Storm overflow register · Anglian Water

Bassingham sewage works: storm overflow spills 2025

Bassingham sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to River Witham. In 2025 it recorded 48 spills totalling 233 hours, against 57 spills and 591 hours in 2024. By hours spilling, it ranks 95 of 419 Anglian Water works, where 1 spilled longest.

Works size: 2,385 population equivalent (BASSINGHAM STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBassingham Water…116 spills, 110.7 h, 5 Jan to 10 Jan24 Jan 2025 07:40 GMT, 2 min25 Jan 2025 10:16 GMT, 2 min25 spills, 2 h, 27 Jan to 28 Jan2 spills, 0.1 h, 29 Jan to 29 Jan2 Feb 2025 11:24 GMT, 2 min5 Feb 2025 14:32 GMT, 2 min3 spills, 0.4 h, 6 Feb to 6 Feb344 spills, 27.6 h, 8 Feb to 10 Feb16 spills, 2.3 h, 13 Feb to 13 Feb14 Feb 2025 18:46 GMT, 2 min19 Jul 2025 14:00 GMT, 2 min18 spills, 46.6 h, 14 Nov to 17 Nov4 spills, 1.5 h, 23 Nov to 24 Nov30 Nov 2025 10:36 GMT, 32 min3 spills, 0.3 h, 1 Dec to 1 Dec87 spills, 8.6 h, 4 Dec to 6 Dec3 spills, 0.1 h, 7 Dec to 7 Dec101 spills, 7.6 h, 9 Dec to 10 Dec29 spills, 2.8 h, 12 Dec to 13 Dec14 Dec 2025 10:14 GMT, 2 min31 spills, 5.1 h, 15 Dec to 16 Dec74 spills, 13.5 h, 17 Dec to 20 Dec20 spills, 2.4 h, 21 Dec to 22 Dec3 spills, 0.1 h, 23 Dec to 23 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

05,00010k15kJan 2025: 113 h spilling ≈ 4,614 m³ (range 1,838-11,583 m³)JanFeb 2025: 30 h spilling ≈ 1,242 m³ (range 495-3,119 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 49 h spilling ≈ 1,986 m³ (range 791-4,986 m³)NovDec 2025: 41 h spilling ≈ 1,659 m³ (range 661-4,165 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
8 Jan 2025, 00:00Bassingham Water Recycling Centre1.0 days391 - 2,462 m³
7 Jan 2025, 00:00Bassingham Water Recycling Centre1.0 days391 - 2,462 m³
9 Jan 2025, 00:00Bassingham Water Recycling Centre21.5 h351 - 2,209 m³
6 Jan 2025, 02:54Bassingham Water Recycling Centre21.1 h343 - 2,165 m³
14 Nov 2025, 12:16Bassingham Water Recycling Centre11.7 h191 - 1,204 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate9,501 m³range 3,785 - 23,853 m³
In litres9.5 millionrange 3.8 million - 23.9 million L
Olympic swimming pools3.8at 2,500 m³ each
Organic load, as people's raw sewage14,252person-days of untreated BOD

Assumed spill rate while spilling: 4.5 - 28.5 L/s (central 11.4 L/s), from a dry-weather flow of 4.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 151 kg855 kg4,771 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 397 kg4,038 kg17,198 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 7.2 kg60 kg222 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 4.5 kg25 kg129 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 378.5 billion organisms9.5 trillion organisms238.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Bassingham Water Recycling Centre

Inlet overflow at sewage works · discharges to River Witham

Spills 2025
48 (232 hours) · down 16% on 2024
Spills 2024
57 (591 hours)
Long-term average
47.5 spills a year (monitored since 2022)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - Other maintenance / capital works (e.g. jetting)
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation completed
Improvement
Operational improvement ongoing
WFD catchment
Witham - conf Cringle Bk to conf Brant (GB105030056780)
Outlet location
SK9072059820 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00064 · ANNNF10345 · company name: Bassingham WRC

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.