 07:30 GMT, 15 min22 Jun 2025 16:15 GMT, 15 min15 Jul 2025 19:00 GMT, 4.8 h19 Jul 2025 12:00 GMT, 6.5 h20 Jul 2025 16:00 GMT, 4 h21 Jul 2025 17:45 GMT, 15 min22 Jul 2025 14:45 GMT, 45 min4 Sep 2025 15:15 GMT, 2.5 h4 spills, 3.3 h, 15 Sep to 15 Sep20 Sep 2025 08:15 GMT, 21.3 h27 Sep 2025 23:45 GMT, 5.8 h1 Oct 2025 08:30 GMT, 75 min3 spills, 12 h, 2 Oct to 3 Oct19 Oct 2025 16:45 GMT, 10.3 h2 spills, 1.5 h, 24 Oct to 25 Oct2 spills, 2 h, 4 Nov to 5 Nov2 spills, 4.8 h, 11 Nov to 12 Nov3 spills, 7.5 h, 12 Nov to 13 Nov10 spills, 41.5 h, 14 Nov to 16 Nov3 spills, 6.3 h, 19 Nov to 19 Nov29 spills, 17.3 h, 23 Nov to 25 Nov123 spills, 537 h, 28 Nov to 24 DecSkelton on Ure Wpc…1 Jan 2025 02:00 GMT, 15 h5 Jan 2025 13:30 GMT, 91.8 h14 Jan 2025 14:45 GMT, 9.5 h24 Jan 2025 03:00 GMT, 7.3 h2 spills, 70.3 h, 26 Jan to 29 Jan20 Feb 2025 14:45 GMT, 75 min3 spills, 5 h, 23 Feb to 23 Feb23 Mar 2025 07:45 GMT, 3.5 h24 May 2025 00:30 GMT, 2 h30 May 2025 06:00 GMT, 30 min22 Jun 2025 14:45 GMT, 60 min2 spills, 4.5 h, 15 Jul to 15 Jul16 Jul 2025 20:45 GMT, 15 min2 spills, 6.3 h, 19 Jul to 19 Jul20 Jul 2025 14:30 GMT, 4.8 h21 Jul 2025 16:15 GMT, 45 min22 Jul 2025 13:30 GMT, 75 min2 Sep 2025 12:45 GMT, 15 min4 Sep 2025 13:45 GMT, 2.5 h14 Sep 2025 17:15 GMT, 15 min15 Sep 2025 12:30 GMT, 60 min2 spills, 17.8 h, 20 Sep to 21 Sep27 Sep 2025 23:30 GMT, 4.8 h1 Oct 2025 07:30 GMT, 60 min2 spills, 10.3 h, 2 Oct to 3 Oct3 spills, 7.3 h, 19 Oct to 20 Oct29 Oct 2025 03:00 GMT, 30 min4 Nov 2025 20:00 GMT, 30 min3 spills, 4.3 h, 10 Nov to 12 Nov12 Nov 2025 19:15 GMT, 5.3 h3 spills, 26.3 h, 14 Nov to 15 Nov19 Nov 2025 03:45 GMT, 3 h2 spills, 4.8 h, 23 Nov to 24 Nov2 spills, 3.5 h, 28 Nov to 28 Nov2 spills, 55.8 h, 29 Nov to 2 Dec3 spills, 2.8 h, 3 Dec to 3 Dec5 spills, 152 h, 4 Dec to 11 Dec12 Dec 2025 09:15 GMT, 2 h3 spills, 39.5 h, 14 Dec to 16 Dec2 spills, 65 h, 17 Dec to 20 Dec22 Dec 2025 00:15 GMT, 3.8 h

Hours spilling by month, 2025

0200400600800Jan 2025: 601 hours spillingJanFeb 2025: 57 hours spillingFebMar 2025: 12 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 5.0 hours spillingMayJun 2025: 1.2 hours spillingJunJul 2025: 34 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 59 hours spillingSepOct 2025: 44 hours spillingOctNov 2025: 188 hours spillingNovDec 2025: 797 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
5 Jan 2025, 13:30Skelton on Ure Wpc Works3.8 days
5 Dec 2025, 18:00Skelton on Ure Wpc Works3.1 days
5 Dec 2025, 08:30Skelton on Ure Wpc Works3.0 days
27 Jan 2025, 02:00Skelton on Ure Wpc Works2.9 days
17 Dec 2025, 20:45Skelton on Ure Wpc Works2.7 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate30,804 m³range 12,270 - 77,335 m³
In litres30.8 millionrange 12.3 million - 77.3 million L
Olympic swimming pools12at 2,500 m³ each
Organic load, as people's raw sewage46,206person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 491 kg2,772 kg15,467 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,288 kg13,092 kg55,759 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 23 kg194 kg719 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 15 kg80 kg418 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.2 trillion organisms30.8 trillion organisms773.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Skelton on Ure Wpc Works

Storm tank at sewage works · discharges to Scour Gutter

Spills 2025
101 (1,159 hours) · down 31% on 2024
Spills 2024
146 (1,910 hours)
Long-term average
127.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Ure from River Skell to River Tutt (GB104027064161)
Outlet location
SE3550068600 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00284 · 27/22/0060 · company name: SKELTON/STW/3XDWF OVERFLOW

Skelton on Ure Wpc Works

Inlet overflow at sewage works · discharges to Scour Gutter

Spills 2025
70 (639 hours) · down 34% on 2024
Spills 2024
106 (1,147 hours)
Long-term average
77.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Ure from River Skell to River Tutt (GB104027064161)
Outlet location
SE3550068600 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00285 · 27/22/0060 · company name: SKELTON/STW/6XDWF OVERFLOW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.