Storm overflow register · Yorkshire Water

Williamthorpe sewage works: storm overflow spills 2025

Williamthorpe sewage treatment works, run by Yorkshire Water, has 1 monitored storm overflow discharging to Williamthorpe Reservoir. In 2025 it recorded 68 spills totalling 784 hours, against 81 spills and 607 hours in 2024. By hours spilling, it ranks 58 of 283 Yorkshire Water works, where 1 spilled longest.

Works size: 3,903 population equivalent (WILLIAMTHORPE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWilliamthorpe STW6 spills, 16 h, 1 Jan to 1 Jan13 spills, 31.3 h, 5 Jan to 7 Jan2 spills, 6 h, 24 Jan to 24 Jan44 spills, 61.3 h, 26 Jan to 30 Jan31 Jan 2025 03:45 GMT, 60 min4 spills, 5.8 h, 20 Feb to 20 Feb25 spills, 19.5 h, 23 Feb to 24 Feb22 Mar 2025 16:30 GMT, 105 min9 spills, 10.3 h, 27 May to 28 May2 spills, 1.5 h, 6 Jul to 6 Jul2 spills, 2.3 h, 4 Sep to 4 Sep2 spills, 5.8 h, 14 Sep to 14 Sep5 spills, 12.8 h, 17 Sep to 17 Sep7 spills, 19 h, 20 Sep to 21 Sep6 spills, 13.8 h, 3 Oct to 4 Oct19 Oct 2025 20:45 GMT, 3.5 h6 spills, 9.5 h, 23 Oct to 23 Oct7 spills, 11.3 h, 4 Nov to 5 Nov53 spills, 138.5 h, 10 Nov to 17 Nov22 spills, 18.8 h, 18 Nov to 19 Nov22 spills, 23.3 h, 23 Nov to 24 Nov113 spills, 222.5 h, 29 Nov to 12 Dec41 spills, 115.8 h, 15 Dec to 20 Dec23 spills, 33 h, 21 Dec to 23 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60kJan 2025: 116 h spilling ≈ 7,724 m³ (range 3,077-19,392 m³)JanFeb 2025: 25 h spilling ≈ 1,685 m³ (range 671-4,231 m³)FebMar 2025: 1.8 h spilling ≈ 120 m³ (range 48-302 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 10 h spilling ≈ 682 m³ (range 272-1,713 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 1.5 h spilling ≈ 100 m³ (range 40-252 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 40 h spilling ≈ 2,662 m³ (range 1,060-6,682 m³)SepOct 2025: 27 h spilling ≈ 1,792 m³ (range 714-4,500 m³)OctNov 2025: 234 h spilling ≈ 15,649 m³ (range 6,233-39,287 m³)NovDec 2025: 329 h spilling ≈ 22,002 m³ (range 8,764-55,237 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 01:30Williamthorpe STW2.9 days1,865 - 11,753 m³
17 Dec 2025, 20:30Williamthorpe STW2.1 days1,372 - 8,647 m³
1 Dec 2025, 02:30Williamthorpe STW1.9 days1,199 - 7,555 m³
27 Jan 2025, 03:45Williamthorpe STW1.9 days1,192 - 7,513 m³
29 Nov 2025, 04:30Williamthorpe STW1.8 days1,119 - 7,052 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate52,417 m³range 20,879 - 131,595 m³
In litres52.4 millionrange 20.9 million - 131.6 million L
Olympic swimming pools21at 2,500 m³ each
Organic load, as people's raw sewage78,626person-days of untreated BOD

Assumed spill rate while spilling: 7.4 - 46.6 L/s (central 18.6 L/s), from a dry-weather flow of 7.4 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 835 kg4,718 kg26,319 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,192 kg22,277 kg94,880 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 40 kg330 kg1,224 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 25 kg136 kg711 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.1 trillion organisms52.4 trillion organisms1.3 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Williamthorpe STW

Storm tank at sewage works · discharges to Williamthorpe Reservoir

Spills 2025
68 (784 hours) · down 16% on 2024
Spills 2024
81 (607 hours)
Long-term average
85.0 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Spital/Calow/Muster Brook (GB104027057640)
Outlet location
SK4316066500 (OS grid reference) · View on Apple Maps
EA ID / permit
YWS00649 · 2941 · company name: WILLIAMTHORPE/STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Yorkshire Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.