Storm overflow register · Yorkshire Water

Wetherby sewage works: storm overflow spills 2025

Wetherby sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to River Wharfe. In 2025 it recorded 50 spills totalling 363 hours, against 46 spills and 230 hours in 2024. By hours spilling, it ranks 122 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 22,596 population equivalent (WETHERBY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWetherby Sewage…26 spills, 19 h, 1 Jan to 2 Jan24 spills, 7 h, 3 Jan to 5 Jan37 spills, 57.8 h, 6 Jan to 10 Jan6 spills, 3.3 h, 27 Jan to 28 Jan6 spills, 7.8 h, 22 Mar to 24 Mar4 spills, 2 h, 20 Jul to 20 Jul7 spills, 19.3 h, 20 Sep to 21 Sep6 spills, 4 h, 3 Oct to 3 Oct8 spills, 4.5 h, 19 Oct to 20 Oct50 spills, 27 h, 14 Nov to 17 Nov7 spills, 1.8 h, 23 Nov to 24 Nov90 spills, 36 h, 29 Nov to 4 Dec179 spills, 78.5 h, 4 Dec to 12 Dec180 spills, 95.3 h, 14 Dec to 24 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

050k100k150k200kJan 2025: 87 h spilling ≈ 33,684 m³ (range 13,417-84,564 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 7.8 h spilling ≈ 3,020 m³ (range 1,203-7,582 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 2.0 h spilling ≈ 774 m³ (range 308-1,944 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 19 h spilling ≈ 7,434 m³ (range 2,961-18,662 m³)SepOct 2025: 8.5 h spilling ≈ 3,291 m³ (range 1,311-8,262 m³)OctNov 2025: 43 h spilling ≈ 16,455 m³ (range 6,554-41,310 m³)NovDec 2025: 196 h spilling ≈ 75,885 m³ (range 30,227-190,513 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
6 Jan 2025, 02:45Wetherby Sewage Treatment Works1.9 days6,940 - 43,740 m³
20 Sep 2025, 16:15Wetherby Sewage Treatment Works13.8 h2,120 - 13,365 m³
22 Dec 2025, 08:15Wetherby Sewage Treatment Works8.8 h1,349 - 8,505 m³
21 Dec 2025, 22:15Wetherby Sewage Treatment Works8.0 h1,234 - 7,776 m³
23 Mar 2025, 01:00Wetherby Sewage Treatment Works5.8 h887 - 5,589 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate140,543 m³range 55,981 - 352,838 m³
In litres140.5 millionrange 56.0 million - 352.8 million L
Olympic swimming pools56at 2,500 m³ each
Organic load, as people's raw sewage210,814person-days of untreated BOD

Assumed spill rate while spilling: 42.8 - 270.0 L/s (central 107.5 L/s), from a dry-weather flow of 42.8 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,239 kg12,649 kg70,568 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 5,878 kg59,731 kg254,396 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 106 kg885 kg3,281 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 67 kg365 kg1,905 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 5.6 trillion organisms140.5 trillion organisms3.5 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Wetherby Sewage Treatment Works

Storm tank at sewage works · discharges to River Wharfe

Spills 2025
50 (363 hours) · up 9% on 2024
Spills 2024
46 (230 hours)
Long-term average
57.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed, Bathing Water and/or Shellfish Water investigation ongoing
Improvement
No improvement action in reporting period
Bathing water
Wharfe at Wilderness Carpark
WFD catchment
Wharfe from Collingham Beck to Tadcaster Weir (GB104027064255)
Outlet location
SE4182047048 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00195 · 27/20/0054 · company name: WETHERBY/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.